Plan Review Details - Permit 15050395
Plan Review Stops For Permit 15050395
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-03 Cont ID  
Sent By shill Date 2015-06-03 Time 15:54 Rev Time 0.00
Received By shill Date 2015-06-03 Time 15:54 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-27 Cont ID  
Sent By jgomez Date 2015-05-27 Time 16:30 Rev Time 0.00
Received By dhayes Date 2015-05-27 Time 16:19 Sent To B
Notes
2015-05-27 16:30:44APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) VERIFY THE WATER HEATER HAS THE REQUIRED ELECTRIC
 DISCONNECT. NEC 422.31
  
 2) ALL COMPONENTS SHALL BE LISTED OR LABELED EQUIPMENT
 SHALL BE INSTALLED AND USED IN ACCORDANCE WITH ANY
 INSTRUCTIONS INCLUDED IN THE LISTING OR LABELING. NEC
 110.3(B)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-05 Cont ID  
Sent By tklarge Date 2015-06-05 Time 05:03 Rev Time 0.00
Received By tklarge Date 2015-05-12 Time 08:18 Sent To  
Notes
2015-06-03 15:55:196/3 TO PLUMBING BOX
  
2015-05-13 08:19:03SENT TO ELECTRICAL UNDER $5000 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-06-05 Cont ID  
Sent By tklarge Date 2015-06-05 Time 05:03 Rev Time 0.00
Received By tklarge Date 2015-06-05 Time 04:45 Sent To  
Notes
***NONE***