Plan Review Details - Permit 15050449
Plan Review Stops For Permit 15050449
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-19 Cont ID  
Sent By dhayes Date 2015-05-19 Time 16:31 Rev Time 0.00
Received By dhayes Date 2015-05-19 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-16 Cont ID  
Sent By dhayes Date 2015-05-16 Time 13:51 Rev Time 0.00
Received By dhayes Date 2015-05-16 Time 13:51 Sent To  
Notes
2015-05-16 14:23:595/16/2015
 PROJECT: 133 MURRAY RD SERVICE CHANGE
 PERMIT#:15050449
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1STELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE A PANEL SCHEDULE FOR EACH PANEL INDICATING
 THE OCPD AND WIRE SIZE FOR EACH CIRCUIT. NEC 408.4
  
 2) INDICATE ON THE RISER DIAGRAM THE CONDUIT AND WIRE
 SIZE FOR THE SERVICE ENTRANCE AND FOR EACH OF THE
 SUB-FEEDS.
  
 3) INDICATE THE SIZE OF THE FEED THROUGH BRANCH WIRING
 NIPPLE FROM PANEL "A" AND INDICATE WHAT IS ON THE BACK
 SIDE OF PANEL "A" TO RECEIVE THE BRANCH WIRING LEAVING
 PANEL "A" THROUGH THIS NEW NIPPLE.
  
 4) REVISE THE SERVICE ENTRANCE CONDUCTORS TO EACH OF
 THE MAIN BREAKERS PANELS. THE RISER DIAGRAM INDICATES
 THE USE OF 2/0CU TO EACH MAIN. IF THERE WERE ONLY ONE
 MAIN YOU COULD UTILIZE NEC 310.15(B)(6) WHICH WOULD
 ALLOW THE USE OF 2/0CU. HOWEVER, THERE ARE TWO MAINS.
 THEREFORE THIS ARTICLE DOES NOT APPLY AND YOU NEED TO
 USE NEC 310.16 TO SIZE YOUR SERVICE ENTRANCE AND
 FEEDERS.
  
 5) INDICATE ON THE RISER DIAGRAM THE INSTALLATION OF A
 GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH THE NEC
 250.50, 250.52, 250.66, AND 250.94
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-05-13 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2015-05-16 13:49:48NOT REVIEWED. THE CUSTOMER CALLED FROM THE COUNTER
 WHILE HE WAS THERE SUBMTTING. WE WENT OVER HIS
 SUBMITTAL AT THE COUNTER AND AGREED IT WAS NOT
 SUFFICIENT TO PASS A REVIEW. THE CUSTOMER AGREED TO
 RESUBMIT THE FOLLOWING DAY.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-19 Cont ID  
Sent By dhayes Date 2015-05-19 Time 16:31 Rev Time 0.00
Received By dhayes Date 2015-05-19 Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-16 Cont ID  
Sent By dhayes Date 2015-05-16 Time 14:24 Rev Time 0.00
Received By dhayes Date 2015-05-14 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-13 Cont ID  
Sent By   Date 2015-05-13 Time   Rev Time 0.00
Received By   Date 2015-05-13 Time   Sent To  
Notes
2015-05-13 12:45:00ELECTRICAL UNDER 5K