Plan Review Details - Permit 15050569
Plan Review Stops For Permit 15050569
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-28 Cont ID  
Sent By jwitmer Date 2015-08-28 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2015-08-28 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-06 Cont ID  
Sent By jwitmer Date 2015-07-06 Time 16:01 Rev Time 0.00
Received By jwitmer Date 2015-07-06 Time 15:02 Sent To  
Notes
2015-07-06 15:34:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050569
 ADD: 250 S. AUSTRALIAN AVE.
 CONT: EDD HELMS AIR CONDITIONING & ELEC.
 TEL: (305)653-2530
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 06/2015
 ACTION: DENIED
  
 1) SHEETS M1 & M3 BOTH SHOW THE REPLACEMENT OF THE
 CHILLER UNITS. THE PLANS DO NOT INDICATE HOW THE UNITS
 ARE GOING TO BE REMOVED AND REPLACED WITHOUT DAMAMGE TO
 THE BUILDING? WILL PORTIONS OF EITHER THE ROOF OR WALLS
 TO BE REMOVED AND REPLACED FOR THE REPLACEMENT OF
 UNITS? 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. PLEASE PROVIDE
 DETAILS.
  
 2) SHEET M-3 SHOWS A WALL FIRE DAMPER BUT NOT A FIRE
 RATING IN ACCORDANCE WITH 2010 FBC-B 716.3.2 DAMPER
 RATING. TABLE 716.3.2.1.
  
 3) SHEET M-2 INDICATES A NEW EXHAUST FAN EF-CR-1 WHAT
 APPEARS TO BE A NEW ROOF TOP EXHAUST FAN, PLEASE
 PROVIDE DETAILS OF THE NEW ROOF TOP PENETRATION. NEW
 ROOF TOP CURB AND PRODUCT APPROVALS FOR NEW ROOF TOP
 UNIT. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(G) PRE-ENGINEERED A/C STANDS ROOF TOP EXHAUST FANS
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) EXHAUST FANS TO COMPLY WITH 2010 FBC-B 1609.8 ROOF
 TOP STRUCTURES AND EQUIPMENT.
  
 6) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
  
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-19 Cont ID  
Sent By albarran Date 2015-08-19 Time 12:24 Rev Time 0.00
Received By albarran Date 2015-08-19 Time 11:51 Sent To  
Notes
2015-08-19 12:28:05PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 NOT ALL ITEMS PREVIOUSLY REQUESTED HAVE BEEN SUBMITTED.
 I WILL NEED TO SEE THE RISER DIAGRAM AND LOAD CALCS FOR
 THE RESPECTIVE PANELS. ACCORDING TO THE NOTES ON SHEET
 E1, THE CONTRACTOR WILL PROVIDE THE RISER, BUT HE HAS
 NOT DONE SO.
 THEREFORE PER SAK, I WILL APPROVE THIS PERMIT AND THE
 REQUIRED RISER DIAGRAM SHALL BE PROVIDED TO THE
 INSPECTOR FOR FINAL INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-14 Cont ID  
Sent By albarran Date 2015-07-14 Time 09:30 Rev Time 0.00
Received By albarran Date 2015-07-14 Time 08:52 Sent To I
Notes
2015-07-14 09:33:34THE FOLLOWING CORRECTIONS TO THE PLANS SHALL BE MADE
 FOR A SUCCESSFUL ELECTRICAL REVIEW.
 1. PROVIDE/INCLUDE ELECTRICAL SPECS FOR THE PROPOSED
 CHILLERS.
 2. PROVIDE LOAD CALCS FOR THE SOURCE PANELS
 3. PROVIDE A PANEL SCHEDULE
 4. INCLUDE PANEL P4 IN THE RISER DIAGRAM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-08-19 Cont ID  
Sent By pleduc Date 2015-08-19 Time   Rev Time 0.00
Received By pleduc Date 2015-08-18 Time 17:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-06-25 Cont ID  
Sent By pleduc Date 2015-06-25 Time   Rev Time 0.00
Received By pleduc Date 2015-06-25 Time 09:59 Sent To  
Notes
2015-06-25 10:19:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET M-3, PROVIDE APPROPRIATE LISTING FOR THE
 FIRE/DAMPER FIRE WALL INSTALLATION.
  
 2) SHEET M-3, PROVIDE ADDITIONAL NOTE FOR THE FIRE
 ALARM SYSTEM CONNECTION "UNDER SEPARATE SHOP DRAWINGS
 PER NFPA 72 REQUIRMENTS AND TESTING"
  
 3) ADDRESS ALL OTHER DEPARTMENT COMMENTS.
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED PENDING REVIEW
 OF THE ABOVE RE-SUBMITTALS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-28 Cont ID  
Sent By jwitmer Date 2015-08-28 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2015-08-18 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-14 Cont ID  
Sent By albarran Date 2015-07-14 Time 09:33 Rev Time 0.00
Received By albarran Date 2015-05-15 Time 14:01 Sent To  
Notes
2015-07-14 09:49:137/14/15 - FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO LARGE DENIED BIN "E". MA
2015-05-15 13:53:49C04

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-08-25 Cont ID  
Sent By ccole Date 2015-08-25 Time 10:08 Rev Time 0.00
Received By ccole Date 2015-08-25 Time 10:05 Sent To  
Notes
2015-08-25 10:12:59MECHANICAL STOP #2 WAS LOCKED/CALLED HELP DESK, THEY
 COULD NOT FIX/I ADDED MECH STOP #3
 8/25/15
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-16 Cont ID  
Sent By ccole Date 2015-06-16 Time 12:33 Rev Time 0.00
Received By ccole Date 2015-06-16 Time 12:33 Sent To  
Notes
2015-06-16 12:44:051ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-1: THE CHILLER ROOM VENTILATION CALCULATIONS
 SHALL BE BASED ON THE AMOUNT OF REFRIGERANT (1600 LBS.)
 IN CHILLERS 1 & 2 BECAUSE THEY OPERATE TOGETHER AS A
 SINGLE SYSTEM. PLEASE REVISE THE CALCULATIONS, AND
 SELECT AN EMERGENCY EXHAUST FAN SIZED CONSISTENTLY WITH
 THE CALCULATION- SECTION 1105.6.4 FMC-10.
 2) M-2: CLARIFY ON THE PLANS HOW THE NORMAL VENTILATION
 SYSTEM IS BEING CONTROLLED. DOES THE EF-7 ROOF FAN RUN
 CONTINUOUSLY, BY AN INDIVIDUAL SWITCH, VIA CONNECTION
 TO A LIGHT SWITCH? PLEASE NOTE THAT PER SECTION 1105.6,
 VENTILATION SYSTEMS FOR MACHINERY ROOMS SHALL BE
 CAPABLE OF EXHAUSTING THE MINIMUM QUANTITY OF AIR AT
 NORMAL OPERATING AND EMERGENCY CONDITIONS, MEANING THAT
 THE REQUIRED NORMAL EXHAUST RATE SHALL BE MAINTAINED
 OVER AND ABOVE THE REQUIRED EMERGENCY EXHAUST RATE.
 PLEASE CORRECT THE NOTE SPECIFYING EF-7 TO SHUT DOWN
 WHEN EF-CH-1 ACTIVATES.
 3) REFRIGERANT LEAK DETECTION AND ALARM: A) THE
 ENGINEER OF RECORD SHALL PROVIDE REVIEWED AND APPROVED
 TESTING DATA, OR REPORTS FROM QUALIFIED SOURCES
 INDICATING THE TLV-TWA (OR TOXICITY MEASURE CONSISTENT
 THEREWITH) FOR THE R-123 REFRIGERANT. IN CONJUNCTION
 WITH THOSE REPORTS THE ENGINEER SHALL ALSO SUBMIT
 REVIEWED AND APPROVED MANUFACTURER?S SPECIFICATIONS FOR
 THE REFRIGERANT LEAK DETECTORS. BASED ON THE REPORTS
 AND SPECIFICATIONS , THE REVISED PLANS SHALL INDICATE
 THE SPACING OF THE DETECTORS, THEIR EXACT MOUNTING
 LOCATIONS, AND AT WHICH VALUE OR LEVEL OF REFRIGERANT
 DETECTION THEY WILL ACTUATE THE ALARM SYSTEM - SEE
 SECTION 8.11.2.1 ASHRAE 15, AND SECTION 8.6 ASHRAE 34,
 AND SECTION 53.11.2.1 FLORIDA FIRE PREVENTION CODE. B)
 SHOW ON THE PLAN THE LOCATION OF THE REQUIRED ALARM
 NOTIFICATION DEVICE AT THE STAIRWELL ENTRANCE PER
 ASHRAE 15 AND FFP. C) PROVIDE A SEQUENCE OF OPERATION
 DIAGRAM ON THE PLAN FOR THE ALARM SYSTEM.
 4) PROVIDE DETAILS FOR, AND THE TERMINATION LOCATIONS
 OF PRESSURE RELIEF DEVICES, FUSIBLE PLUG AND PURGE
 SYSTEMS PER SECTION 1105.7 FMC-10. PLEASE NOTE ALL
 SYSTEMS SHALL TERMINATE 15 FT. ABOVE THE ADJOINING
 GRADE (MAIN ROOF LEVEL) AND 20 FT. FROM ANY VENTILATION
 OPENING.
 5) THE TERMINATION OR DISCHARGE LOCATION FOR THE NEW
 EF-CH-1 SHALL BE LOCATED A MINIMUM OF 10 FT. ABOVE THE
 ROOF LEVEL PER SECTION 501.2(2) FMC-10. PLEASE REVISE
 THE PLAN ACCORDINGLY.
 6) SUBMIT MANUFACTURER'S SPECIFICATIONS AND A MIAMI
 DADE NOA OR FL. PRODUCT APPROVAL FOR THE NEW EXHAUST
 FAN. ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY
 THE ENGINEER OF RECORD.
 7) PROVIDE DETAILS FOR ANCHORING THE CONDENSER AND
 CHILLED WATER PUMPS, AND ANY REQUIRED PIPING SUPPORT
 STANDS TO THE EXISTING SLAB.
 8) INDICATE ON THE PLAN WHAT NECESSARY ALTERATIONS WILL
 BE MADE TO THE EXISTING STRUCTURE TO FACILITATE REMOVAL
 AND REPLACEMENT OF THE CHILLERS AND PUMPS, AND PROVIDE
 A DETAILED WORK SCHEDULE REPORT FROM BEGINNING TO TOTAL
 COMPLETION OF THE PROJECT.
 9) PLEASE NOTE THAT COMMISIONING OF THE SYSTEM IS
 REQUIRED FOR FINAL APPROVAL OF THE PROJECT PER SECTION
 503.2.9 FBC-10 ENERGY CONSERVATION. THE ENGINEER OF
 RECORD SHALL PROVIDE EVIDENCE OF SYSTEM COMPLETION
 INCLUDING A WRITTEN BALANCE REPORT TO BE PROVIDED TO
 THE OWNER OF THE BUILDING OR DESIGNATED REPRESENTATIVE.
 PLEASE PROVIDE NOTES ON THE PLAN DETAILING THE TESTING
 AND BALANCING PROCEDURE.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2015-06-19 Cont ID  
Sent By aaponte Date 2015-06-19 Time 15:54 Rev Time 0.00
Received By ccole Date 2015-06-19 Time 15:54 Sent To  
Notes
***NONE***