Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By pleduc Date 2015-06-10 Time 16:00 Rev Time 0.00
Received By albarran Date 2015-06-08 Time 13:47 Sent To FIRE
Notes
2015-06-08 14:06:34IMPORTANT NOTICE:
 FOR FINAL INSPECTION A REACCEPTANCE TEST REPORT AS
 DESCRIBED IN 2013 NFPA 72 SECTION 14.4.2 SHALL BE
 PROVIDED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-29 Cont ID  
Sent By albarran Date 2015-05-29 Time 10:42 Rev Time 0.00
Received By albarran Date 2015-05-29 Time 10:17 Sent To  
Notes
2015-05-29 11:00:45THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
 1. THESE PLANS FAIL TO PROPERLY DEFINE THE SCOPE OF
 WORK.
 2. THE RISER DIAGRAM INDICATES THAT ONLY THREE (3) NEW
 DEVICES ARE BEING INSTALLED
 3. AS PART OF THE NEW DEVICES BEING INSTALLED, A NEW
 SMOKE DETECTOR IN THE ELECTRIC ROOM WHICH SHOULD HAVE
 ALREADY HAD ONE THERE. CHECK THE DEVICE PLACEMENT AS
 SHOWN ON THE PLANS WITH THE ACTUAL SCOPE OF WORK. AND
 CORRECT THE DRAWINGS ACCORDINGLY.
 I SPOKE WITH MICHAEL COTTIERO OF KNIGHT FIRE & SECURITY
 ON THIS OVER THE PHONE.
  
 THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008
 EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE
 APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA
 BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND
 FLORIDA BUILDING CODE ENERGY CONSERVATION.
  
 FOR QUESTIONS ON THE ABOVE, PLEASE CONTACT:
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 PH: (561) 805-7943
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-10 Cont ID  
Sent By pleduc Date 2015-06-10 Time   Rev Time 0.00
Received By pleduc Date 2015-06-10 Time 15:18 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-14 Cont ID  
Sent By pleduc Date 2015-05-14 Time   Rev Time 0.00
Received By pleduc Date 2015-05-14 Time 11:35 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-10 Cont ID  
Sent By malbarra Date 2015-06-10 Time   Rev Time 0.00
Received By pleduc Date 2015-06-05 Time   Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-29 Cont ID  
Sent By albarran Date 2015-05-29 Time 11:01 Rev Time  
Received By albarran Date 2015-05-13 Time   Sent To  
Notes
2015-05-29 11:01:40SENT TO SMALL DENIED BIN "K". MA
2015-05-13 18:51:47SENT TO FIRE BOX.