Plan Review Details - Permit 15050695
Plan Review Stops For Permit 15050695
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2016-04-05 Cont ID  
Sent By cthroop Date 2016-04-05 Time 11:35 Rev Time 0.00
Received By cthroop Date 2016-04-05 Time 11:35 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-03-08 Cont ID  
Sent By cthroop Date 2016-03-08 Time 13:31 Rev Time 0.00
Received By cthroop Date 2016-03-08 Time 13:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-01-19 Cont ID  
Sent By cthroop Date 2016-01-19 Time 14:57 Rev Time 0.00
Received By cthroop Date 2016-01-19 Time 14:57 Sent To  
Notes
2016-01-19 15:07:53CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 4TH BUILDING REVIEW.
  
 THE FOLLOWING REVIEW COMMENTS FROM THE PREVIOUS THREE
 (3) REVIEWS HAVE NOT BEEN ADDRESSED.
 FLORIDA STATUTE 553.80 (2) (B) MANDATES THE APPLICATION
 OF 4 TIMES THE ORIGINAL PLAN REVIEW FEE BE APPLIED TO
 THIS APPLICATION.
  
 PROVIDE RESPONSES TO THE FOLLOWING ITEMS:
 1. ROOFING - PROVIDE PRODUCT APPROVALS.
 2. PROVIDE DETAIL FOR NEW CONCRETE FLOOR.
 3. PROVIDE DETAIL FOR THE APPLICATION OF STUCCO.
 4. PROVIDE DETAIL FOR ROOF OVERHANG.
 5. CONFLICT BETWEEN SHEET A-1, BLDG. C "NEW WORK" AND
 SHEET E-1, BLDG. C "NO CHANGES".
 6. CONFLICT BETWEEN INSULATION VALUES ON PLAN -VS-
 ENERGY SUBMITTAL.
  
 NOTE: THIS PLAN REMAINS DEFICIENT. ENGINEER OF RECORD
 SHOULD FULLY RE-EVALUATE PLAN PRIOR TO RE-SUBMITTAL.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-02 Cont ID  
Sent By skennedy Date 2015-10-02 Time 10:45 Rev Time 0.00
Received By skennedy Date 2015-10-02 Time 09:19 Sent To  
Notes
2015-10-02 10:42:533RD REVIEW: FBC 2010
  
 THE PLANS DO NOT CONTAIN SUFFICIENT CLARITY TO INDICATE
 THE WORK PROPOSED OR SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 PLEASE RESOLVE THE FOLLOWING CONFLICTS OR PROVIDE
 ADDITIONAL DETAIL IN THE SUBMITTED DRAWINGS AS FOLLOWS:
  
 1. INCORPORATE SHEET S-0 INTO THE DRAWING SET IF IT IS
 INTENDED THAT IT REMAIN PART OF THE SUBMITTAL.
 2. SHEET S-0 INDICATES BUILDING C WILL HAVE NO WORK
 DONE ON IT YET SHEET S-1 STATES "NEW WORK IN THIS
 BUILDING."
 3. SHEET S-1 FLOOR PLAN SHOWS A SECTION A IS ON SHEET
 S-1 BUT NO SECTION A EXIST.
 4. SHEET S-1 INDICATES NEW CONCRETE FLOOR BUT HAS NO
 DETAIL.
 5. INSULATION VALUES ON PLAN V. ENERGY SUBMITTAL
 CONFLICT.
 6. INADEQUATE DETAILS ARE PROVIDED FOR THE APPLICATION
 OF STUCCO.
 7. COVERED PATION FOUNDATION DETAILS LACK BASIC
 REEQUIRED INFORMATION.
 8. ELEVATIONS AND DETAILS PROVIDED ARE NOT COORDINATED
 WITH PLAN.
  
 NOTE; IN GENERAL, THIS PLAN IS DEFICIENT TO THE POINT
 THAT A REVIEW CANNOT BE EFFICIENTLY PERFORMED. IT IS
 SUFFICIENT TO STATE THAT THE ENGINERE OF RECORD SHOULD
 FULLY RE-EVALUATE THIS PLAN.
  
  
 GENERAL COMMENTS FROM 1ST & 2ND REVIEW ARE BELOW:
  
  
 MINIMUM PLAN REVIEW CRITERIA SHALL BE PROVIDED PER FBC
 107 TO INCLUDE BUT NOT LIMITED TO:
  
 1.AN ENERGY SUBMITTAL
  
 2.PRODUCT APPROVALS FOR WINDOWS & ROOFING FBC 107.3.4 -
 PROVIDE PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR SUBMITTALS.
  
 3.STRUCTURAL DETAILS FOR THE NEW OVERHANGS
  
 4. OPEN CONDITION WHERE EXISTING SHUTTERS ARE PROPOSED
 TO BE REMOVED
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-07 Cont ID  
Sent By skennedy Date 2015-08-07 Time 13:07 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 13:07 Sent To  
Notes
2015-08-07 13:12:152ND REVIEW: FBC 2010
  
 THE REVIEW COMMENTS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED. ONE SHEET WAS RE-SUBMITTED AND WAS RETRIEVED
 BY THE APPLICANT THIS DATE. ESSIENTIALLY, THE
 RE-SUBMITTAL ACCOMPLISHED NOTHING EXCEPT A MEETING SUCH
 THAT THE INADEQUACY OF THE INITIAL SUBMITTAL AND THE
 RE-SUBMITTAL COULD BE EXPLAINED TO THE DRAFTSMAN AND
 THE CONTRACTOR REPRESENTATIVE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 15:10 Rev Time 0.00
Received By skennedy Date 2015-07-08 Time 14:07 Sent To  
Notes
2015-07-08 15:30:561ST REVIEW: FBC 2010
  
 THE PLANS DO NOT CONTAIN SUFFICIENT CLARITY TO INDICATE
 THE WORK PROPOSED OR SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 MINIMUM PLAN REVIEW CRITERIA SHALL BE PROVIDED PER FBC
 107 TO INCLUDE BUT NOT LIMITED TO:
  
 1.AN ENERGY SUBMITTAL
  
 2.PRODUCT APPROVALS FOR WINDOWS & ROOFING FBC 107.3.4 -
 PROVIDE PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH ARE
 REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR SUBMITTALS.
  
 3.STRUCTURAL DETAILS FOR THE NEW OVERHANGS
  
 4. OPEN CONDITION WHERE EXISTING SHUTTERS ARE PROPOSED
 TO BE REMOVED
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-05 Time 18:41 Rev Time 0.00
Received By albarran Date 2016-04-05 Time 18:35 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-04 Time 18:35 Rev Time 0.00
Received By albarran Date 2016-04-04 Time 17:34 Sent To  
Notes
2016-04-04 18:39:58AN ELECTRICAL STOP HAD NOT BEEN ADDED TO THE REVIEWS
 BECAUSE THIS WAS TAKEN IT WITHOUT MENTIONING THE CHANGE
 TO THE ELECTRICAL PLAN. I PASSED THE ELECTRICAL REVIEW
 THOUGH THE LOAD CALCS WERE NOT CORRECT, THE 200 AMP
 SERVICE IS AMPLE FOR THE LOAD. THE FILE WAS HAND
 DELIVERED TO CT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-02-24 Cont ID  
Sent By albarran Date 2016-02-24 Time 19:02 Rev Time 0.00
Received By albarran Date 2016-02-24 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-01-21 Cont ID  
Sent By mvaldes Date 2016-01-21 Time 11:25 Rev Time 0.00
Received By mvaldes Date 2016-01-21 Time 11:25 Sent To  
Notes
2016-01-21 11:41:01JOB PERMIT NUMBER: 15050695
 JOB ADDRESS: 616 CLAREMORE DR
 WEST PALM BEACH
 DATE: JAN 21 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. PANEL B IS SHOWN AS 200 AMPS ON RISER DIAGRAM
 DOESN?T MATCH BUILDING B WHICH STATES 150 AMPS AND IS
 NON ?COMPLIANT ACCORDING TO DEMAND LOAD CALCULATIONS.
 FBC-R E3704.2
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-23 Cont ID  
Sent By skennedy Date 2015-10-23 Time 11:39 Rev Time 0.00
Received By skennedy Date 2015-10-23 Time 11:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-29 Cont ID  
Sent By albarran Date 2015-06-29 Time 18:43 Rev Time 0.00
Received By albarran Date 2015-06-29 Time 18:07 Sent To  
Notes
2015-06-29 18:49:24LIMITED APPROVAL ON THIS PERMIT AS MARKED ON PLANS. THE
 SUBMITTED DRAWINGS INCLUDE A POOL AND SUPPORTING
 EQUIPMENT AS WELL AS INDICATION OF NEW ELECTRICAL
 PANEL; NONE OF WHICH IS ADDRESSED ON THE PERMIT
 APPLICATION, THEREFORE NOT INCLUDED AS PER THE SCOPE OF
 WORK ALLOWED.
 SHALL COMPLY WITH THE SMOKE DETECTOR REQUIREMENTS OF
 FBC-R 314

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2016-03-08 Cont ID  
Sent By fmittner Date 2016-03-08 Time 11:18 Rev Time 0.00
Received By fmittner Date 2016-03-08 Time 11:18 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-12-11 Cont ID  
Sent By fmittner Date 2015-12-11 Time 15:55 Rev Time 0.00
Received By fmittner Date 2015-12-11 Time 15:55 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By fmittner Date 2015-10-06 Time 10:56 Rev Time 0.00
Received By fmittner Date 2015-10-06 Time 10:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-06-04 Cont ID  
Sent By fmittner Date 2015-06-04 Time 16:24 Rev Time 0.00
Received By fmittner Date 2015-06-04 Time 16:24 Sent To  
Notes
2015-06-04 16:25:35CHANGES TO FRONT FACADE REQUIRE COA SUBMITTAL. OPENING
 SIZES/SHAPES SHALL NOT BE CHANGED. QUESTIONS CONTACT
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2016-04-05 Cont ID  
Sent By albarran Date 2016-04-05 Time 18:42 Rev Time 0.00
Received By albarran Date 2016-04-05 Time 11:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2016-04-05 Cont ID  
Sent By cthroop Date 2016-04-05 Time 11:29 Rev Time 0.00
Received By cthroop Date 2016-03-22 Time 10:02 Sent To  
Notes
2016-03-23 10:02:21R24

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-03-08 Cont ID  
Sent By cthroop Date 2016-03-08 Time 15:18 Rev Time 0.00
Received By cthroop Date 2016-02-10 Time 09:39 Sent To  
Notes
2016-02-11 09:39:57R22

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-22 Cont ID  
Sent By ccole Date 2016-01-22 Time 16:59 Rev Time 0.00
Received By ccole Date 2015-12-01 Time 09:47 Sent To  
Notes
2015-12-02 09:48:05R10

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-23 Cont ID  
Sent By skennedy Date 2015-10-23 Time 11:39 Rev Time 0.00
Received By skennedy Date 2015-09-08 Time 09:24 Sent To  
Notes
2015-09-09 09:24:44RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-07 Cont ID  
Sent By skennedy Date 2015-08-07 Time 13:08 Rev Time 0.00
Received By skennedy Date 2015-07-20 Time 13:59 Sent To  
Notes
2015-07-23 13:59:43ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 15:32 Rev Time  
Received By skennedy Date 2015-05-18 Time   Sent To  
Notes
2015-05-19 09:05:21EXPEDITED!!! SENT TO R10.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2016-04-07 Cont ID  
Sent By skennedy Date 2016-04-07 Time 16:40 Rev Time 0.00
Received By skennedy Date 2016-04-07 Time 16:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-04-05 Cont ID  
Sent By cthroop Date 2016-04-05 Time 11:32 Rev Time 0.00
Received By cthroop Date 2016-04-05 Time 11:32 Sent To  
Notes
2016-04-05 11:35:186TH REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-01-22 Cont ID  
Sent By ccole Date 2016-01-22 Time 16:58 Rev Time 0.00
Received By ccole Date 2016-01-22 Time 16:58 Sent To  
Notes
2016-01-22 16:58:36PERMIT #15050695
 1/22/16
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-08-07 Cont ID  
Sent By skennedy Date 2015-08-07 Time 13:07 Rev Time 0.00
Received By skennedy Date 2015-08-07 Time 13:07 Sent To  
Notes
2015-08-07 13:08:521ST REVIEW: FBC 2010
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2016-03-08 Cont ID  
Sent By skennedy Date 2016-03-08 Time 14:07 Rev Time 0.00
Received By skennedy Date 2016-03-08 Time 14:07 Sent To  
Notes
2016-03-08 14:11:22FBC 2010 RESIDENTIAL M
  
 PROVISIONALLY APPROVED WITH ASSUMPTION SHEET E-1 ONLY
 WILL BE RESUBMITTED TO RESOLVE FLOOR PLAN CONFLICT
 LAUNDRY V. BATH.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-02-29 Cont ID  
Sent By ccole Date 2016-02-29 Time 15:01 Rev Time 0.00
Received By ccole Date 2016-02-29 Time 15:01 Sent To  
Notes
2016-02-29 15:01:194TH REVIEW: FBC 2014 MECHANICAL
 PERMIT #15050695
 2/29/16
  
 1) AS PREVIOUSLY REQUESTED SUBMIT AC PLANS FOR THE
 PROPOSED PROIECT
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-01-22 Cont ID  
Sent By ccole Date 2016-01-22 Time 16:55 Rev Time 0.00
Received By ccole Date 2016-01-22 Time 16:55 Sent To  
Notes
2016-01-22 16:56:541ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15050695
 1/22/16
  
 1) PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW. NO PLANS
 WERE SUBMITTED WITH THE PLAN SETS AND THE AC
 CALCULATIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-02 Cont ID  
Sent By ccole Date 2015-10-02 Time 14:36 Rev Time 0.00
Received By ccole Date 2015-10-02 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 15:31 Rev Time 0.00
Received By skennedy Date 2015-07-08 Time 15:31 Sent To  
Notes
2015-07-08 15:34:471ST REVIEW: FBC 2010
  
 FBC 107 PROVIDE MECHAMICAL PLAN, EQUIPMENT SCHEDULE,
 ENERGY AND SIZING CALCULATIONS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2016-04-01 Cont ID  
Sent By gjohnson Date 2016-04-01 Time 14:17 Rev Time 0.00
Received By gjohnson Date 2016-04-01 Time 14:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2016-02-20 Cont ID  
Sent By tklarge Date 2016-02-20 Time 04:22 Rev Time 0.00
Received By tklarge Date 2016-02-20 Time 03:50 Sent To  
Notes
2016-02-20 04:07:061) ONE SET OF THE REVISED PLANS IS MISSING SHT. #3 AND
 THE OTHER SET HAS SHT. #3 DATED 11/22/15 WHICH HAS NOT
 BEEN CORRECTED. SUBMIT TWO REVISED SETS OF PLANS
 SHOWING THE ENTIRE SCOPE OF PLUMBING WORK TO BE DONE IN
 ALL BUILDINGS. IF NO PLUMBING WORK IS TO BE PERFORMED
 IN A STRUCTURE, CLEARLY NOTE IT ON THE PLANS. 2014 FBC
 SEC. 107.2.1.
 2) SHT. A-1 SHOWS A NEW BATHROOM AND SHT. E-1 SHOWS A
 LAUNDRY ROOM IN THE SAME LOCATION. CLARIFY. 2ND
 REQUEST.
 3) SHT. A-1 SHOWS SHELVES IN THE BATHROOM NEXT TO THE
 KITCHEN AND SHT. E-1 SHOWS A NEW SHOWER IN THE SAME
 LOCATION. CLARIFY. 2ND REQUEST.
 4) PROVIDE AN EXISTING FLOOR PLAN. 2014 FBC SEC.
 107.2.1.
 5) INDICATE ON THE PLANS IF ANY NEW PLUMBING WORK WILL
 BE DONE IN BUILDING A.2ND REQUEST.
 6) PROVIDE A RISER DIAGRAM THAT MATCHES THE FLOOR PLAN
 AND SHOWING ALL FIXTURES FOR ALL NEW PLUMBING WORK TO
 BE DONE IN EACH BUILDING. 2014 FBC SEC. 107.2.1. 2ND
 REQUEST.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-12-06 Cont ID  
Sent By gjohnson Date 2015-12-06 Time 09:34 Rev Time 0.00
Received By gjohnson Date 2015-12-06 Time 09:34 Sent To  
Notes
2015-12-06 09:50:463RD REVIEW: FBC 2010
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.SHEET A-1 SHOWS A NEW BATHROOM. SHEET E-1 SHOWS A
 LAUNDRYROOM IN SAME LOCATION PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
 2.SHEET A-1 SHOWS SHELVES IN BATHROOM NEXT TO KITCHEN .
 SHEET E-1 SHOWS A NEW SHOWER IN THAT SAME LOCATION
 PLEASE CLARIFY.
 PER WPB AMEND. TO FBC SEC 107.2.1
 3.PLEASE PROVIDE EXISTING FLOOR PLAN.
 PER WPB AMEND. TO FBC SEC 107.2.1
 4. PLEASE CLARIFY IS THERE ANY PLUMBING WORK BEING DONE
 IN BUILDING A.
 PER WPB AMEND. TO FBC SEC 107.2.1
 5. PLEASE PROVIDE A SINGLE RISER DIAGRAM MATCHING THE
 FLOOR PLAN AND SHOWING ALL FIXTURES.
 PER WPB AMEND. TO FBC SEC 107.2.1
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-04 Cont ID  
Sent By tklarge Date 2015-10-04 Time 03:34 Rev Time 0.00
Received By tklarge Date 2015-10-04 Time 03:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-10 Cont ID  
Sent By tklarge Date 2015-06-10 Time 05:26 Rev Time 0.00
Received By tklarge Date 2015-06-10 Time 05:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2016-03-08 Cont ID  
Sent By cthroop Date 2016-03-08 Time 15:19 Rev Time 0.00
Received By cthroop Date 2016-03-08 Time 15:19 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-01-19 Cont ID  
Sent By cthroop Date 2016-01-19 Time 14:40 Rev Time 0.00
Received By cthroop Date 2016-01-19 Time 14:40 Sent To  
Notes
2016-01-19 14:43:04CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PREVIOUS REQUEST FOR PRODUCT APPROVALS NOT ADDRESSED.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By skennedy Date 2015-07-08 Time 15:32 Rev Time 0.00
Received By skennedy Date 2015-07-08 Time 15:32 Sent To  
Notes
2015-07-08 15:33:261ST REVIEW: FBC 2010
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2016-03-08 Cont ID  
Sent By fmittner Date 2016-03-08 Time 11:18 Rev Time 0.00
Received By fmittner Date 2016-03-08 Time 11:18 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2015-12-11 Cont ID  
Sent By fmittner Date 2015-12-11 Time 15:56 Rev Time 0.00
Received By fmittner Date 2015-12-11 Time 15:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-10-06 Cont ID  
Sent By fmittner Date 2015-10-06 Time 10:56 Rev Time 0.00
Received By fmittner Date 2015-10-06 Time 10:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-04 Cont ID  
Sent By fmittner Date 2015-06-04 Time 16:25 Rev Time 0.00
Received By fmittner Date 2015-06-04 Time 16:25 Sent To  
Notes
***NONE***