Plan Review Details - Permit 15050575
Plan Review Stops For Permit 15050575
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-09-09 Cont ID  
Sent By jwitmer Date 2015-09-02 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2015-09-02 Time 13:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-08-11 Cont ID  
Sent By jwitmer Date 2015-08-11 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-08-11 Time   Sent To  
Notes
2015-08-11 12:16:06BUILDING PLAN REVIEW
 W. P. B. REVISION: 15050575
 W. P. B. PERMIT: 14120580
 ADD: 901 45TH ST. QUANTUM HOUSE
 CONT: HEDRICK BROTHERS
 TEL: ( 561)689-8880
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUES. AUG. 11/ 2015
 ACTION: DENIED
  
 1) 2ND REQUEST. SHEET M1.1 SHOWS THE EAST WEST CORIDORS
 WITH FIRE DAMPERS AT THE FIRE RATED DORMITORY/ ASSEMBLY
 OCCUPANCY SEPARATION WALLS. PLEASE PROVIDE COMPLIANCE
 WITH THE 2010 FBC-B SECTION 716.4 ACCESS AND
 IDENTIFICATION. THIS SHOULD OCCUR AT ALL FIRE DAMPERS
 ON SITE.
 RESPONSE INDICATES SEE M5.1 DETAIL # 9. PLEASE NOTE
 THIS IS A WALL SECTION DETAIL OF A FIRE DAMPER LOCATED
 IN A RATED WALL. IR DOES NOT PROVIDE HOW YOU WILL GAIN
 ACCESS THROUGH A GYPSUM CEILING OR IDENTIFICATION FOR
 THE FIRE DAMPER.
  
 THE PRIME PERMIT # 14120580 SHEET 013-A1.5 AND SHEET
 015-A1.7 NORTH PARTIAL CEILING PLAN SHOWS GYPSUM
 CEILINGS ON BOTH SIDES OF THE RATED WALL AND DOORWAY.
 THE DUCTWORK AND FIRE DAMPER ARE INSTALLED BETWEEN THE
 2 CEILINGS. PLEASE ALSO SEE SHEET 025-A4.0 AND 026-A4.1
 SHOW THE 2 DIFFERENT ELEVTIONS OF CEILINGS, THE UPPER
 CEILING RATED PER U. L. P531.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
2015-08-11 12:02:56BUILDING PLAN REVIEW
 W. P. B. REVISION: 15050499
 W. P. B. PERMIT: 14120580
 ADD: 901 45TH ST. QUANTUM HOUSE
 CONT: HEDRICK BROTHERS
 TEL: ( 561)689-8880
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 24/ 2015
 ACTION: DENIED
  
 1) SHEET M1.1 SHOWS THE EAST WEST CORIDORS WITH FIRE
 DAMPERS AT THE FIRE RATED DORMITORY/ ASSEMBLY OCCUPANCY
 WALLS. PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B
 SECTION 716.4 ACCESS AND IDENTIFICATION. THIS SHOULD
 OCCUR AT ALL FIRE DAMPERS ON SITE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 10:43 Rev Time  
Received By jwitmer Date 2015-06-24 Time 08:30 Sent To  
Notes
2015-06-24 10:43:39BUILDING PLAN REVIEW
 W. P. B. REVISION: 15050575
 W. P. B. PERMIT: 14120580
 ADD: 901 45TH ST. QUANTUM HOUSE
 CONT: HEDRICK BROTHERS
 TEL: ( 561)689-8880
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 24/ 2015
 ACTION: DENIED
  
 1) SHEET M1.1 SHOWS THE EAST WEST CORIDORS WITH FIRE
 DAMPERS AT THE FIRE RATED DORMITORY/ ASSEMBLY OCCUPANCY
 WALLS. PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B
 SECTION 716.4 ACCESS AND IDENTIFICATION. THIS SHOULD
 OCCUR AT ALL FIRE DAMPERS ON SITE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-24 Cont ID  
Sent By albarran Date 2015-06-24 Time 11:21 Rev Time 0.00
Received By albarran Date 2015-06-23 Time 16:45 Sent To  
Notes
2015-06-24 11:23:31THE REPLACEMENT UNITS HAVE REDUCED THE ELECTRICAL
 DEMAND OF THE SITE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-28 Cont ID  
Sent By wjolin Date 2015-05-28 Time 14:16 Rev Time 0.00
Received By wjolin Date 2015-05-20 Time 16:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-09 Cont ID  
Sent By lmarchan Date 2015-09-09 Time 09:59 Rev Time 0.00
Received By lmarchan Date 2015-08-21 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-18 Cont ID  
Sent By lmarchan Date 2015-08-13 Time 09:07 Rev Time 0.00
Received By lmarchan Date 2015-07-31 Time 13:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-24 Cont ID  
Sent By cpuell Date 2015-06-24 Time 11:44 Rev Time 0.00
Received By cpuell Date 2015-05-15 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-09-09 Cont ID  
Sent By ccole Date 2015-09-09 Time 09:45 Rev Time 0.00
Received By ccole Date 2015-09-09 Time 09:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-13 Cont ID  
Sent By ccole Date 2015-08-13 Time 11:33 Rev Time 0.00
Received By ccole Date 2015-08-13 Time 11:33 Sent To  
Notes
2015-08-13 11:44:13MECHANICAL APPROVED WITH EXCEPTION.
 8/13/15
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) ACCESS PANELS REQUIRED FOR FIRE DAMPERS AT THE
 FIRE-RATED DORMITORY CORRIDOR/ASSEMBLY OCCUPANCY
 SEPARATION WALLS- SECTION 607.4 ACCESS AND
 IDENTIFICATION.
 FIRE AND SMOKE DAMPERS SHALL BE PROVIDED WITH AN
 APPROVED MEANS OF ACCESS, LARGE ENOUGH TO PERMIT
 INSPECTION AND MAINTENANCE OF THE DAMPER AND ITS
 OPERATING PARTS. THE ACCESS SHALL NOT AFFECT THE
 INTEGRITY OF FIRE-RESISTANCE-RATED ASSEMBLIES. THE
 ACCESS OPENINGS SHALL NOT REDUCE THE FIRE-RESISTANCE
 RATING OF THE ASSEMBLY. ACCESS POINTS SHALL BE
 PERMANENTLY IDENTIFIED ON THE EXTERIOR BY A LABEL
 HAVING LETTERS NOT LESS THAN 0.5 INCH (12.7 MM) IN
 HEIGHT READING: FIRE/SMOKE DAMPER, SMOKE DAMPER OR FIRE
 DAMPER. ACCESS DOORS IN DUCTS SHALL BE TIGHT FITTING
 AND SUITABLE FOR THE REQUIRED DUCT CONSTRUCTION.
 2) PROVIDE A PRODUCT SAUBMITTAL PACKAGE THAT INCLUDES
 THE REVISED ENERGY CALCULATIONS, AND MANUFACTURER'S
 SPECIFICATIONS FOR THE AC UNITS, FIRE DAMPERS,
 MOTORIZED O/A DAMPERS, VAV BOXES, AND THE DUCT SMOKE
 DETECTORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By ccole Date 2015-06-23 Time 11:22 Rev Time 0.00
Received By ccole Date 2015-06-23 Time 11:22 Sent To  
Notes
2015-06-23 11:36:231ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE REVISED ENERGY CALCULATIONS SHOWING THE
 COMPLIANCE DATA FOR THE NEW AC UNITS.
 2) SHEET M0.1: PROVIDE THE OUTDOOR AIR CALCULATIONS FOR
 THE GUEST ROOMS PER TABLE 403.3 FBC-10 MECHANICAL.
 3) SHEETS M0.1 & M1.1: THE REQUIRED 108 CFM'S OF
 OUTDOOR AIR FOR THE GUEST ROOM CORRIDORS SHOWN IN THE
 SCHEDULE IS NOT BEING SUPPLIED: PLEASE NOTE THE MINI
 SPLIT SYSTEMS AC-1A AND AC-1B ARE DUCTLESS.
 4) M1.1: THE AC-1A &1B CASSETTES APPEAR TO BE MOUNTED
 IN THE FIRE-RATED CORRIDOR CEILING MEMBRANE. INDICATE
 HOW THESE OPENINGS ARE GOING TO PROTECTED FROM FIRE AND
 SMOKE INTRUSION- REFERENCE SECTION 607.6.2 FBC-10
 MECHANICAL.
 5) M1.1 THE RETURN AIR GRILLS AND SUPPLY DUCTS ABOVE
 THE EAST AND WEST CORRIDOR FIRE DOORS IN THE CORRIDOR
 CEILINGS MUST BE PROTECTED WITH FIRE/SMOKE DAMPERS.
 PROVIDE A SCHEDULE ON THE PLANS INDICATING THE MAKES,
 MODELS, TYPES, SIZES, AND FIRE-RESISTANCE RATINGS OF
 THESE DAMPERS, AND ALL REQUIRED DAMPERS TO BE INSTALLED
 IN THE CORRIDORS AND GUEST ROOMS. NOTE: ALL DAMPER
 ACCESS DOORS LOCATED IN THE CORRIDOR AND GUEST ROOM
 CEILINGS SHALL BE FIRE-RATED. PROVIDE DETAILS AND
 SUBMIT SPECS FOR ALL PRODUCTS REVIEWED AND STAMPED BY
 THE DESIGN PROFESSIONAL OF RECORD.
 6) M1.1: SHOW THE LOCATIONS OF THE CONDENSER UNITS FOR
 AC-1A & 1B, AND PROVIDE INSTALLATION DETAILS.
 7) M1.1: FIRE/SMOKE DAMPERS ARE REQUIRED FOR THE
 EXHAUST DUCTS PENENTRATING THE EAST AND WEST RATED
 CORRIDOR WALLS, UNLESS CLAIMING ONE OF THE EXCEPTIONS
 UNDER SECTION 607.5.3: PLEASE PROVIDE DETAUILS
 INDICATING COMPLIANCE.
 8) M1.1: SHOW THE O/A SUPPLY DUCT FOR AC-2.
 9) PROVIDE A NARRATIVE INDICATING HOW THE DUCT SMOKE
 DETECTORS WILL BE SUPERVISED RELATING TO THE FIRE ALARM
 SYSTEM AND THE FAN SHUT SEQUENCE OF OPERATION. CLARIFY
 IS AC-1A & 1B WILL BE LINKED TO THE SYSTEM.
 10) PROVIDE PRIMARY AND SECONDARY CONDENSATE DISPOSAL
 DETAILS FOR ALL OF THE AIR HANDLERS- SECTION 307 FBC-10
 MECH.
 11) PROVIDE REFRIGERANT PIPING DETAILS INCLUDING PIPING
 MATERIAL, PIPING INSULATION, PIPING RUNS AND THROUGH
 PENETRATION FIRE-STOPPING DETAILS. INDICATE THE AMOUNT
 OF REFRIGERANT CHARGE IN LBS. FOR AC-1.
 12) PROVIDE HANGING AND SUPPORT DETAILS FOR THE VAV
 BOXES AND DUCTS.
 13) PROVIDE A SUBMITTAL PACKAGE FROM THE DESIGN
 PROFESSIONAL OF RECORD THAT INCLUDES THE AC UNITS, THE
 FIRE/SMOKE DAMPERS, THE DUCT SMOKE DETECTORS, THE
 MOTORIZED O/A DAMPERS, AND THE VAV BOXES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-11 Cont ID  
Sent By tklarge Date 2015-06-11 Time 06:22 Rev Time 0.00
Received By tklarge Date 2015-06-11 Time 05:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2015-09-10 Cont ID  
Sent By skennedy Date 2015-09-10 Time 14:47 Rev Time 0.00
Received By skennedy Date 2015-09-10 Time 13:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-19 Cont ID  
Sent By dkittred Date 2015-05-19 Time 14:02 Rev Time 0.00
Received By dkittred Date 2015-05-19 Time 13:42 Sent To  
Notes
2015-09-09 10:56:519/9/15 - RE-STAMPED PLANS BECAUSE OF SHEET
 REVISIONS/CHANGE-OUT. DK
  
  
2015-05-19 14:16:595/18/2015 - PLACEMENT OF A/C UNITS ON THE NORTH SIDE OF
 THE BUILIDING HAVE CHANGED SLIGHTLY. PLACEMENT OF A/C
 UNITS SHALL TAKE INTO CONSIDERATION LOCATION OF WALKWAY
 AND LANDSCAPING ON THE APPROVED SITE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  