Plan Review Details - Permit 15050694
Plan Review Stops For Permit 15050694
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-01-21 Cont ID  
Sent By rmcdouga Date 2016-01-21 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2016-01-21 Time 08:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-11 Cont ID  
Sent By rmcdouga Date 2016-01-11 Time 08:02 Rev Time 0.00
Received By rmcdouga Date 2016-01-11 Time 07:39 Sent To  
Notes
2016-01-11 08:17:44PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE STRUCTURAL ENGINEER, W. ERIK GENZ.
  
 2) STRAPS AND CONNECTORS SHALL BE USED TO PROVIDE A
 CONTINOUS LOAD PATH FROM THE ROOF TO THE FOUNDATION.
 FBC-R 301.1
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-19 Cont ID  
Sent By rmcdouga Date 2015-05-19 Time 17:36 Rev Time 0.00
Received By rmcdouga Date 2015-05-19 Time 17:36 Sent To Z
Notes
2015-05-19 17:25:47PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SCOPE OF WORK SHOWN ON THE PLANS IS MORE THAN
 THE $2400.00 VALUE FOR REFRAMING DAMAGED WALLS THAT IS
 SPECIFIED ON THE PERMIT APPLICATION. PLEASE CLEARLY
 SPECIFY THE COMPLETE SCOPE OF WORK ON THE PLANS AND
 APPLICATION. INCREASE THE VALUE OF WORK ACCORDINGLY.
 FBC 107.2.1 & 109.3
  
 2) SHOW COMPLIANCE WITH FBC-R 704. IN ORDER TO PROVIDE
 FOR INSPECTION FOR TERMITE INFESTATION, CLEARANCE
 BETWEEN EXTERIOR WALL COVERINGS AND FINAL EARTH GRADE
 ON THE EXTERIOR OF A BUILDING SHALL NOT BE LESS THAN 6
 INCHES. INSTALL A STUCCO WEEP SCREED AT OR BELOW THE
 FOUNDATION PLATE LINE AS REQUIRED BY ASTM C 1063.
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT WINDOW/GLASS TYPES, STRUCTURAL MULLIONS
 AND EXTERIOR DOOR TYPES.
  
 4) IF STORM PANELS WILL BE USED, SUBMIT TWO SETS OF
 PRODUCT APPROVALS THAT HAVE BEEN REVIEWED AND APPROVED
 IN WRITING BY THE DESIGNER OF RECORD. FBC - R 301.2.1.2
 SUBMIT TWO COPIES OF AN INSTALLATION SCHEDULE AND KEY
 PLAN FOR THE STORM PANELS. SPECIFY THE OPENING SIZE,
 THE WIND PRESSURES, TYPE OF ANCHOR, ANCHOR SPACING,
 EDGE DISTANCE, PANEL LENGTH, PANEL SPAN, SEPARATION
 DISTANCE FROM PANEL TO GLASS AND THE APPLICABLE SECTION
 NUMBER FROM THE INSTALLATION DRAWINGS. I HAVE INCLUDED
 A LINK TO THE CONSTRUCTION SERVICES DEPARTMENT SITE
 THAT HAS MANY OF THE RELATED FORMS INCLUDING THE
 SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE
 DEVICES.
 HTTP://WPB.ORG/DEVELOPMENT/FORMS-AND-PUBLICATIONS/
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-21 Cont ID  
Sent By rmcdouga Date 2016-01-21 Time 09:11 Rev Time 0.00
Received By rmcdouga Date 2016-01-21 Time 09:11 Sent To  
Notes
2016-01-21 09:12:22SEPARATE SUB-PERMIT IS REQUIRED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-11 Cont ID  
Sent By rmcdouga Date 2016-01-11 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2016-01-11 Time 08:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-19 Cont ID  
Sent By rmcdouga Date 2015-05-19 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2015-05-19 Time 16:42 Sent To  
Notes
2015-05-19 09:15:08SENT TO R. MCDOUGALS DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-11 Cont ID  
Sent By rmcdouga Date 2016-01-11 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2016-01-04 Time 09:46 Sent To  
Notes
2016-01-05 09:46:48RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-02 Cont ID  
Sent By shill Date 2015-06-02 Time 09:15 Rev Time  
Received By shill Date 2015-05-18 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2015-06-02 Cont ID  
Sent By shill Date 2015-06-02 Time 09:15 Rev Time 0.00
Received By shill Date 2015-06-02 Time 09:15 Sent To  
Notes
2015-06-02 09:16:23THIS WAS ROUTED BACK TO BUILDING BY ZONING
 ZONING REVIEW NOT NEEDED (NO CHANGE IN FOOTPRINT)
  