Plan Review Details - Permit 15050180
Plan Review Stops For Permit 15050180
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By dhayes Date 2015-06-08 Time 13:30 Rev Time 0.00
Received By dhayes Date 2015-06-08 Time 11:08 Sent To  
Notes
2015-06-08 11:09:276/8/2015
 PROJECT: KITCHEN REMODEL
 PERMIT#: 15050180
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) NEC 210.52(A)
 VERIFY RECEPTACLE SPACING. THERE APPEAR TO BE WALLS IN
 NEED OF RECEPTACLES TO MEET THIS MINIMUM REQUIREMENT.
 SEE THE DINING ROOM WALLS SPECIFICALLY.
  
 2) NEC 210.7 (B)
 THE PANEL SCHEDULE INDICATES CIRCUITS 5 AND 7 ARE FOR
 THE DISHWASHER AND DISPOSAL BUT INDICATE A SINGLE
 RECEPTACLE FEEDING BOTH. WHERE TWO OR MORE BRANCH
 CIRCUITS SUPPLY DEVICES OR EQUIPMENT ON THE SAME YOKE,
 A MEANS TO SIMULTANEOUSLY DISCONNECT THE UNGROUNDED
 CONDUCTORS SUPPLYING THOSE DEVICES SHALL BE PROVIDED AT
 THE POINT AT WHICH THE BRANCH CIRCUITS ORIGINATE.
  
 3) NEC 422.31
 A DISCONNECT IS REQUIRED FOR THE WATER HEATER.
  
 4) FBC-RESIDENTIAL 314 AND 315.
 SMOKE DETECTORS ARE REQUIRED TO BE INSTALLED INSIDE AND
 OUTSIDE OF SLEEPING AREAS. WHEN ALTERATIONS, REPAIRS,
 OR ADDITIONS REQUIRING A PERMIT OCCUR, OR WHEN ONE OR
 MORE SLEEPING ROOMS ARE ADDED OR CREATED IN EXISTING
 DWELLINGS, THE INDIVIDUAL DWELLING UNIT SHALL BE
 EQUIPPED WITH SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS.
  
 5) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-07 Cont ID  
Sent By dhayes Date 2015-05-07 Time 12:40 Rev Time 0.00
Received By dhayes Date 2015-05-07 Time 11:57 Sent To  
Notes
2015-05-07 12:40:025/7/2015
 PROJECT: KITCHEN REMODEL
 PERMIT#: 15050180
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 210.52(A)
 VERIFY RECEPTACLE SPACING. THERE APPEAR TO BE WALLS IN
 NEED OF RECEPTACLES TO MEET THIS MINIMUM REQUIREMENT.
  
 2) WPB AMENDMENTS TO FBC 107.3.5.1.2
 PROVIDE ADDITIONAL DETAIL TO SUPPORT THE RELOCATION OF
 THE BREAKER PANEL INCLUDING HOW ALL EXISTING BRANCH
 CIRCUITS WILL BE RELOCATED. PROVIDE A DESIGN DETAIL
 ILLUSTRATING METHODS AND MATERIALS PROPOSED.
  
 3) NEC 210.8(6)
 ALL ALL OUTLETS IN THE KITCHEN SHALL HAVE GFI
 PROTECTION FOR PERSONELL.
  
 4) PROVIDE DIMENSIONS FOR NEW LOCATION OF PANELBOARD TO
 SHOW COMPLIANCE WITH THE NEC 110.26
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-08 Cont ID  
Sent By dhayes Date 2015-06-08 Time 13:30 Rev Time 0.00
Received By dhayes Date 2015-05-18 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-28 Cont ID  
Sent By dhayes Date 2015-05-07 Time 14:36 Rev Time 0.00
Received By dhayes Date 2015-05-06 Time 12:43 Sent To  
Notes
2015-05-07 12:43:13TRAVELLING WITH MASTER 15041147 IN B11


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved