Plan Review Details - Permit 15050733
Plan Review Stops For Permit 15050733
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2015-08-21 Time 15:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-13 Cont ID  
Sent By jwitmer Date 2015-07-13 Time 13:13 Rev Time  
Received By jwitmer Date 2015-07-13 Time 12:00 Sent To  
Notes
2015-07-13 13:13:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050733
 ADD: 2749 EXCHANGE CT.
 CONT: CILAS CONCRETE
 TEL: (561-689-39??
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 13/ 2015
 ACTION: DENIED
  
 1) PLEASE DECIDE WHERE THE SCOPE OF THIS PERMIT IS
 GOING TO TAKE PLACE. THE 1ST SUBMITTED PLANS INDICATED
 UNITS C & D. THE 2ND SET OF PLANS NOW INDICATES UNITS A
 & B, WHERE AS THE PERMIT APPLICATION STILL INDICATES
 UNITS C & D. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 107.2.1. ADMINISTRATION,
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION.
  
 2) THE VALUE OF THIS PROJECT IS ALSO TO LOW TO BE
 CONSIDERED A DEMOLITION AND INTERIOR BUILDOUT. THE
 PERMIT APPLICATION INDICATES THE DEMOLITION OF ONE
 WALL. SHEET 1 INDICATES (2) WALLS BEING REMOVED. SHEET
 2 & 3 SHOW NEW WALLS AND ELECTRICAL PLEASE UPDATE THE
 VALUE OF THE PERMIT IF THIS IS TO BE A INTERIOR
 BUILDOUT.
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
  
 3) IF A TENANT IMPROVEMENT SHEETS 2 & 3 FAIL TO PROVIDE
 HOW THE NEW WALLS ARE GOING TO BE CONSTRUCTED. 2010
 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. ALL
 NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 2010 FBC-B 1607.13 INTERIOR WALLS AND PARTITIONS.
 INTERIOR WALLS AND PARTITIONS THAT EXCEED 6 FEET (1829
 MM) IN HEIGHT, INCLUDING THEIR FINISH MATERIALS, SHALL
 HAVE ADEQUATE STRENGTH TO RESIST THE LOADS TO WHICH
 THEY ARE SUBJECTED BUT NOT LESS THAN A HORIZONTAL LOAD
 OF 5 PSF (0.240 KN/M2).
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-18 Cont ID  
Sent By albarran Date 2015-08-18 Time 12:34 Rev Time 0.00
Received By albarran Date 2015-08-18 Time 12:16 Sent To B
Notes
2015-08-18 12:51:30PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. FBC REQUIRES THAT A MINIMUM OF TWO SETS OF DRAWINGS
 BE PROVIDED. ONLY ONE SET WAS SUBMITTED AT THE TIME OF
 THE RESUB.
 2. THE ELECTRICAL COMMENTS PREVIOUSLY MADE AS A RESULT
 OF THE FIRST REVIEW HAVE NOT BEEN ADDRESSED.
 3. YOU WERE INSTRUCTED AT THE TIME OF THE FIRST DENIAL
 ON HOW TO PROPERLY RESUBMIT YOUR CORRECTIONS. I HAVE
 NOT FOUND A RESPONSE LETTER OR NARRATIVE ADDRESSING THE
 ELECTRICAL COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-20 Cont ID  
Sent By albarran Date 2015-07-20 Time 12:49 Rev Time 0.00
Received By albarran Date 2015-07-20 Time 12:35 Sent To I
Notes
2015-07-20 12:54:10PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. PER NEC 600.5, PROVIDE A DEDICATED SIGN OUTLET AT
 EACH ENTRANCE.
 2. PER NEC 220.16, PROVIDE LOAD CALCS FOR THE ADDITION
 OF NEW LOADS TO AN EXISTING SERVICE.
 3. PER NEC 408.4, PROVIDE A PANEL SCHEDULE
 4. PER FBC-E 505, PROVIDE A COMPLIANT LIGHTING DESIGN.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By pleduc Date 2015-06-25 Time   Rev Time 0.00
Received By pleduc Date 2015-06-25 Time 16:02 Sent To  
Notes
2015-06-25 16:07:07THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 EXIT SIGNS AND FIRE EXTINGUISHER LOCATIONS SHALL BE
 VERIFIED BY THE FIRE INSPECTOR ON INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-19 Cont ID  
Sent By pleduc Date 2015-05-19 Time   Rev Time 0.00
Received By pleduc Date 2015-05-19 Time 15:18 Sent To  
Notes
2015-05-19 15:28:45THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 EXIT SIGNS AND FIRE EXTINGUISHER LOCATIONS SHALL BE
 VERIFIED BY THE FIRE INSPECTOR ON INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 15:39 Rev Time 0.00
Received By jwitmer Date 2015-08-14 Time 10:51 Sent To  
Notes
2015-08-14 10:51:37RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-20 Cont ID  
Sent By albarran Date 2015-07-20 Time 13:01 Rev Time 0.00
Received By albarran Date 2015-06-24 Time 09:25 Sent To  
Notes
2015-07-20 13:08:277/20/15 - FAILED ELECTRICAL & BLDG. REVIEWS. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "C". MA
2015-06-24 09:26:07NEW PLANS SUBMITTED TO REPLACE ORIGINAL INCORRECT
 PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-19 Cont ID  
Sent By skennedy Date 2015-06-19 Time 11:18 Rev Time  
Received By skennedy Date 2015-05-18 Time   Sent To  
Notes
2015-06-19 11:19:40MARIE NICHOLS, TENENT INDICATED JOB IS CANCELLED.
2015-05-18 17:45:44SENT TO B10 BOX.