Plan Review Details - Permit 15050687
Plan Review Stops For Permit 15050687
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-04 Cont ID  
Sent By albarran Date 2015-06-04 Time 08:48 Rev Time 0.00
Received By albarran Date 2015-06-04 Time 08:23 Sent To I
Notes
2015-06-04 08:48:43ELECTRICAL PROVISO:
 THE SYSTEM GROUNDING SHALL BE INSPECTED FOR INTEGRITY
 AND ANY DEFICIENCY CORRECTED AS PER CURRENT CODE
 REQUIREMENTS. INTER-SYSTEM BONDING TERMINAL REQUIRED AS
 PER NEC 250.94
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-02 Cont ID  
Sent By albarran Date 2015-06-02 Time 17:38 Rev Time 0.00
Received By albarran Date 2015-06-02 Time 17:36 Sent To I
Notes
2015-06-02 17:39:13SCOPE OF WORK NEEDS TO BE CLEARLY DEFINED ON THE
 DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-04 Cont ID  
Sent By albarran Date 2015-06-04 Time 08:55 Rev Time  
Received By albarran Date 2015-05-18 Time   Sent To  
Notes
2015-06-04 08:56:30SENT TO SMALL READY "E"
2015-05-18 17:16:30SENT TO <$5K ELECTRICAL BOX.