Plan Review Details - Permit 15050612
Plan Review Stops For Permit 15050612
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-05 Cont ID  
Sent By rmcdouga Date 2015-06-05 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2015-06-05 Time 13:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-27 Cont ID  
Sent By rmcdouga Date 2015-05-27 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2015-05-27 Time 09:38 Sent To  
Notes
2015-05-27 09:39:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE OPENING NUMBERS DO NOT CORRESPOND TO THE KEY
 PLANS WHICH ARE SHEETS A1.0 AND A2.0 OF THE APPROVED
 MASTER PLANS (#14070510). ALSO REFER TO THE WINDOW AND
 DOOR SCHEDULE FOR 'F' UNIT ON SHEET A4.0. FBC 107.2.1
  
 2) THE MINIMUM EDGE DISTANCE FOR THE 1/4" SOLID SET
 ANCHORS IS LISTED AS 3.5" FOR BOTH CONCRETE AND
 CONCRETE BLOCK IN THE TABLE ON SHEET 9. THE EDGE
 DISTANCE ON THE INSTALLATION SCHEDULE IS SPECIFIED AS
 2.5". IF USING A 2.5" EDGE DISTANCE THE TABLE IN THE
 PRODUCT APPROVAL REQUIRES THE ANCHOR SPACING TO BE
 REDUCED BY HALF. YOU WILL NEED TO REVISE THE EDGE
 DISTANCE OR THE ANCHOR SPACING IN THE INSTALLATION
 SCHEDULE.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-27 Cont ID  
Sent By rmcdouga Date 2015-05-27 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2015-05-14 Time 09:38 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved