Plan Review Details - Permit 15050482
Plan Review Stops For Permit 15050482
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2015-08-21 Time 06:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-29 Cont ID  
Sent By jwitmer Date 2015-07-29 Time 11:30 Rev Time 0.00
Received By jwitmer Date 2015-07-29 Time 10:31 Sent To  
Notes
2015-07-29 11:29:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050482
 ADD: 915 NORTH DIXIE HWY.
 CONT: CONSTRUCTION REMODELING 1
 TEL: (561)714-0696
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 29/ 2015
 ACTION: DENIED
  
 1) SHEET A1 THE COVER SHEET:
 1A) BUILDING DATA:
 1A)(1) COMPLIED. GYM WITHOUT SEATING.
  
 1A)(2) COMPLIED. 8/09/2015.
  
 2) DISCREPANCY IN PLANS, SHEET A-1. THE FLOOR PLAN SHOW
 INFILL WALLS BETWEEN THE 2 TENANT SPACES. WALL
 IDENTIFICATION TAG IS LABELED A "C" TYPE WALL. BENEATH
 THE FLOOR PLAN THE WALL LEGEND INDICATES WALL TYPE C TO
 BE A (2) HOUR FIRE RATED WALL. NOTE UNDER WALL TYPE C
 SEE SECTION DWRAIL 2/A1. WHEN VIEWING THIS SECTION IT
 IS INDICATED AS A (1) HOUR FIRE RATED WALL. NOTE NO UL
 OR GYPSUM NUMBER IDENTIFYING THE ASSEMBLY.
  
 PLEASE ALSO NOTE THE TERM OR CAN NOT BE USED. THE WALL
 TYPE HAS TO BE SPECIFIC. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 2A) COMPLIED.
  
 2B) SEMI- COMPLIED.WITH THE DISCREPANCY LISTED IN
 COMMENT (2) PLANS WILL BE CORRECT. WITH THE NEW TENANCY
 DELINEATION BETWEEN THE BUSINESS OCCUPANCY AND ASSEMBLY
 OCCUPANCY AND THE OCCUPANCY SEPARATION WALL AT EAST
 RESTROOM. 2010 FBC-B TABLE 508.4 & 707.3.8 FIRE
 BARRIERS SEPARATING MIXED OCCUPANCIES.
  
 3) COMPLIED.
  
 4) 2ND REQUEST. RESPONSE INDICATES THAT SURVEY WAS
 ATTACHED, WHERE? PLEASE PROVIDE A SITE PLAN OR SURVEY
 WITH THE REAR PROPERTY LINE INDICATED, TO VERIFY THE
 NEW REAR EXIT DOOR DOES NOT ROSS OVER THE PROPERTY
 LINE.
 2010 FBC-B 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC REIGHT -OF-WAY.
  
 5&6) COMPLIED.
  
 7)2ND REQUEST. PLEASE NOTE THE SUBMITTED DOOR APPROVAL
 IS FOR A DAYBAR LS -18 DOOR AND FRAME ONLY. SHEET A-1
 SHOWS A SIDELITE AND DOOR.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 8) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9-10) COMPLIED.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By jwitmer Date 2015-06-10 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2015-06-10 Time 08:02 Sent To  
Notes
2015-06-10 10:17:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050482
 ADD: 915 NORTH DIXIE HWY.
 CONT: CONSTRUCTION REMODELING 1
 TEL: (561)714-0696
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 10/ 2015
 ACTION: DENIED
  
 1) SHEET A1 THE COVER SHEET:
 1A) BUILDING DATA:
 1A)(1) THE OCCUPANCY TYPE IS LISTED AS BUSINESS WITH A
 SQUARE FOOTAGE OF 4173 SQ. FT. PLEASE NOTE THE LAST
 KNOWN USE WAS UNDER PERMIT # 08030500
 A MIXED USE BUILDING, BUSINESS: LAW OFFICES & S2
 PARKING GARAGE. THE WORK TO BE COMPLETED UNDER THIS
 PERMIT IS IN THE PORTION OF THE MIXED USE KNOWN TO BE A
 S2 OCCUPANCY THE PARKING GARAGE, WITH AN AREA OF 4173
 SQ. FT. THIS WILL BE A CHANGE OF OCCUANCY TO AN A3 A
 GYM. SEE THE 2010 FBC-B 303.1 IS THE GYM WITHOUT
 SPECTATOR SEATING? IF NO SPECTATOR SEATING THE
 OCCUPANCY CLASSIFICATION WOULD BE A A-3. IF THERE IS
 SPECTATOR SEATING THE OCCUPANCY CLASSIFICATION WILL BE
 A A-4.
  
 1A)(2) OCCUPANT LOAD IS TAKEN FOR A BUSINESS OCCUPANCY
 @ 100 SQ. FT. PER OCCUPANT. SHEET A-1 DOES NOT SHOW ANY
 EQUIPMENT FOR THE GYM SO THE OCCUPANT LOAD IS TAKEN @
 15 SQ. FT. PER OCCUPANT. FBC-B TABLE 1004.1.1, THE
 OCCUPANT LOAD WILL BE 4173/ 15= 279 OCCUPANTS.
  
 2) PLEASE REVIEW THE 2010 FBC-B TABLE 508.4 REQUIRED
 OCCUPANCY SEPARATION, FOR NON-SPRINKLERED BUILINGS
 BETWEEN A BUSINESS OCCUPANCY AND A ASSEMBLY OCCUPANCY
 THE OCCUPANY SEPARATION WALLS REQUIRE A 2 HOUR FIRE
 SEPARATION. UNDER THE PERMIT # 08030500 THE DRESSING
 ROOM, SHOWER AND THE (2) ACCESSIBLE RESTROOMS WERE PART
 OF THE REQUIRED PLUMBING FIXTURE COUNT FOR THE LAW
 OFFICES.
  
 2A) PLEASE INDICATE HOW THE OTHER EXISTING TENANT
 (BUSINESS OCCUPANCY) SPACE WILL REMAIN CODE COMPLIANT
 WITH THE REMOVAL OF THESE RESTROOMS FROM THAT TENANTCY?
 FBC-B 102.6 EXISTING STRUCTURES THAT WERE CODE
 COMPLIANT ARE STILL CODE COMPLIANT WHEN NO WORK IS
 COMPLETED. UNDER THE SCOPE OF THIS PERMIT YOU MAY BE
 CREATING A NON-CONFORMITY IN THE CODE BY NOT HAVING
 ENOUGH RESTROOMS FOR THE OCCUPANT LOAD.
  
 2B) WITH THE NEW TENANCY DELINEATION BETWEEN THE
 BUSINESS OCCUPANCY AND ASSEMBLY OCCUPANCY AND THE
 OCCUPANCY SEPARATION WALL CHANGING LOCATION AT THE
 DRESSING ROOM, SHOWER, RESTROOMS AND INFILL DOOR
 OPENINGS, PLEASE PROVIDE DOCUMENTATION OF HOW THE NEW
 WALLS WILL BE BUILT TO MAINTAIN A 2 HOUR FIRE
 SEPERATION BETWEEN THE (2) OCCUPANCIES. 2010 FBC-B
 TABLE 508.4 & 707.3.8 FIRE BARRIERS SEPARATING MIXED
 OCCUPANCIES.
  
 3) SHEET A1 EXTERIOR WALL DETAIL INDICATES WITHIN THE
 NOTES THE STRUCTURAL PLANS ARE DESIGNED TO THE 2010
 FLORIDA RESIDENTIAL CODE, PLEASE CORRECT, THIS IS UNDER
 THE 2010 FLORIDA BUILDING CODE- BUILDING CODE.
  
 4) PLEASE PROVIDE A SITE PLAN OR SURVEY WITH THE REAR
 PROPERTY LINE INDICATED, TO VERIFY THE NEW REAR EXIT
 DOOR DOES NOT ROSS OVER THE PROPERTY LINE.
 2010 FBC-B 3202.2 DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC REIGHT -OF-WAY.
  
 5) SHEET A1 THE WIND DESIGN INDICATES THE WIND DESIGN
 AS 170 MPH, EXPOSURE B, PLEASE PROVIDE THE MEAN ROOF
 HEIGHT AND PRESSURES IN VASD. FBC-B 1609.1.5/
 1609.1.2.3.1.
  
 6) SHEET A1 DETAIL # 3 INDICATES THERE TO BE A NEW
 LINTEL AND A # 5 24 INCHES LONG VERTICALLY DOWELLED
 INTO EVERY EXISTING FILLED CELL ABOVE. THE PLANS DO NOT
 INDICATE HOW THE NEW #5 REINFORCING BARS ARE TO TIE
 INTO THE FOOTING AND TO THE BEAM ABOVE TO BE PART OF
 THE MWFRS MAIN WIND FORCE RESISTING SYSTEM, NOR HOW
 MUCH EMBEDDMENT INTO THE FOUNDATION AND BEAM ABOVE IS
 REQUIRED.
  
 7) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE NEW
 EXTERIOR SWING DOOR. 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) THE A-1 SHEET DOESN'T SHOW THE LOCATION OF THE
 REQUIRED FIRE EXTINGUISHERS PER FBC-B 906.1.1.
  
 10) MISSING ON THE PLANS THE INTERIOR FINISH
 CLASSIFICATION EXIST. BLDG CODE.912.3.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-20 Cont ID  
Sent By albarran Date 2015-07-20 Time 13:48 Rev Time 0.00
Received By albarran Date 2015-07-20 Time 13:36 Sent To  
Notes
2015-07-20 13:50:40ALL PREVIOUS ELECTRICAL COMMENTS HAVE BEEN SATISFIED,
 RETURNED TO B27

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 15:49 Rev Time 0.00
Received By albarran Date 2015-07-07 Time 14:42 Sent To I
Notes
2015-07-07 15:44:44PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 1. CORRECT THE ELECTRICAL RISER DIAGRAM TO SHOW THE
 ELECTRIC METER AHEAD OF THE MAIN DISCONNECT.
 2. INDICATE PROPER GROUNDING FOR THE SERVICE ON THE
 RISER DIAGRAM.
 3. PER FBC-B EMERGENCY LIGHTING IS REQUIRED IN THE
 BATHROOMS
 4. NEC 600.5 REQUIRES A DEDICATED 20 AMP CIRCUIT FOR
 SIGNAGE IN AN ACCESSIBLE LOCATION CLOSE TO EACH
 ENTRANCE. (THE OVERHEAD DOOR DOES NOT COUNT).
 5. ADDITIONAL EMERGENCY LIGHTS MAY BE REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-08-19 Cont ID  
Sent By pleduc Date 2015-08-19 Time   Rev Time 0.00
Received By pleduc Date 2015-08-19 Time 10:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-07-16 Cont ID  
Sent By pleduc Date 2015-07-16 Time   Rev Time 0.00
Received By pleduc Date 2015-07-16 Time 14:21 Sent To  
Notes
2015-07-16 15:00:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET LS-1 INDICATES THE OCCUPANCY AS BUSINESS
 100/SQ FT/PERSON. BASED ON THE INFORMATION PROVIDED
 THIS IS AN ASSEMBLY OCCUPANCY PER NFPA 1 AND NFPA 101.
 PER CHAPTER 7 OF NFPA 101, 50/SQ FT/PERSON IS REQUIRED.
  
 2) THE OCCUPANCY SHALL COMPLY WITH REQUIREMENTS OF NFPA
 1 & 101 ASSEMBLEY OCCUPANCIES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By pleduc Date 2015-05-15 Time   Rev Time 0.00
Received By pleduc Date 2015-05-15 Time 14:09 Sent To  
Notes
2015-05-15 14:48:07THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) PROVIDE DIMENSIONS TO ALL WALLS.
  
 2) PROVIDE AN ENTIRE BUILDING LAYOUT, NOT JUST THIS
 SPACE, ON THE SITE PLAN.
  
 3) PROVIDE A COMPLETE LIFE SAFETY PLAN THAT ILLUSTRATES
 OCCUPANT LOAD, TRAVEL DISTANCES, COMMON PATHS OF
 TRAVEL, EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING
 TO A PUBLIC WAY, FIRE EXTINGUISHER LOCAIONS.
  
 4) PROVIDE A DOOR SCHEDULE THAT INCLUDES LATCH HARDWARE
 AND LOCKING MECHANISMS. BASED ON OCCUPANCY LOAD PANIC
 HARDWARE MAY BE REQUIRED.
  
 5) THE FIRE RESISTIVE RATING OF THE SEPARATION WALLS
 SHALL COMPLY WITH THE MINIMUM RATING REQUIREMENTS OF
 THE FLORIDA BUILDING CODE AND THE OCCUPANCIES THAT ARE
 SEPARATED. PROVIDE ADJACENT OCCUPANCY CLASSIFICATIONS
 AND REQUIRED SEPARATIONR FIRE RATING PER EXACT SECTION
 OF THE FLORIDA BUILDING CODE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2015-08-17 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-29 Cont ID  
Sent By skennedy Date 2015-07-29 Time 13:23 Rev Time 0.00
Received By skennedy Date 2015-07-13 Time 16:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 15:44 Rev Time 0.00
Received By albarran Date 2015-05-14 Time 07:51 Sent To  
Notes
2015-07-07 15:48:227/7/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "C". MA
2015-05-15 07:46:57B27
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 06:07 Rev Time 0.00
Received By jwitmer Date 2015-08-21 Time 06:01 Sent To  
Notes
2015-08-21 06:07:36P. B. C. IMPACT FEE OFFICE
 MU-2015-19764
 4300 SQ. FT. / GYM
 PERMIT TECH DB EUC
 FEES BY W. SWOOPE
 AMOUNT PAID $0.00.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-07-29 Cont ID  
Sent By jwitmer Date 2015-07-29 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2015-07-29 Time 11:29 Sent To  
Notes
2015-07-29 11:30:1011) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-06-10 Cont ID  
Sent By jwitmer Date 2015-06-10 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2015-06-10 Time 13:19 Sent To  
Notes
2015-06-10 13:20:10BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-29 Cont ID  
Sent By tklarge Date 2015-07-29 Time 08:29 Rev Time 0.00
Received By tklarge Date 2015-07-29 Time 06:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-13 Cont ID  
Sent By tklarge Date 2015-06-13 Time 05:03 Rev Time 0.00
Received By tklarge Date 2015-06-13 Time 03:32 Sent To  
Notes
2015-06-13 04:03:461) THE CREATION OF THE NEW UNIT TO A GYM IS INCLUDING
 THE EXISTING TOILET ROOMS THAT WERE PREVIOUSLY LOCATED
 IN THE ADJACENT ATTORNEY'S OFFICE. AFTER LOOKING AT THE
 BUILDOUT PLANS FOR THE ATTORNEY'S OFFICE FROM 2008, IT
 APPEARS THE ATTORNEY'S OFFICE WILL BE DEFICIENT IN THE
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES PER THE
 2010 FPC TABLE 403.1.THE INCLUSION OF THE EXISTING
 TOILET ROOMS WILL CAUSE THE NON-CONFORMITY OF THE
 ADJACENT TENANT SPACE.REFER TO WPB AMENDMENTS TO 2010
 FBC SEC.102.6.
 2) SUBMIT AN ENLARGED PLAN OF THE ACCESSIBLE SHOWER AND
 SHOW THE CLEAR INSIDE DIMENSIONS OF THE SHOWER. COMPLY
 WITH 2010 FBC-ACCESSIBILITY SEC.608.
 3) SHT.P-1 - ELEVATIONS - THE MEASUREMENTS SHOWN ON THE
 DETAILS ARE SO SMALL THEY ARE ILLEGIBLE. SUBMIT CLEAR
 AND LEGIBLE DETAILS FOR REVIEW PER WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 4) SUBMIT 2 COPIES OF MANUF. SPECIFICATION SHEETS FOR
 THE AQUATIC ADA SHOWER COMPARTMENT. AT A MINIMUM,
 PREFAB UNITS SHALL COMPLY WITH 2010 FPC SEC.417.1.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-08-17 Cont ID  
Sent By skennedy Date 2015-07-29 Time 13:22 Rev Time 0.00
Received By aaponte Date   Time   Sent To  
Notes
2015-07-29 13:23:20NEW COVER SHEET TO BE SUBMITTED ON 3RD CYCLE. AA TO
 RE-REVIEW OR STAMP THEN.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-24 Cont ID  
Sent By aaponte Date 2015-06-24 Time 16:59 Rev Time 0.00
Received By aaponte Date 2015-06-24 Time 16:52 Sent To  
Notes
***NONE***