Plan Review Stops For Permit 15050767 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-05-28 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-28 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-05-28 |
Time |
10:01 |
Sent To |
|
|
Notes |
2015-05-28 10:09:04 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1)PROVIDE A PANEL SCHEDULE WITH OCPD AND WIRE SIZES. | | EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY | | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC | | PURPOSE OR USE. NEC 408.4 | | | | 2) PANEL TO BE USED AS JUNCTION BOX TO COMPLY WITH NEC | | 314 | | | | 3) RACEWAY CONDUIT FILL FOR BRANCH CIRCUITS TO COMPLY | | WITH NEC 310.16, TABLES 4 AND 8, AND ANNEX C. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|