Plan Review Details - Permit 15050499
Plan Review Stops For Permit 15050499
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 12:26 Rev Time  
Received By jwitmer Date 2015-06-24 Time   Sent To  
Notes
2015-06-24 11:42:14BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050499
 ADD: 3234 S. DIXIE HWY.
 L. B. ROWE
 TEL: (561)635-8227
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 24/2015
 ACTION: DENIED
  
 1) SHEET A1 DOES NOT INDICATE UNDER THE 2010 EXISTING
 BUILDING CODE TO WHAT COMPLIANCE METHOD THE PLANS WERE
 DESIGNED/
  
 2) THE PLANS DO NOT INDICATE IF THE BUILDING IS FIRE
 SPRINKLERED OR NOT. 107.3.5.1.1 MINIMUM COMMERCIAL
 BUILDING PLAN REVIEW CRITERIA.
  
 3) THE PLANS INDICATE SPLITTING ONE TENANT SPACE AND
 CREATING TWO TENANT SPACES. THE PLANS DO NOT PROVIDE
 WHAT DESIGN THE TENANT SEPARATION WALL WILL BE DESIGNED
 TOO? 2010 FBC-B 709.1.6. PLEASE PROVIDE DETAIL OF THE
 TENANT SEPARATION WALL.
  
 4) SHEET A1 INDICATES THERE IS TO BE REPLACEMENT
 WINDOWS AND DOORS. PLEASE PROVIDE THE WIND DESIGN
 CRITERIA FOR THIS LOCATION.
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) PLEASE PROVIDE THE MISSING PRODUCT APPROVALS TO
 COMPLY WITH: 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) STOREFRONTS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) PLEASE NOTE IF THIS IS A NON-SPRINKLERED BUILDING
 THE COMMON PATH OF TRAVEL IS 75 FEET FOR BUSINESS AND
 MERCANTILE OCCUPANCIES.
 2010 FBC-B 1014.3. THE TENANCY IN 3234 DOES NOT HAVE A
 REAR DOOR MAKING THE TRAVEL DISTANCE OVER 75 FEET. THIS
 WILL REQUIRE A SECOND MEANS OF EGRESS TO COMPLY WITH
 FBC-B 1014.3.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-09 Cont ID  
Sent By rlecky Date 2015-06-09 Time 13:40 Rev Time 0.00
Received By rlecky Date 2015-06-09 Time 12:55 Sent To  
Notes
2015-06-09 13:43:2315050499
 3234 S. DIXIE HWY
 COMMERCIAL REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 ON THE PANEL SCHEDULE INCLUDE THE SHOW WINDOW LIGHTING
 AND SIGN CIRCUIT. PROVIDE SHOW WINDOW LIGHTING OUTLETS.
 NEC 210.62, 408.4, 600.5
  
 PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO
 THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS
 PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY
 CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. VERIFY THE
 LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY BACKUP. FBC
 ENERGY CONSERVATION 505.2
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE SPECIFICATIONS/DETAIL FOR FIRESTOPPING THE
 RECEPTACLES ON THE NEW FIREWALL SEPERATION. NEC 300.21
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-27 Cont ID  
Sent By pleduc Date 2015-05-27 Time   Rev Time 0.00
Received By pleduc Date 2015-05-27 Time 14:13 Sent To  
Notes
2015-05-27 14:31:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE OCCUPANY IS NOT CLEARLY INDICATED;
 STORE/COMMERCIAL IS GENERAL AND VAGUE. PLEASE PROVIDE
 EXISTING AND PROPOSED OCCUPANCY PER NFPA 101.
  
 2) A LIFE SAFETY PALN IS NOT PROVIDED. COMPLETE LIFE
 SAFETY PLANS FOR EACH OCCUPANCY SHALL BE PROVIDED THAT
 ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON
 PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 3) THE FIRE WALL DOES NOT INDICATE A FIRE RATING. A 2HR
 FIRE RATING IS REQUIRED WITH FIRE WALL DETAIL DRAWINGS,
 INCLUDING LISTED SEALED OPENINGS.
  
 4) NO DIMENSIONS ARE INDICATED. PLEASE INDICATED ALL
 DIMENSIONS ON THE RESUBMITTAL.
  
 5) EXIT DOOR HARDWARE IS NOT INDICATED. DOORS SHALL BE
 ARRANGED TO BE OPENED READILY FROM THE EGRESS SIDE
 WHENEVER THE BUILDING IS OCCUPIED. LOCKS, IF PROVIDED,
 SHALL NOT REQUIRE THE USE OF A KEY, TOOL, OR SPECIAL
 KNOWLEDGE OR EFFORT FOR OPERATION FROM THE EGRESS SIDE.
  
 INDICATE IF THE DOORS WILL BE EQUIPPED WITH ANY
 LOCK/LATCH. IF THE DOORS WILL BE EQUIPPED WITH A
 LOCK/LATCH, INDICATE HOW THE LOCK/LATCH WILL BE
 RELEASED FROM THE EGRESS SIDE OF THE DOOR.
  
 PER SECTION 7.2.1.5.9, THE LOCK/LATCH RELEASING
 MECHANISM ON ALL DOORS SHALL OPEN THE DOOR WITH NOT
 MORE THAN ONE RELEASING OPERATION. THE RELEASING
 MECHANISM SHALL HAVE AN OBVIOUS METHOD OF OPERATION
 THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS.
 THE RELEASING DEVICE SHOULD BE CAPABLE OF BEING
 OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE TIGHT
 GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST TO
 OPERATE.
  
 A THUMB TURN LOCK IS NOT PERMITTED ON THE MAIN ENTRY
 DOOR(S). IN LIEU OF PANIC HARDWARE, THE MAIN ENTRY IS
 PERMITTED TO BE EQUIPPED WITH A KEYED LOCK WITH
 LOCK/UNLOCK INDICATOR WINDOW AND SIGNAGE STATING THE
 DOOR IS TO REMAIN UNLOCKED DURING BUSINESS HOURS. NO
 OTHER LOCKING OR LATCHING MECHANISMS ARE PERMITTED.
  
 THUMB-TURN LOCK WHEN EQUIPPED ON OTHER DOORS IS SHALL
 BE INSTALED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW
 (SUCH AS ADAMS RITE 4089 OR SIMILAR).
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 12:26 Rev Time  
Received By jwitmer Date 2015-05-21 Time   Sent To  
Notes
2015-05-22 08:44:34C09

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2015-06-24 Time 12:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By ccole Date 2015-06-23 Time 07:29 Rev Time 0.00
Received By ccole Date 2015-06-23 Time 07:23 Sent To  
Notes
2015-06-23 07:48:351ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE PLAN INDICATES TWO NEW TENANT SPACES ARE BEING
 CREATED FROM ONE, HOWEVER MINIMAL DETAILS HAVE BEEN
 PROVIDED FOR COMFORT CONDITIONING. PLEASE PROVIDE THE
 FOLLOWING LIST OF REQUIRED INFORMATION, PLAN DETAILS
 AND SPECIFICATIONS FOR EACH NEW OCCUPANCY:
 A) MIINIMUM VENTILATION CALCULATIONS PER TABLE 403.3
 FBC MECHANICAL. INDICATE THE REQUIRED AND PROVIDED
 OUTSIDE AIR CFM'S.
 B) AC LOAD CALCULATIONS PER ACCA MANUAL N, OR
 ASHRAE/ACCA STANDARD 183- SECTION 503.2.1 FBC-10 ENERGY
 CONSERVATION.
 C) ENERGY CALCULATIONS: SUBMIT EITHER COMPLIANCE FORMS
 502 OR 506- TABLE 101.4.1 FBC-10 ENERGY.
 D) AC LAYOUT PLANS: SHOW THE NEW SUPPLY AND RETURN DUCT
 RUNS INCLUDING DUCT SIZES AND CFM DISTRIBUTION,
 LOCATIONS OF EQUIPMENT, REFRIGERANT AND CONDENSATE
 PIPING RUNS AND DETAILS.
 E) AC EQUIPMENT SCHEDULES- MAKES AND MODELS OF AC
 EQUIPMENT, COOLING AND HEATING CAPACITIES, EFFICIENCY
 RATINGS, ELECTRICAL DATA.
 F) AIR DISTRIBUTION SCHEDULE-TYPE OF DUCTWORK,
 DIFFUSERS, AND GRILLS,
 G) AC EQUIPMENT INSTALLATION AND DUCT HANGING AND
 SUPPORT DETAILS.
 2) PROVIDE TOILET ROOM EXHAUST DETAILS- EXHAUST FAN
 EQUIPMENT SCHEDULES, EXHAUST DUCT TYPES AND SIZES AND
 EXHAUST DUCT RUNS AND TERMINATION LOCATIONS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-14 Cont ID  
Sent By tklarge Date 2015-06-14 Time 06:05 Rev Time 0.00
Received By tklarge Date 2015-06-14 Time 05:22 Sent To  
Notes
2015-06-14 06:05:311) THE SUBMITTED PLANS SHOW THE EXISTING SPACE BEING
 CONVERTED INTO TWO SEPARATE UNITS. INDICATE THE TYPE OF
 OCUPANCY OF THE SPACES PER THE 2010 FBC SEC.303.
 ADDITIONAL PLUMBING FIXTURES MAY BE REQUIRED PER TABLE
 403.1 OF 2010 FBC-PLUMBING.
 2) INDICATE THE SQUARE FOOTAGE AND OCCUPANT LOAD OF
 BOTH SPACES ON THE PLANS. 2010 FBC SEC. 107.2.1.
 107.3.5.1.
 3) ELEVATION # 3 SHOWS THE WATER CLOSET LOCATED AT
 1'-8" FROM THE REAR WALL TO THE CENTERLINE OF THE WATER
 CLOSET. COMPLY W/ 2010 FBC-ACCESSIBILITY CODE
 SEC.604.2.
 4) THE INSTALLATION OF THE REAR GRAB BAR SHALL COMPLY
 WITH 2010 FBC SEC.604.5.2.
 5) THE LOCATION OF THE TOILET PAPER DISPENSER SHALL
 COMPLY WITH FAC SEC. 604.7.
 6) THE HEIGHT OF THE GRAB BARS SHALL BE INSTALLED IN
 ACCORDANCE WITH 2010 FAC SEC.609.4. THE HEIGHT SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE.
 7) SHOW THE CLEAR FLOOR SPACE FOR THE WATER CLOSET AND
 LAVATORY ON THE FLOOR PLAN. CLEAR FLOOR SPACES SHALL
 COMPLY WITH 2010 FAC SEC.604.3 & SEC.305.3.
 8) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 ANY FIXTURE PER FAC SEC. 603.2.3.( SEE EXCEPTIONS)
 9) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 CHANGES BEING MADE TO THE PLUMBING SYSTEM. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-27 Cont ID  
Sent By ajones Date 2015-05-27 Time 11:47 Rev Time 0.00
Received By ajones Date 2015-05-27 Time 11:47 Sent To  
Notes
***NONE***