Plan Review Details - Permit 15050732
Plan Review Stops For Permit 15050732
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-06 Cont ID  
Sent By jwitmer Date 2015-06-06 Time 16:42 Rev Time 0.00
Received By jwitmer Date 2015-06-06 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-26 Cont ID  
Sent By rlecky Date 2015-05-26 Time 13:23 Rev Time 0.00
Received By rlecky Date 2015-05-26 Time 13:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-29 Cont ID  
Sent By scaldero Date 2015-05-29 Time 11:22 Rev Time 0.00
Received By scaldero Date 2015-05-29 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-20 Cont ID  
Sent By tklarge Date 2015-06-20 Time 08:57 Rev Time 0.00
Received By tklarge Date 2015-06-19 Time 16:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-18 Cont ID  
Sent By tklarge Date 2015-06-18 Time 08:00 Rev Time 0.00
Received By tklarge Date 2015-06-12 Time 15:41 Sent To  
Notes
2015-06-15 15:43:19SENT TO CHRIS COLE FOR MECHANICAL REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-18 Cont ID  
Sent By ajones Date 2015-06-18 Time 08:01 Rev Time 0.00
Received By tklarge Date 2015-05-18 Time 18:29 Sent To  
Notes
2015-05-18 17:42:46SENT TO B03.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-16 Cont ID  
Sent By ccole Date 2015-06-16 Time 13:42 Rev Time 0.00
Received By ccole Date 2015-06-16 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By ccole Date 2015-06-10 Time 15:09 Rev Time 0.00
Received By ccole Date 2015-06-10 Time 15:09 Sent To  
Notes
2015-06-10 15:43:171ST REVIEW: FBC 2010 MECHANICAL
  
 1) MINIMUM VENTILATION CALCULATIONS ARE REQUIRED FOR
 THE PROPOSED NEW FOOT MASSAGE BUSINESS IN COMPLIANCE
 WITH SECTION 709.1 FBC-10 EXISTING BUILDING. PLEASE SEE
 TABLE 403.3 FBC-10 MECHANICAL AND PROVIDE A TABLE ON
 THE PLAN INDICATING THE TOTAL CFM'S OF REQUIRED OUTDOOR
 AIR, AND THE TOTAL OUTDOOR AIR THAT IS BEING PROVIDED
 TO THE SPACES BY THE EXISTING SYSTEMS, OR BY ANY
 PROPOSED NEW SYSTEMS.
 2) PROVIDE AN AC LAYOUT PLAN INDICATING THE LOCATIONS
 OF ALL SUPPLY AND RETURN DUCTS, DIFFUSERS AND GRILLS.
 PROVIDE NOTES AND SYMBOLS ON THE PLAN TO CLEARLY
 INDICATE WHAT COMPONENTS ARE EXISTING, RELOCATED, OR
 NEWLY INSTALLED.
 3) PLEASE REMOVE THE SUBMITTED MANUAL J AC
 CALCULATIONS. ACCA MANUAL J IS A CALCULATION METHOD FOR
 RESIDENTIAL AC SYSTEMS. IF NEW AC SYSTEM IS PROPOSED,
 THE SIZING CALCULATION SHALL BE PERFORMED IN ACCORDANCE
 WITH ACCA MANUAL N OR ASHRAE STANDARD 183- SECTION
 503.2.1 FBC-10 ENERGY CONSERVATION
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-06-20 Cont ID  
Sent By tklarge Date 2015-06-20 Time 08:57 Rev Time 0.00
Received By tklarge Date 2015-06-20 Time 08:45 Sent To  
Notes
2015-06-19 16:59:10ROUTED TO PLUMBING/CC

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-06-18 Cont ID  
Sent By tklarge Date 2015-06-18 Time 08:00 Rev Time 0.00
Received By tklarge Date 2015-06-18 Time 06:50 Sent To  
Notes
2015-06-18 08:00:061) SHT. S-1 - ZONING & OCCUPANCY BOX - SHOWS THE
 OCCUPANCY TYPE AS MERCANTILE AND THE GENERAL BUILDING
 CODE ANALYSIS BOX ON E-1 NOTES THE OCCUPANCY AS
 BUSINESS.CLARIFY. ALSO, THE INFORMATION IN THE GENERAL
 BUILDING CODE ANALYSIS BOX ON SHT. E-1 DOES NOT APPEAR
 TO BE FOR THIS SPACE. THE TENANT SPACE IS LISTED AS
 6300 SQ.FT. AND SHT. S-1 NOTES THIS SPACE AS 1300 SQ.
 FT. IF DOES NOT APPLY TO THIS SPACE THEN DELETE IT FROM
 THE PLANS.
 2) THIS OCCUPANCY SHALL BE CLASSIFIED PER SEC. 302 OF
 THE 2010 - FBC-BUILDING.INDICATE THE CORRECT OCCUPANCY
 ON BOTH SHEETS OF BOTH SETS OF PLANS.
 3) THERE IS ALSO A DISCREPANCY IN THE TYPE OF
 CONSTRUCTION ON THE PLANS.SHT. S-1 NOTES THE TYPE OF
 CONSTRUCTION AS TYPE III ( IN THE ZONING & OCCUPANCY
 BOX) & AS TYPE IIB ( IN THE CODE INFORMATION BOX). WHAT
 TYPE OF CONSTRUCTION IS IT? SHT. E-1 SHOWS THE TYPE OF
 CONSTRUCTION AS IIB IN THE GENERAL BUILDING CODE
 ANALYSIS BOX. THE TYPE OF CONSRTUCTION SHALL BE THE
 SAME ON ALL SHEETS. REVISE THE INFORMATION ON ALL
 SHEETS TO MATCH.
 4) THE NEW P-1 SHEET THAT WAS SUBMITTED SHOWS THE
 OCCUPANCY CLASSIFICATION AS "BUSINESS" AND
 "MERCANTILE". CLARIFY. THIS DOES NOT APPEAR TO BE A
 MIXED OCCUPANCY AND IT IS NOT A MERCANTILE
 OCCUPANCY.REVISE ALL THE SHEETS TO REFLECT THE CORRECT
 OCCUPANCY OF THIS SPACE AND THE CORRECT TYPE OF
 CONSTRUCTION.
 5) THE FLOOR DRAIN SHALL BE EQUIPPED WITH A FLOOR
 DRAIN.SHOW THIS ON THE PLAN.
 6) THERE IS NO CONNECTION OF THE HOT WATER LINE SHOWN
 AT THE HOT WATER HEATER. CLARIFY.
  
 NOTE: CORRECTIONS SHALL BE MADE TO ALL THE SHEETS ON
 BOTH SETS OF PLANS.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-09 Cont ID  
Sent By tklarge Date 2015-06-09 Time 09:48 Rev Time 0.00
Received By tklarge Date 2015-06-09 Time 09:15 Sent To  
Notes
2015-06-09 09:28:011) SUBMIT A WATER RISER FOR REVIEW. WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
 2) THE WASHING MACHINE SHALL BE ON A 3 INCH STACK PER
 THE 2010 FPC SEC.406.3.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 MANUAL FOR THE TANKLESS WATER HEATER. WPB AMEND.TO 2010
 FBC SEC. 107.2.1.
 4) CLEANOUTS ARE REQUIRED IN WASTE STACKS PER 2010 FPC
 SEC.708.3.4.
 5) THE SINK IN THE BREAK ROOM SHALL COMPLY WITH THE FL.
 ACCESS. CODE SEC. 212, 606.1- 606.5. THE MAXIMUM HEIGHT
 SHALL BE 34 INCHES. SHOW THIS ON BOTH SETS OF PLANS.
 6) SHT. S-1 SHOWS THE OCCUPANCY TYPE AS MERCANTILE AND
 THE GENERAL BUILDING CODE ANALYSIS BOX ON E-1 NOTES THE
 OCCUPANCY AS BUSINESS.CLARIFY. ALSO, THE BOX ON SHT.
 E-1 DOES NOT APPEAR TO BE FOR THIS SPACE. THE TENANT
 SPACE IS LISTED AS 6300 SQ.FT. AND SHT. S-1 NOTES THIS
 SPACE AS 1300 SQ. FT.THERE IS ALSO A DIS
 7) THIS OCCUPANCY SHALL BE CLASSIFIED PER SEC. 302 OF
 THE 2010 - FBC-BUILDING.INDICATE THE CORRECT OCCUPANCY
 ON BOTH SHEETS OF BOTH SETS OF PLANS.
 8) THERE IS ALSO A DISCREPANCY IN THE TYPE OF
 CONSTRUCTION ON THE PLANS.SHT. S-1 NOTES THE TYPE OF
 CONSTRUCTION AS TYPE III (ZONING 7 OCCUPANCY BOX) & AS
 TYPE IIB (CODE INFORMATION BOX) AND AS TYPE IIB ON SHT.
 E-1. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-29 Cont ID  
Sent By ajones Date 2015-05-29 Time 08:40 Rev Time 0.00
Received By ajones Date 2015-05-29 Time 08:40 Sent To  
Notes
***NONE***