Plan Review Details - Permit 15050486
Plan Review Stops For Permit 15050486
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By jgomez Date 2015-08-05 Time 12:44 Rev Time 0.00
Received By jgomez Date 2015-08-05 Time 12:44 Sent To  
Notes
2015-08-05 12:46:42BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS SUBMITTED. A) CONDITIONED
 FLOOR AREA ON ITEM #6 DOESN'T MATCH PLANS. B) NEED
 INSULATION BETWEEN GARAGE & 2ND FLOOR. C) REVISE WINDOW
 OVERHANG DEPTH TO MATCH PLANS. GABLE END WALLS DON'T
 PROVIDE 8" OVERHANG DEPTH.
 2- PROVIDE COMPLETE HANDRAIL AND GUARDRAILS (INTERIOR
 AND EXTERIOR) DETAILS/SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE LIVE LOADS OF TABLE R301.5.
 3- SHEET A2.3: FLAT ROOF NEEDS OVERFLOW SCUPPERS. SEC.
 R903.4.1
 4- REVISE LOCATION OF ATTIC ACCESS LOCATED IN CLOSET
 202B. NEED HEADROOM. ACCESS IS BLOCKED BY THE CLOTHES
 ROD. SEC. R807.
 5- THE PROJECT INFORMATION ON THE SOIL TEST REPORT
 SUBMITTED DOESN'T MATCH PROPOSED CONSTRUCTION. REVISE
 AS REQUIRED.
 6- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R1
 SUBMITTED: PERIMETER & CORNER AREAS WAS SELECTED BASED
 ON EXPOSURE "B". THIS DOESN'T MATCH PLANS. SEE SHEET
 S000. REVISE AS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-07-08 Cont ID  
Sent By jgomez Date 2015-07-07 Time 09:07 Rev Time 0.00
Received By jgomez Date 2015-07-07 Time 09:06 Sent To  
Notes
2015-07-07 09:07:26NEW SINGLE FAMILY RESIDENCE, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PLANS ARE MISSING THE DOORS AND WINDOWS SCHEDULE.
 PRODUCT APPROVALS SUBMITTED WILL BE REVIEWED WHEN THE
 DOORS AND WINDOWS SCHEDULES ARE PROVIDED. SEC. R301 OF
 2010 FBC.
 ALSO, EGRESS WILL BE REVIEWED WHEN COMPLETE INFORMATION
 IS SUBMITTED.
  
 2-PROVIDE PRODUCT APPROVAL AS REQUIRED BY F.A.C.
 61G20-3 FOR:
 A) ENTRY DOOR AS SHOWN ON PLANS. INFORMATION SUBMITTED
 DOESN'T HAVE A FLORIDA PRODUCT APPROVAL NUMBER OR
 MIAMI-DADE NOA NUMBER. IF THERE IS NO AN APPROVED
 ASSEMBLY, THEN MANUFACTURER MAY SUBMIT COMPLETE
 ENGINEERING FOR BUILDING OFFICIAL APPROVAL.
  
 B) THERMA TRU DOOR PRODUCT APPROVAL FL 7630-R4
 SUBMITTED DOESN'T MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER OF RECORD. NEED PRODUCT APPROVAL THAT
 MEETS THE CALCULATED DESIGN PRESSURES.
  
 C) FLAT ROOF ASSEMBLY. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 D) BALCONY WATERPROOFING UNDERLAYMENT THAT IS DESIGNED
 TO RECEIVE TILE AS SHOWN ON PLANS. AND, PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301. ALSO, PROVIDE PRODUCT
 APPROVAL FOR MATERIAL SPECIFIED FOR BALCONY ABOVE ENTRY
 AREA (WITH RAS 117 CALCULATIONS, IF REQUIRED).
  
 E) BAHAMA SHUTTERS AS SHOWN ON SHEET A3.1. AND, PROVIDE
 COMPLETE INSTALLATION SCHEDULE.
  
 F) GARAGE DOOR AS SHOWN ON SHEET A3.1
  
 G) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: PRODUCT APPROVALS SUBMITTED HAVE A
 DRAWINGS/SUBMITTAL REVIEW STAMP. THIS STAMP IS NOT
 ACCEPTABLE. IT DOESN'T IDENTIFY THE FIRM OR THE DESIGN
 PROFESSIONAL REVIEWING THE PRODUCT APPROVALS.
  
 4- 5V-CRIMP ROOF PANEL NOA 11-0810.10 SUBMITTED:
 CLEARLY IDENTIFY WHICH SYSTEM IS GOING TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 OF 2010 FBC-RESIDENTIAL.
  
 5- WINDOW MULLIONS: CLEARLY IDENTIFY ALL MULLION SIZES
 TO BE USED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 6- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 OF 2010 FBC-RESIDENTIAL.
  
 7- REVISE ENERGY CALCULATIONS SUBMITTED. SEC.
 103.2.1.1.2 AND SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
 ***NOTE: INFORMATION ON ENERGY CALCULATIONS AND PLANS
 NEED TO BE COORDINATED TO AVOID UNNECCESARY DELAYS AND
 CONFLICTS.
  
 A) COMPLETE INFORMATION ON TOP OF FORM: OWNER, CORRECT
 BUILDER'S NAME, PERMIT OFFICE AND JURISDICTION NUMBER.
  
 B) CONDITIONED FLOOR AREA ON ITEM #6 DOESN'T MATCH
 PLANS. NOTE: ALSO TAKE INTO CONSIDERATION THE BONUS
 ROOM ON SECOND FLOOR. SEE MECHANICAL PLAN.
  
 C) NEED INSULATION ON EXTERIOR WALLS, ADJACENT WALLS.
 SEC. 401.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) NEED INSULATION ON CEILING. CLARIFY WHERE ARE THE
 CATHEDRAL/SINGLE ASSEMBLY CEILINGS. SEC. 401.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) NEED INSULATION BETWEEN A/C SPACES AND NON-A/C
 SPACES. SEC. 401.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 F) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 G) REVISE TYPE OF ROOF ON PAGE 2 OF 6 TO MATCH PLANS.
  
 H) CLARIFY WHERE ARE THE WOOD DOORS SHOWN ON PAGE 3 OF
 6.
  
 I) REVISE WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH
 PLANS.
  
 ***NOTE: LABELS WILL BE REQUIRED FOR INSPECTION FOR THE
 WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR SPECIFIED ON
 ITEM #7.
  
 8- ELEVATIONS SHOWN ON THE A1.1 SITE PLAN DON'T MATCH
 THE ELEVATIONS SHOWN ON THE SURVEY. REVISE AS REQUIRED
 TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- SHEET A2.1:
 A) SPECIFY POWDER ROOM DOOR SIZE TO SHOW COMPLIANCE
 WITH SEC. R320.
  
 B) PROVIDE SPECIFICATIONS OF GARAGE DOOR LEADING TO
 MAIN HOUSE TO SHOW COMPLIANCE WITH SEC. R302.5.1
  
 10- SET OF PLANS IS MISSING DRAWING A7.1 LISTED IN THE
 LIST OF DRAWINGS ON SHEET A1.1. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 11- PROVIDE COMPLETE HANDRAIL AND GUARDRAILS (INTERIOR
 AND EXTERIOR) DETAILS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5 AND ALL
 THE REQUIREMENTS OF SEC. R311.7.7 AND R312.
  
 12- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY SHOWING COMPLIANCE WITH SEC. R311.7.
  
 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF EXTERIOR CEILINGS AT LOGGIA AND ENTRY
 PORCH. SEC R301.
  
 14- SHEET A2.2: CLARIFY WHAT'S THE DOTTED SQUARE SHOWN
 IN THE CENTER OF THE STAIRWAY. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 15- SHEET A2.3:
 A) FLAT ROOF NEED MAIN ROOF DRAINS AND AND OVERFLOW
 SCUPPERS TO COMPLY WITH SEC. R903.4 AND R903.4.1
  
 B) REVISE ROOF DRAIN DETAIL. CLARIFY IF INSTALLING ROOF
 RIGID INSULATION. COORDINATE WITH BUILDING WALL
 SECTIONS, THE ENERGY CALCULATIONS AND FLAT ROOF PRODUCT
 APPROVAL APPROVED ASSEMBLY. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) COORDINATE ROOF MEMBRANE AND FLAT ROOF NOTES WITH
 PRODUCT APPROVALS SUBMITTED TO AVOID CONFLICTS. SEE
 APPROVED ASSEMBLIES AND REVISE INFORMATION AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 16- GUTTERS WITH DOWNSPOUTS ARE REQUIRED FOR EAVES LESS
 THAN 6". PROVIDE COMPLETE DETAILS AND SPECIFICATIONS.
 PROVIDE DIMENSIONS FOR ALL EAVES. SEC. R318.6
  
 17- SPECIFY WINDOW SILL HEIGHT ON ALL SECOND FLOOR
 WINDOWS TO VERIFY COMPLIANCE WITH SEC. R612.2
  
 18- LABELING ORIENTATION OF EAST AND WEST ELEVATIONS
 ARE INCORRECT.. EAST ELEVATION IS WEST ELEVATION AND
 WEST ELEVATION IS EAST ELEVATION. REVISE AS REQUIRED TO
 MATCH ACTUAL BUILDING ORIENTATION. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 19- PROVIDE FRAMING DETAILS FOR ARCHED ENTRY DOOR. SEC.
 R301.
  
 20- PROVIDE ICC EVALUATION REPORT FOR THE SPECIFIED
 ICYNENE INSULATION (PLEASE MAKE SURE IS THE CURRENT
 REPORT). SEC. R316.
  
 21- PROVIDE SPECIFICATIONS FOR CEILING ABOVE GARAGE.
 TABLE R302.6.
  
 22- SPECIFY ATTIC ACCESS LOCATION AND SIZE. SEC. R807.
  
 23- COORDINATE FASTENING OF WINDOW STRUCTURAL BUCKS
 SHOWN ON SHEET A5.2 WITH FASTENING SHOWN ON DETAIL 08
 OF SHEET S400. SEC. 107.2.1 CITY AMENDMENTS.
  
 24- SHEET S000: (1) CLARIFY WHY THERE IS NOT ROOF ZONE
 #3 ON MASTER BEDROOM BALCONY. (2) CLARIFY WHY FLAT ROOF
 ON SECOND FLOOR IS ZONE 1. SEC. R301.
  
 25- PROVIDE COPY OF SOIL TEST REPORT REFERENCED ON THE
 NOTES OF THE FOOTING SCHEDULE. SEC. R401.4.
  
 26- NOA 06-0222.01 SPECIFIED FOR PRECAST LINTELS ON
 SHEET S400 IS EXPIRED. NEED CURRENT NOA. COORDINATE
 WITH NOA SUBMITTED.
  
 *** PLEASE PROVIDE REPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** REPLACE ANY REVISED DRAWING TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By albarran Date 2015-08-03 Time 14:39 Rev Time 0.00
Received By albarran Date 2015-08-03 Time 13:29 Sent To  
Notes
2015-08-03 14:40:01ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-25 Cont ID  
Sent By albarran Date 2015-06-25 Time 13:12 Rev Time 0.00
Received By albarran Date 2015-06-25 Time 08:28 Sent To B
Notes
2015-06-25 13:13:52PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED. AS THIS WAS A PAGE BY PAGE
 REVIEW, YOU WILL NOTICE REPEATED COMMENTS ON EACH
 RESPECTIVE PAGE. EACH OF THE COMMENTS NOTED HAVE BEEN
 CLOUDED OR IN SOME WAY IDENTIFIED IN A RED LAYER ON THE
 DIGITAL PLANS.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 SHEET E-0
 1. AMEND THIS NOTE TO ALSO INCLUDE: THE TIP OF A
 CEILING (PADDLE) FAN BLADE, PER NFPA 29.8.3.4(8)
 2. CORRECT THIS TO READ: NFPA 101, 2012 EDITION
 3. CORRECT THIS TO READ: NFPA 72, 2010 EDITION
 4. THOUGH THE INDIVIDUAL PANEL CALCS WILL COMPLY WITH
 THE PROPOSED CONDUCTORS AND THE SERVICE CONDUCTORS AS A
 WHOLE. THE NUMBERS AS REFLECTED HEREIN SHALL BE
 CORRECTED.
 SHEET E-1
 1. NEC 210.52 (A)(1) SPACING. RECEPTACLES SHALL BE
 INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY
 ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6
 FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE
 DISTANCE FROM THE EDGE OF THE WALL
 2. AN ADDITIONAL OUTLET WILL BE REQUIRED IN THIS AREA
 TO COMPLY WITH MINIMUM OUTLET SPACING REQUIREMENTS
 3. THESE OUTLETS CAN'T BE BEHIND OR OBSTRUCTED BY THE
 POOL EQUIPMENT.
 4. AN ADDITIONAL OUTLET WILL BE REQUIRED IN THIS AREA
 TO COMPLY WITH MINIMUM OUTLET SPACING REQUIREMENTS
 5. PER NFPA 29.8.3.4(9), A SMOKE DETECTOR IS REQUIRED
 IN THIS AREA
 6. ACCORDING TO THE CIRCUIT SCHEDULE OF PANEL "A",
 CIRCUIT 23 IS FOR THE REFRIGERATOR. INDICATE IF AN
 ADDITIONAL CIRCUIT WILL BE DRAWN FOR THE MICROWAVE.
 7. CORRECT THIS MISQUOTED CODE SECTION. THE APPLICABLE
 FBC IS 2010 SECTION 907.2.11.4
 8. THE FOLLOWING NOTES WERE ADDED TO THE DRAWING:
 A) NEC 240.24 LOCATION IN OR ON PREMISES. (A) & (B)
 PANELS SHALL BE LOCATED SUCH THAT OVER CURRENT DEVICES
 ARE ACCESSIBLE AND THAT OCCUPANTS SHALL HAVE ACCESS TO
 OCP DEVICES.
 B) NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 C) NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 D) NEC 406.8(B) RECEPTACLES IN WET LOCATIONS. 15- AND
 20-AMPERE, 125- AND 250-VOLT RECEPTACLES INSTALLED IN A
 WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS
 WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS
 INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT
 NONLOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE.
 SHEET E-2
 1. PER NFPA 29.8.3.4(9), A SMOKE DETECTOR IS REQUIRED
 IN THIS AREA & PER FBC-R 315 IT SHALL BE COMBINATION
 SMOKE & CARBON MONOXIDE DETECTOR.
 2. NEC 210.52(E)(3) BALCONIES. BALCONIES GREATER THAN
 20 SQ. FT. SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 INSTALLED WITHIN THE PERIMETER OF THE BALCONY.
 3. THIS DETECTOR ALONE DOES NOT MEET THE LOCATION
 REQUIREMENTS OF NFPA 29.5.1(2) WITH RELATION TO BEDROOM
 3 OR THE FUTURE BONUS ROOM.
 4. THIS AHU SHALL HAVE A DISCONNECT AS REQUIRED BY NEC
 440.14
 5. REARRANGE THE BEDROOM OUTLETS TO COMPLY WITH NEC
 210.52
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-10 Cont ID  
Sent By tklarge Date 2015-08-10 Time 12:17 Rev Time 0.00
Received By tklarge Date 2015-07-21 Time 11:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-07 Cont ID  
Sent By jgomez Date 2015-07-07 Time 09:06 Rev Time 0.00
Received By jgomez Date 2015-05-15 Time 10:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2015-07-06 Cont ID  
Sent By skennedy Date 2015-07-06 Time 16:46 Rev Time 0.00
Received By skennedy Date 2015-07-06 Time 16:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-03 Cont ID  
Sent By ccole Date 2015-08-03 Time 10:45 Rev Time 0.00
Received By ccole Date 2015-08-03 Time 10:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-25 Cont ID  
Sent By ccole Date 2015-06-25 Time 08:24 Rev Time 0.00
Received By ccole Date 2015-06-25 Time 08:23 Sent To  
Notes
2015-06-25 09:27:521ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE AC LOAD CALCULATIONS FOR THE AC SYSTEMS IN
 ACCORDANCE WITH ACCA MANUAL J- SECTION 403.6.1 FBC-10
 ENERGY CONSERVATION.
 2) THE SUBMITTED ENERGY CALCULATION FORM 405-10 IS
 INCOMPLETE: A) DOCUMENT MUST BE SIGNED AND DATED BY THE
 PREPARER AND THE OWNER- SEE PAGE 1. B) CODE COMPLIANCE
 CHECKLIST ON PAGE 6 MUST BE CHECKED OFF. C) THE INPUT
 DATA REPORT INDICATING THE THERMAL ENVELOPE
 CONSTRUCTION AND INSULATION MATERIALS AND VALUES MUST
 BE SUBMITTED. PLEASE NOTE THE PLAN DOES NOT CLEARLY
 INDICATE INDICATE WALL, CEILING, AND ATTIC INSULATIONS
 AND R-VALUES TO CORRELATE WITH THE CALCS- REFERENCE
 SECTION 103.22. FBC-10 ENERGY CONSERVATION.
 3) SHEET M-1, AIR HANDLER CLOSET: A) PROVIDE THE
 DIMENSIONS OF THE RETURN AIR GRILL D1400 AT CLOSET. B)
 PROVIDE THE DIMENSIONS OF THE AIR HANDLER CLOSET AND
 AIR HANDLER CLEARANCE MEASUREMENTS IN COMPLIANCE WITH
 SECTION M1305.1.1 FBC-10 RESIDENTIAL. C) INDICATE THE
 THE TYPE OF AIR BARRIER TO BE INSTALLED ON THE WALLS
 AND CEILING OF THE CLOSET AND HOW IT WILL BE SEALED. D)
 PROVIDE DETAILS FOR THE DOUBLE DOORS- PLEASE NOTE RATED
 DOORS WITH THRESHOLD AND WEATHER STRIPPING ARE
 REQUIRED- SECTIONS R302.5.1 & M1601.4.1
 4) M-2 AIR HANDLER CLOSET: A) REFERENCE COMMENTS 3B, &
 C ABOVE, AND ALSO INDICATE THE DIMENSIONS OF THE RETURN
 DUCT AND GRILL MAKING CONNECTION INTO THE CLOSET
 5) M-3: PLEASE REMOVE THE DUCT SMOKE DETECTOR NOTES
 FROM THE CONTROLS DIAGRAM UNLESS THEY ARE ACTUALLY
 BEING INSTALLED- NOTE THEY ARE NOT REQUIRED FOR SINGLE
 FAMILY HOMES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-08-11 Cont ID  
Sent By tklarge Date 2015-08-10 Time 12:16 Rev Time 0.00
Received By tklarge Date 2015-08-10 Time 11:13 Sent To  
Notes
2015-08-10 12:16:45PLUMBING APPROVED WITH PROVISO:
 THESE ITEMS SHALL BE CORRECTED PRIOR TO THE FIRST
 INSPECTION.
  
 1) SHT.P-1 IS LISTED AS GROUND FLOOR PLUMBING BUT THE
 PLAN IS PLUMBING NOTES. WHAT HAPPENED TO THE GROUND
 FLOOR PLUMBING PLAN? SUBMIT A GROUND FLOOR PLUMBING
 PLAN FOR REVIEW. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE STORM RISER SHOWS A 3" LINE DRAINING INTO A
 SMALLER 2" LINE. THIS VIOLATES THE 2010 FBC-PLUMBING
 SEC.706.3 AND 1101.6.A LARGER DRAIN LINE CANNOT DRAIN
 INTO A SMALLER DRAIN LINE.
 3) SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION LESS
 THAN 4 INCHES. THE PLAN SHOWS THE SCUPPER WITH A 2 INCH
 OPENING. COMPLY WITH 2010 FPC SEC. 1107.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-14 Cont ID  
Sent By tklarge Date 2015-06-14 Time 07:01 Rev Time 0.00
Received By tklarge Date 2015-06-14 Time 06:13 Sent To  
Notes
2015-06-14 07:01:311) SUBMIT A RISER FOR THE ROOF DRAIN. SHOW THE PIPE
 SIZE OF THE VERTICAL LEADER AND THE HORIZONTAL DRAIN
 PIPE. PIPE SIZES SHALL COMPLY W/ 2010 FBC-PLUMBING,
 TABLE 1106.2 (1), TABLE 1106.3. INDICATE ON THE PLAN
 THE SQUARE FOOTAGE OF THE ROOF THAT IS DRAINING INTO
 THE ROOF DRAIN.
 2) SUBMIT DETAILS AND CALCULATIONS FOR ROOF DRAINAGE OF
 NON-SLOPED ROOF AREAS AND ALSO SECONDARY (EMERGENCY)
 DRAINAGE OF THESE ROOF AREAS. 2010 FBC-R, SECS.R903.4,
 R903.4.1.
 3) SHT. P.0 - NOTE #1 - DELETE THE REFERENCE TO 2001
 FBC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-08-10 Cont ID  
Sent By jgomez Date 2015-08-10 Time 10:45 Rev Time 0.00
Received By jgomez Date 2015-08-10 Time 07:48 Sent To  
Notes
2015-08-10 07:49:02APPROVED WITH PROVISO:
  
 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL16709-R1
 SUBMITTED: PERIMETER AND CORNER AREAS NAIL ENHANCEMENT
 WAS SELECTED BASED ON EXPOSURE "B". THIS IS NOT THE
 BUILDING EXPOSURE SPECIFIED BY THE ENGINEER OF RECORD
 ON SHEET S000. PROVIDE INFORMATION FOR THE CORRECT
 EXPOSURE. SEC. R301.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-07-09 Cont ID  
Sent By jgomez Date 2015-07-09 Time 08:00 Rev Time 0.00
Received By jgomez Date 2015-07-09 Time 07:52 Sent To  
Notes
2015-07-09 08:03:301- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9N-3 FOR:
 A) FLAT ROOF ASSEMBLY. AND CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. AND, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 B) BALCONY WATERPROOFING UNDERLAYMENT THAT IS DESIGNED
 TO RECEIVE TILE AS SHOWN ON PLANS. AND, PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS IF REQUIRED TO MEET THE
 DESIGN PRESSURES OF SEC. R301.
  
 2- 5V-CRIMP ROOF PANEL NOA 11-0810.10 SUBMITTED:
 CLEARLY IDENTIFY WHICH SYSTEM IS GOING TO BE USED TO
 VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301 OF 2010 FBC-RESIDENTIAL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-08-11 Cont ID  
Sent By skennedy Date 2015-08-11 Time 10:18 Rev Time 0.00
Received By skennedy Date 2015-08-11 Time 10:18 Sent To  
Notes
2015-05-15 10:11:33SEE LARGE DENIED BIN C

Review Stop Z ZONING
Rev No 2 Status P Date 2015-08-11 Cont ID  
Sent By sgraham Date 2015-08-11 Time   Rev Time 0.00
Received By sgraham Date 2015-08-11 Time 14:35 Sent To  
Notes
2015-08-11 10:21:02ZONING PASSED ON 05/29/2015.
2015-05-29 11:06:345/29/15 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE SURVEYS

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-21 Cont ID  
Sent By sgraham Date 2015-05-21 Time 10:45 Rev Time 0.00
Received By sgraham Date 2015-05-21 Time 10:45 Sent To  
Notes
2015-05-21 10:47:045/21/15 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE SURVEYS.
 2. MAXIMUM ROOF HEIGHT IS 30' FEET, YOU CAN NOT HAVE A
 36' FEET ROOF