Plan Review Details - Permit 15050705
Plan Review Stops For Permit 15050705
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-02 Cont ID  
Sent By albarran Date 2015-06-02 Time 15:35 Rev Time 0.00
Received By albarran Date 2015-06-02 Time 15:15 Sent To I
Notes
2015-06-02 15:36:30APPROVED AS NOTED BELOW:
 IMPORTANT NOTICE:
 1. PROPER GROUND COVER OVER RACEWAYS & CONDUCTOR
 INSULATION AS INDICATED IN NEC 300.5 WILL BE REQUIRED &
 VERIFIED. NO SITE TUBES FOR TRENCH INSPECTION
 2. GROUNDING ELECTRODE CONDUCTOR PER NEC 250.66 (#4)
 3. INTER-SYSTEM BONDING TERMINAL PER NEC 250.94
 4. GROUNDING ELECTRODE SYSTEM TO BE REPAIRED/CORRECTED
 TO COMPLY W/NEC 250.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-02 Cont ID  
Sent By albarran Date 2015-06-02 Time 15:37 Rev Time  
Received By albarran Date 2015-05-18 Time   Sent To  
Notes
2015-06-02 15:49:10I'VE TRIED CALLING R GOOD ELECTRIC AT THE NUMBER ON THE
 PERMIT AND IN THE SYSTEM AND NONE SEEM TO WORK. I
 CONTINUE TO GET CRAFTMASTER POOL.APPARENTLY THEY ARE
 TIED TOGETHER. I NOTIFIED THEM OF THE STATUS AND
 BALANCE ON THIS PERMIT.
  
2015-05-18 17:21:16SENT TO <$5K ELECTRICAL BOX.