Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-28 Cont ID  
Sent By dhayes Date 2015-05-28 Time 10:01 Rev Time 0.00
Received By dhayes Date 2015-05-28 Time 10:01 Sent To  
Notes
2015-05-28 10:09:04APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1)PROVIDE A PANEL SCHEDULE WITH OCPD AND WIRE SIZES.
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 2) PANEL TO BE USED AS JUNCTION BOX TO COMPLY WITH NEC
 314
  
 3) RACEWAY CONDUIT FILL FOR BRANCH CIRCUITS TO COMPLY
 WITH NEC 310.16, TABLES 4 AND 8, AND ANNEX C.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]