Plan Review Details - Permit 15050258
Plan Review Stops For Permit 15050258
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-17 Cont ID  
Sent By rmcdouga Date 2015-06-17 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2015-06-17 Time 11:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-08 Cont ID  
Sent By rmcdouga Date 2015-05-08 Time 15:24 Rev Time 0.00
Received By rmcdouga Date 2015-05-08 Time 15:13 Sent To  
Notes
2015-05-08 15:48:01PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE TWO (2) SETS OF AN EVALUATION REPORT FROM A
 CERTIFIED ROOFING CONSULTANT OF THE EXISTING ROOF
 SYSTEM'S ABILITY TO RESIST PROJECT DESIGN PRESSURES AND
 FOR COMPATIBILITY AND BOND PERFORMANCE WITH THE
 SELECTED ADHESIVE AS DOCUMENTED THROUGH FIELD UPLIFT
 TESTING IN ACCORDANCE WITH ASTM E907, FM LPDS 1-52 OR
 ANSI/SPRI IA-1. SEE NOTE 12 ON PAGE 2 OF 39.