Plan Review Details - Permit 15050702
Plan Review Stops For Permit 15050702
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-04 Cont ID  
Sent By albarran Date 2015-06-04 Time 09:30 Rev Time 0.00
Received By albarran Date 2015-06-04 Time 09:22 Sent To I
Notes
2015-06-04 09:35:17CONTRACTOR SENT ME REVISED LOAD CALCS INDICATING THE
 USE OF A 48KW GENERATOR

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-02 Cont ID  
Sent By albarran Date 2015-06-02 Time 18:46 Rev Time 0.00
Received By albarran Date 2015-06-02 Time 18:28 Sent To I
Notes
2015-06-02 18:53:03THE LOAD CALCS YOU SUBMITTED CALL FOR A 60KW GENERATOR,
 YOUR SUBMITTAL PACKAGE REFLECTS A 48 KW UNIT. YOU WILL
 NEED THE AUXILIARY TRANSFER SWITCH CONTACT KIT TO SHED
 UNNECESSARY LOAD UNDER EMERGENCY CONDITIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-04 Cont ID  
Sent By albarran Date 2015-06-04 Time 09:42 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-06-04 09:42:59SMALL READY "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-02 Cont ID  
Sent By albarran Date 2015-06-02 Time 18:55 Rev Time 0.00
Received By albarran Date 2015-05-18 Time   Sent To  
Notes
2015-06-02 18:56:54FAILED ZONING & ELECTRICAL REVIEWS. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "M".
2015-05-18 17:22:44ZONING BOX.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-15 Cont ID  
Sent By sgraham Date 2015-06-15 Time   Rev Time 0.00
Received By sgraham Date 2015-06-15 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-20 Cont ID  
Sent By sgraham Date 2015-05-20 Time 12:28 Rev Time 0.00
Received By sgraham Date 2015-05-20 Time 12:28 Sent To E
Notes
2015-05-20 12:29:495/20/15 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE SURVEYS HIGHLIGHTING THE
 LOCATION OF GENERATOR.