Plan Review Details - Permit 15050608
Plan Review Stops For Permit 15050608
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-11 Cont ID  
Sent By hmoser Date 2015-06-18 Time 11:07 Rev Time 0.00
Received By wjolin Date 2015-06-11 Time 13:45 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-02 Cont ID  
Sent By wjolin Date 2015-06-02 Time 15:27 Rev Time 0.00
Received By wjolin Date 2015-06-02 Time 14:59 Sent To  
Notes
2015-06-02 15:27:41REFER TO MECHANICAL REVIEWER COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-18 Cont ID  
Sent By wjolin Date 2015-06-18 Time 11:07 Rev Time 0.00
Received By hmoser Date 2015-06-05 Time   Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-02 Cont ID  
Sent By hmoser Date 2015-06-02 Time 15:27 Rev Time 0.00
Received By wjolin Date 2015-05-15 Time 11:57 Sent To M
Notes
2015-05-16 11:57:50TO HAROLD MOSER'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-18 Cont ID  
Sent By hmoser Date 2015-06-18 Time 11:07 Rev Time 0.00
Received By hmoser Date 2015-06-18 Time 11:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-18 Cont ID  
Sent By wjolin Date 2015-06-02 Time 15:27 Rev Time 0.00
Received By hmoser Date 2015-05-18 Time 14:06 Sent To FIRE
Notes
2015-05-18 16:05:13PLAN DENIED
  
 1) REFER TO SECTION 506.3.12.3 TERMINATION LOCATION.
 EXCEPTION
 EXHAUST OUTLETS SHALL TERMINATE NOT LESS THAN 5 FT.
 FROM PARTS OF THE SAME OR TIGUOUS BUILDING, AND
 ADJACENT BUILDING, ADJACENT PROPERTY LINE AND AIR
 INTAKE OPENINGS INTO THE BUILDING WERE AIR FROM
 THE EXHAUST DISCHARGES AWAY FROM SUCH LOCATIONS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676