Plan Review Details - Permit 15050268
Plan Review Stops For Permit 15050268 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2015-05-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-05-21 |
Time |
16:27 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-05-21 |
Time |
13:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2015-05-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-05-23 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-05-23 |
Time |
10:11 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-05-21 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-21 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-05-21 |
Time |
16:26 |
Sent To |
|
|
Notes |
2015-05-21 16:31:29 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE LOCATION OF SUB PANEL "A" ON THE | | ELECTRICAL FLOOR PLANS. FBC 107.2.1 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-05-27 |
|
|
Cont ID |
|
Sent By |
mmanhong |
Date |
2015-05-27 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
mmanhong |
Date |
2015-05-27 |
Time |
13:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2015-05-23 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-05-23 |
Time |
10:12 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-05-23 |
Time |
10:12 |
Sent To |
|
|
Notes |
2015-05-23 10:13:18 | CONTRACTOR PROVIDED MISSING DUCT SIZES WHICH ARE | | REDLINED ON THE PLANS. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-05-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-05-21 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-05-21 |
Time |
13:08 |
Sent To |
|
|
Notes |
2015-05-21 16:29:55 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SOME OF THE SUPPLY AND RETURN DUCT SIZES ARE NOT | | SPECIFIED ON THE PLANS. FBC 107.2.1 | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2015-05-21 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-21 |
Time |
11:55 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-05-21 |
Time |
11:55 |
Sent To |
|
|
Notes |
2015-05-21 11:55:41 | REDLINED PLANS |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2015-05-27 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2015-05-27 |
Time |
12:37 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2015-05-27 |
Time |
12:37 |
Sent To |
B |
|
Notes |
|
|
|