Plan Review Details - Permit 15050177
Plan Review Stops For Permit 15050177
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-09-10 Cont ID  
Sent By jwitmer Date 2015-09-10 Time 13:08 Rev Time 0.00
Received By jwitmer Date 2015-09-10 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-08-26 Cont ID  
Sent By jwitmer Date 2015-08-26 Time 10:31 Rev Time 0.00
Received By jwitmer Date 2015-08-24 Time   Sent To  
Notes
2015-08-24 16:20:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050177
 ADD: 1152 OKEECHOBEE RD
 CONT: ABACOA CONSTRUCTION
 TEL: (561)722-3890
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WEDNESDAY JULY 22/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) THE RAISED PLATFORM 20 INCHES ABOVE THE FLOOR DOES
 INDICATE VERTICAL ACCESSIBILITY WILL BE ACHIEVED BY A
 RAMP. THE PLANS INDICATE 20 FEET OF RUN, BUT THERE IS A
 LANDING AT THE TOP OF THE RAMP WHERE A 90 DEGREE TURN
 MUST BE MADE. PLEASE SHOW COMPLIANCE WITH:
  
 4A) 2010 FBC-ACCESSIBILITY 405.7.4 CHANGE IN DIRECTION.
 RAMPS THAT CHANGE DIRECTION BETWEEN RUNS AT LANDINGS
 SHALL HAVE A CLEAR LANDING 60 INCHES (1525 MM) MINIMUM
 BY 60 INCHES (1525 MM) MINIMUM.
  
 4B) ACCESSIBILITY 405.8 HANDRAILS. RAMP RUNS WITH A
 RISE GREATER THAN 6 INCHES (150 MM) SHALL HAVE
 HANDRAILS COMPLYING WITH 505.
 505.3 CONTINUITY.
 HANDRAILS SHALL BE CONTINUOUS WITHIN THE FULL LENGTH OF
 EACH STAIR FLIGHT OR RAMP RUN. INSIDE HANDRAILS ON
 SWITCHBACK OR DOGLEG STAIRS AND RAMPS SHALL BE
 CONTINUOUS BETWEEN FLIGHTS OR RUNS.
  
 505.4 HEIGHT. TOP OF GRIPPING SURFACES OF HANDRAILS
 SHALL BE 34 INCHES (865 MM) MINIMUM AND 38 INCHES (965
 MM) MAXIMUM VERTICALLY ABOVE WALKING SURFACES, STAIR
 NOSINGS, AND RAMP SURFACES. HANDRAILS SHALL BE AT A
 CONSISTENT HEIGHT ABOVE WALKING SURFACES, STAIR
 NOSINGS, AND RAMP SURFACES.
  
 4C) 405.9 EDGE PROTECTION. EDGE PROTECTION COMPLYING
 WITH 405.9.1 OR 405.9.2 SHALL BE PROVIDED ON EACH SIDE
 OF RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS.
  
  
 5-9) COMPLIED.
  
 10) THE MECHANICAL PLANS ALSO SHOW WALL LOUVERS AND
 ROOF TOP A/C STANDS. PLEASE PROVIDE COMPLIANCE WITH:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS
 (G) PRE-ENGINEERED A/C STANDS
  
 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 14:03 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2015-07-22 14:03:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050177
 ADD: 1152 OKEECHOBEE RD
 CONT: ABACOA CONSTRUCTION
 TEL: (561)722-3890
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WEDNESDAY JULY 22/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED.
  
 4) THE PLATFORM DOES INDICATEVERTICAL ACCESSIBILITY
 WILL BE ACHIEVED BY A PLATFORM LIFT. , PLEASE PROVIDE
 COMPLIANCE WITH THE 2010 FBC-ACCESSIBILITY CODE,
 201.1.1 VERTICAL ACCESSIBILITYSECTIONS 553.501-553.513,
 F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN DO
 NOT RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE OR
 FACILITY GOVERNED BY THOSE SECTIONS FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND
 BELOW THE OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER
 THE STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN
 SUCH BUILDING, STRUCTURE OR FACILITY. PLEASE PROVIDE
 THE MANUFACTURERS LIFT DESIGN CRITERIA.
  
 PLATFORM LIFTS ARE TO MEET THE ASME A18.1 STANDARDS.
 PLEASE SHOW COMPLIANCE WITH 410 PLATFORM LIFTS:
  
 410.1 GENERAL.
 PLATFORM LIFTS SHALL COMPLY WITH ASME A18.1 (1999
 EDITION OR 2003 EDITION) (INCORPORATED BY REFERENCE,
 SEE ?REFERENCED STANDARDS? IN CHAPTER 1). PLATFORM
 LIFTS SHALL NOT BE ATTENDANT-OPERATED AND SHALL PROVIDE
 UNASSISTED ENTRY AND EXIT FROM THE LIFT.
  
 410.2 FLOOR SURFACES.
 FLOOR SURFACES IN PLATFORM LIFTS SHALL COMPLY WITH 302
 AND 303.
  
 410.3 CLEAR FLOOR SPACE.
 CLEAR FLOOR SPACE IN PLATFORM LIFTS SHALL COMPLY WITH
 305.
  
 410.4 PLATFORM TO RUNWAY CLEARANCE.
 THE CLEARANCE BETWEEN THE PLATFORM SILL AND THE EDGE OF
 ANY RUNWAY LANDING SHALL BE 1 INCH (32 MM) MAXIMUM.
  
 410.5 OPERABLE PARTS.
 CONTROLS FOR PLATFORM LIFTS SHALL COMPLY WITH 309.
  
 410.6 DOORS AND GATES.
 PLATFORM LIFTS SHALL HAVE LOW-ENERGY POWER-OPERATED
 DOORS OR GATES COMPLYING WITH 404.3. DOORS SHALL REMAIN
 OPEN FOR 20 SECONDS MINIMUM. END DOORS AND GATES SHALL
 PROVIDE A CLEAR WIDTH 32 INCHES (815 MM) MINIMUM. SIDE
 DOORS AND GATES SHALL PROVIDE A CLEAR WIDTH 42 INCHES
 (1065 MM) MINIMUM.
  
 5-7) COMPLIED.
  
 8) 2ND REQUEST. SHEET LS-1 THE DOOR SCHEDULE SHOWS DOOR
 TYPE 1 TO BE A 2'-8" DOORS ARE TO COMPLIANCE FOR FBC-B
 1008.1.1 AND ACCESS. CODE 404.2.3.
  
 9) SHEET LS-1 THE PLANS INDICATES THE STORAGE ROOM TO
 BE 425 SQ. FT. THE OVERALL TOTAL SQUARE FOOTAGE GIVEN
 IS 4,000 SQ. FT. OR OVER 10 % OF THE FLOOR AREA THAT
 CREATES A MIXED USE OCCUPANCY. SEE 2010 FBC-B 508.2.1
 AREA LIMITATIONS. PLEASE REVIEW THE 2010 FBC-B TABLE
 508.4 DEPENDING IF THE STORAGE ROOM IS A S1 OR S2 THE
 ROOM WILL REQUIRE A 1 HR OR 2 HOUR FIRE SEPARATION, NO
 FIRE SPRINKLERS.
  
 10) THE MECHANICAL PLANS (M1) ALSO SHOW WALL LOUVERS
 AND ROOF TOP A/C STANDS. PLEASE PROVIDE COMPLIANCE
 WITH:
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS- OUTSIDE AIR
  
  
 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 12 ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-20 Cont ID  
Sent By jwitmer Date 2015-05-20 Time 11:01 Rev Time  
Received By jwitmer Date 2015-05-19 Time 13:23 Sent To  
Notes
2015-05-19 16:58:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050177
 ADD: 1152 OKEECHOBEE RD
 CONT: ABACOA CONSTRUCTION
 TEL: (561)722-3890
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUESDAY MAY 19/ 2015
 ACTION: DENIED
  
 1) SHEET LS-1 SHOWS A RAISED PLATFORM AND STAGE. SHEET
 D-1 INDICATES A FLOOR LOADING OF 55 LBS. THIS OCCUPANCY
 IS DECLARED AN A2 NIGHTCLUB. THE MINIMUM UNIFORM
 DISTRIBUTED LOADS FOUND IN FBC-B TABLE 1607.1(4) 125
 PSF AND THE STAIRS 100 PSF.
  
 2) SHEET LS-1 THE RAISED PLATFORM WILL NEED TO ALL THE
 RISERS TO BE THE SAME HEIGHT AS REQUIRED IN 2010 FBC-B
 1009.4.2 RISER HEIGHT AND TREAD DEPTH. STAIR RISER
 HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM AND 4 INCHES
 (102 MM) MINIMUM. 1009.4.4 DIMENSIONAL UNIFORMITY.
 STAIR TREADS AND RISERS SHALL BE OF UNIFORM SIZE AND
 SHAPE. THE TOLERANCE BETWEEN THE LARGEST AND SMALLEST
 RISER HEIGHT OR BETWEEN THE LARGEST AND SMALLEST TREAD
 DEPTH SHALL NOT EXCEED 3/8 INCH (9.5 MM) IN ANY FLIGHT
 OF STAIRS.
  
 3) DISCREPANCY IN PLAN, THE PLANS INDICATE 3 RISERS,
 FROM THE CITYS VISIT OF SITE AND PICTURES OF THE
 LOCATION THE REISERS ARE NOT UNIFORM AND REVIEW THE
 AMOUNT OF RISERS SHOWN IN PLAN (3) 3 X 7+ 21 INCHES,
 THE PLANS INDICATE THE PLATFORM HEIGHT OF 14 INCHES.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED
 DESCREPANCY IN PLANS.
  
 4) THE PLATFORM DOES NOT SHOW HOW VERTICAL
 ACCESSIBILITY WILL BE ACHIEVED, PLEASE PROVIDE
 COMPLIANCE WITH THE 2010 FBC-ACCESSIBILITY CODE,
 201.1.1 VERTICAL ACCESSIBILITYSECTIONS 553.501-553.513,
 F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN DO
 NOT RELIEVE THE OWNER OF ANY BUILDING, STRUCTURE OR
 FACILITY GOVERNED BY THOSE SECTIONS FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL LEVELS ABOVE AND
 BELOW THE OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER
 THE STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN
 SUCH BUILDING, STRUCTURE OR FACILITY.
  
 5) THE PLATFORM ALSO IS MISSING A HANDRAIL REQUIRED BY
 FBC-ACCESSIBILITY CODE 504.6 HANDRAILS. STAIRS SHALL
 HAVE HANDRAILS COMPLYING WITH 505. 505.2 WHERE
 REQUIRED. HANDRAILS SHALL BE PROVIDED ON BOTH SIDES OF
 STAIRS AND RAMPS.
  
 505.4 HEIGHT.
 TOP OF GRIPPING SURFACES OF HANDRAILS SHALL BE 34
 INCHES (865 MM) MINIMUM AND 38 INCHES (965 MM) MAXIMUM
 VERTICALLY ABOVE WALKING SURFACES, STAIR NOSINGS, AND
 RAMP SURFACES. HANDRAILS SHALL BE AT A CONSISTENT
 HEIGHT ABOVE WALKING SURFACES, STAIR NOSINGS, AND RAMP
 SURFACES.
  
 505.10 HANDRAIL EXTENSIONS.
 HANDRAIL GRIPPING SURFACES SHALL EXTEND BEYOND AND IN
 THE SAME DIRECTION OF STAIR FLIGHTS AND RAMP RUNS IN
 ACCORDANCE WITH 505.10.
  
 6) THE DJ BOOTH DOES NOT INDICATE IF THIS IS ABOVE THE
 FLOOR OR A PIT BENEATH THE FLOOR LEVEL. SHEET D1 DOES
 NOT GIVE ANY ELEVATIONS NEITHER DOES SHEET LS1.
 107.2.1.3.
  
 7) SHEET LS-1 INDICATES ON THE FLOOR PLAN A BAR AND
 CONCESSION AREA WITH COUNTER, PLEASE PROVIDE COMPLIANCE
 WITH THE 2010 FBC-ACCESSIBLITY CODE 904.4 SALES AND
 SERVICE COUNTERS.
  
 8) SHEET LS-1 PLEASE PROVIDE A DOOR SCHEDULE FOR ALL
 DOORS, COMPLIANCE FOR FBC-B 1008.1.1 AND ACCESS. CODE
 404.2.3.
  
 SHEET LS-1 PLEASE PROVIDE DIMENSIONS FOR ALL RESTROOMS
 AND SHOWER STALLS TO REVIEW FOR REQUIRED ACCESSIBLITY
 ISSUES, PLEASE PROVIDE ENLARGED FLOOR PLAN & ELEVATION
 OF BATHROOMS AND SHOWERS FOR ACCESSIBILITY. SHOW
 CLEARANCES BETWEEN FIXTURES, GRAB BAR HEIGHTS, BACKING
 FOR GRAB BARS ETC... CHAPTER 6 OF FL ACCESS. CODE.
  
 9) SHEET LS-1THE PLANS FAIL TO PROVIDE SQ. FEET AREA OF
 OCCUPANCIES AND ACCESSORY OCUPANCIES INDICATE THE
 SQUARE FOOTAGE OF EACH AREA TO SEE IF THIS BUILDING
 QUALIFIES AS A MIXED USE OCCUPANCY BETWEEN THE A2 AND
 STORGE ROOM. SEE FBC-B TABLE 508.4 FOR HOUR RATINGS.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2015-09-14 Cont ID  
Sent By albarran Date 2015-09-14 Time 14:22 Rev Time 0.00
Received By albarran Date   Time   Sent To I
Notes
2015-09-14 14:22:54THIRD ELECTRICAL STOP WAS NOT NECESSARY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-21 Cont ID  
Sent By albarran Date 2015-07-21 Time 14:00 Rev Time 0.00
Received By albarran Date 2015-07-20 Time 18:22 Sent To B
Notes
2015-07-21 14:22:12ELECTRICAL PROVISO: NEC 210.8 RECEPTACLES WITHIN 6' OF
 A SINK SHALL BE GFCI PROTECTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-11 Cont ID  
Sent By albarran Date 2015-05-11 Time 17:23 Rev Time 0.00
Received By albarran Date 2015-05-11 Time 15:58 Sent To B
Notes
2015-05-11 19:07:00COMMENTSN AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN
 REVIEW
 PERMIT #: 15050177
 DATE: 5/11/15
 APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010
 CHAPTER 1; NEC 2008
 REVIEW CYCLE: 1
 ACTION: FAILED
  
 1. PER FBC 907.2.1, GROUP A BLDGS W/AN OCCUPANT LOAD OF
 300 OR GREATER ARE REQUIRED TO HAVE A FIRE ALARM SYSTEM
 INSTALLED (SEE FIRE REVIEW)
 2. THE FIRE ALARM SYSTEM SHALL BE ON A SEPARATE PERMIT
 AND SUBMITTAL ACCOMPANIED BY THE PROPER FIRE ALARM
 DRAWINGS.
 3, MISSING EXIT LIGHT IN STORAGE ROOM, LOCKER ROOM AND
 IN THE AREA MID-WAY AS YOU EXIT THE REAR AREA INTO THE
 LOUNGE.
 4. OUTLETS BEHIND THE BAR, IF WITHIN 6' OF THE SINK
 SHALL BE GFI PROTECTED.
 5. AS PER NEC 210.62, YOU ARE REQUIRED TO HAVE AN
 OUTLET AT THE TOP OF EVERY SHOW WINDOW FOR EVERY 12' OR
 FRACTION THEREOF. THIS OUTLET SHALL BE WITHIN 18" OF
 THE TOP OF THE WINDOW.
 6.AS PER NEC 600.5, YOU ARE TO HAVE A DEDICATED SIGN
 OUTLET LOCATED ACCESSIBLE ABOVE EVERY ENTRANCE.
 7. AS PER NEC 700.12(F) EMERGENCY LIGHTING SHALL BE ON
 THE SAME LIGHTING CIRCUIT AS THE AREA THEY OCCUPY.
 INDICATE LIGHTING CIRCUIT NUMBER TO ASCERTAIN
 COMPLIANCE.
 8. AS PER FBC 2010 ENERGY 502.3.8, ALL RECESSED
 LIGHTING SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACE.
 9. AS PER FBC 2010 ENERGY, ALL LIGHTING SHALL COMPLY
 WITH SECTION 505.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-07-07 Cont ID  
Sent By scaldero Date 2015-07-07 Time 13:37 Rev Time 0.00
Received By scaldero Date 2015-07-07 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-11 Cont ID  
Sent By scaldero Date 2015-05-11 Time 14:38 Rev Time 0.00
Received By scaldero Date 2015-05-11 Time 13:38 Sent To  
Notes
2015-05-11 14:36:29PERMIT # 15050177
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLAN APPROVED WITH COMMENTS. ALL COMMENTS MUST BE
 ADDRESSED AND/OR COMPLIED WITH.
  
 PROVISO:
 1) SHEETS "C-1" AND "OC-1" SHOW DIFFERENT OCCUPANT
 LOADS. SHEET "C-1" STATES 341 OCCUPANTS AND SHEET
 "OC-1" SHOWS A TOTAL OF 150 OCCUPANTS. PLEASE PROVIDE
 THE CORRECT OCCUPANT LOAD.
  
 2) PER NFPA 101, CHAPTER 13: EXISTING ASSEMBLY
 OCCUPANCIES - ASSEMBLY OCCUPANCIES WITH OCCUPANT LOADS
 OF 300 OR MORE SHALL BE PROVIDED WITH AN APPROVED FIRE
 ALARM SYSTEM AND PROTECTED BY AN APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 3) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 5) PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS
 WITH EXIT SIGNS.
  
 6) DJ BOOTH, PLATFORM, & STAGE: HANDRAILS ARE REQUIRED
 ON BOTH SIDES OF THE STAIR. HANDRAILS SHALL BE LOCATED
 NOT LESS THAN 34 INCHES AND NOT MORE THAN 38 INCHES
 ABOVE THE SURFACE OF THE TREAD, MEASURED VERTICALLY TO
 THE TOP OF THE RAIL FROM THE LEADING EDGE OF THE TREAD.
 HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR
 SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION
 SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25 INCHES AND
 NOT MORE THAN 2 INCHES.
  
 7) FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. A THUMB TURN STYLE
 LOCK IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED
 LOCK.
  
  
 SUE ELLEN CALDERON, MPA
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2015-08-11 Time 14:25 Sent To  
Notes
2015-08-11 14:28:05B35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 14:03 Rev Time 0.00
Received By jwitmer Date 2015-06-30 Time   Sent To  
Notes
2015-06-30 13:43:17B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-05 Cont ID  
Sent By jgomez Date 2015-06-03 Time 10:45 Rev Time 0.00
Received By jgomez Date 2015-05-06 Time 13:34 Sent To  
Notes
2015-06-05 10:45:27LAST REVIEW DONE ON 6/3/15.
2015-05-07 13:33:31B08

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-09-08 Cont ID  
Sent By ccole Date 2015-09-08 Time 17:16 Rev Time 0.00
Received By ccole Date 2015-09-08 Time 17:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-08-18 Cont ID  
Sent By ccole Date 2015-08-18 Time 13:32 Rev Time 0.00
Received By ccole Date 2015-08-18 Time 13:32 Sent To  
Notes
2015-08-18 14:12:153RD REVIEW: FBC 2010 MECHANICAL
 PERMIT #15050177
 8/18/15
  
 1) THE REVISED ENERGY CALCULATIONS MUST BE SIGNED AND
 DATED BY THE PERSON WHO PREPARED THEM-
 SECTION103.2.3.1.2 FBC-10- ENERGY CONSERVATION.
 2) SHEET M-1: AS PREVIOUSLY REQUESTED PROVIDE THE
 VENTILATION CALCULATION AND OUTSIDE AIR CFM'S FOR THE
 VIP AREA. CORRECT THE TOTAL CFM'S OF O/A FOR THE OFFICE
 TO 33 CFM'S.
 3) AS PREVIOUSLY REQUESTED PROVIDE THE NOA OR FLORIDA
 PRODUCT APPROVAL FOR THE O/A LOUVER.
 4) PROVIDE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTREUCTIONS FOR THE AREA SMOKE
 DETECTORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-07-10 Cont ID  
Sent By ccole Date 2015-07-10 Time 11:07 Rev Time 0.00
Received By ccole Date 2015-07-10 Time 11:07 Sent To  
Notes
2015-07-10 11:10:022ND REVIEW: FBC 2010 MECHANICAL
 PERMIT #1505177 7/10/15
  
 1) THE ENERGY EFFICIENCY FORM IS LISTING TWO 13 SEER
 SYSTEMS, AND ONE 10 SEER SYSTEM WHICH IS NOTED ON THE
 FORM AS A FAILED COMPLIANCE, HOWEVER THE PLAN IS
 INDICATING THREE 16 SEER SYSTEMS: PLEASE CORRECT.
 2) SHEET M-1: THE 24X24 INCH RETURN GRILL IS UNDERSIZED
 FOR 1600 CFM PER SECTION 601.4 (50 SQ. INCHES PER 100
 CFM REQUIRED- MINIMUM GRILL SIZE IS APPROXIMATELY 28 X
 28 SQ. INCHES). PLEASE NOTE THAT THE PLANS DO NOT SHOW
 WHAT THE GRILL IS TO BE MOUNTED TO- A DOOR AT THE FRONT
 OF THE CLOSET IS NOT SHOWN ON THE PLANS.
 3) M-1: INDICATE HOW ACCESS FOR SERVICE IS BEING
 PROVIDED TO AHU-1 & 3 EACH LOCATED ABOVE THE DROP
 CEILINGS, AND SHOW THE LEVEL 30 X 30 INCH LEVEL WORKING
 SPACE IN FRONT OF THE CONTROL SIDES OF THE UNITS-
 REFERENCE SECTION 306.1.
 4) M-1: THE ASHRAE 62- 89 VENTILATION CALCULATIONS
 SHOWN ON THE PLAN ARE OUTDATED. REVISE THE CALCULATIONS
 AS PREVIOUSLY REQUESTED USING TABLE 403.3. A)
 BAR/LOUNGE- 7.5 CFM PER PERSON PLUS .18 CFM PER SF. B)
 STORAGE- .12 CFM PER SF. C) OFFICE- 5 CFM PER
 PERSON/.06 CFM PER SF. D) STAGES- 10 CFM PER PERSON/.06
 CFM PER SF. E)THE LOCKER/SHOWER ROOM REQUIRES EXHAUST
 RATES OF 50 CFM INTERMITTENT OR 20 CFM CONTINUOUS FOR
 THE SHOWER, AND .25 CFM PER SF FOR THE ROOM ITSELF. F)
 AN ACCURATE CALCULATION FOR THE VIP ROOM WILL DEPEND ON
 THE TYPE OF ACTIVITY CONDUCTED IN THE SPACE.
 5) M-1: THERE ARE SD SYMBOLS SHOWN AT THE RETURNS OF
 THE THREE AIR HANDLERS. PLEASE CLARIFY IF THESE ARE
 MEANT TO BE DUCT SMOKE DETECTOR SYMBOLS (DS), AND
 CLARIFY HOW THEY WILL BE SUPERVISED PER SECTION
 606.4.1. PLEASE NOTE THAT DETECTORS SHALL BE INSTALLED
 IN SUPPLY SYSTEMS WITH A DESIGN CAPACITY GREATER THAN
 2000 CFM- 606.2.1
 6) M-1: AS PREVIOUSLY REQUESTED PROVIDE DUCT HANGING
 AND CONNECTION DETAILS, INCLUDING THE DISTRIBUTION
 BOXES- CHAPTER 5- SMACNA 2005.
 7) M-1: SOME DUCT SIZES ARE STILL NOT SHOWN IN THE REAR
 CORRIDOR AND VIP ROOM: PLEASE LIST THESE SIZES AND THE
 DB SIZES.
 8) M-1: A DUCT CONNECTION BETWEEN THE R/A GRILL IN THE
 CORRIDOR AND A SUPPLY DIFFUSER IN THE OFFICE IS SHOWN
 ON THE PLAN: PLEASE CORRECT.
 9) M-1: PLEASE ENLARGE THE DRYWELL DETAIL FOR CLARITY.
 10) AS PREVIOUSLY REQUESTED, PROVIDE TWO COPIES OF FL.
 PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR THE O/A
 INTAKE LOUVERS, AND FOR THE AST AC STAND REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD- DCA RULE
 9N-03.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-03 Cont ID  
Sent By ccole Date 2015-06-03 Time 16:58 Rev Time 0.00
Received By ccole Date 2015-06-03 Time 16:58 Sent To  
Notes
2015-06-03 17:49:311ST REVIEW: FBC 2010 MECHANICAL
  
 1) PROVIDE AC LOAD CALCULATIONS IN ACCORDANCE WITH
 ASHRAE/ACCA STANDARD 183, OR ACCA MANUAL N FOR THE NEW
 SYSTEMS- SECTION 503.2.1 FBC-10 ENERGY CONSERVATION.
 2) PROVIDE VENTILATION CALCULATIONS FOR THE A2
 OCCUPANCY INCLUDING A TABLE DEPICTING THE REQUIRED AND
 PROVIDED O/A OR EXHAUST FOR EACH ROOM OR SPACE ON THE
 PLAN- TABLE 403.3 FBC-10 MECHANICAL.
 3) SHEET M-1: PLEASE INDICATE ALL THE DUCT SIZES ON THE
 PLAN: MANY ARE NOT INDICATED.
 4) PLEASE LABEL THE AIR HANDLERS AS EITHER 1, 2, OR 3.
 5) M-1: SHOW THE OUTSIDE AIR INTAKE DUCTS FOR THE AHU'S
 SHOWN BY THE CONCESSION STAND, AND OVER THE MEN'S
 TOILET ROOM. INDICATE THE TYPE AND SIZE OF THE DUCTS,
 AIR INLET LOCATION, AND TYPE AND SIZE OF INLET GRILL OR
 LOUVER. PLEASE NOTE, TWO COPIES OF A FL. PRODUCT
 APPROVAL OR MIAMI-DADE NOA WILL BE REQUIRED.
 6) M-1: PROVIDE MOTORIZED DAMPERS FOR THE OUTSIDE AIR
 INTAKES THAT WILL AUTOMATICALLY SHUT OFF WHEN THE
 SYSTEMS OR SPACES ARE NOT IN USE- SECTION 503.2.4.4
 FBC-10 ENERGY CONSERVATION.
 7) M-1: PROVIDE EXHAUST VENTILATION PLANS AND
 SPECIFICATIONS FOR THE TOILET ROOMS, INCLUDING EXHAUST
 FAN EQUIPMENT SCHEDULES, THE TYPE AND SIZE OF EXHAUST
 DUCTS, DUCT RUNS, AND TERMINATION LOCATIONS.
 8) M-1: INDICATE SUPPLY CFM'S AT THE 24 X 24 DIFFUSERS
 SHOWN ON THE PLAN AND THE LEGEND.
 9) M-1: PER DETAIL NO. 2 ON M-2, SHOW THE LOCATIONS OF
 ALL REQUIRED DUCT SMOKE DETECTORS, AND TEST STATIONS ON
 THE PLAN- SEE FIRE DEPARTMENT COMMENTS REGARDING THE
 REQUIRED FIRE ALARM SYSTEM.
 10) M-1: PROVIDE AN AIR DISTRIBUTION SCHEDULE ON THE
 PLAN INDICATING THE MAKES AND MODELS OF DIFFUSERS AND
 GRILLS. SHOW DUCT HANGING AND CONNECTION DETAILS.
 11) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE NEW AIR
 HANDLERS: SHOW THE TYPE AND SIZE OF PIPING, PIPING
 RUNS, AND DISCHARGE LOCATIONS- SECTION 307 FBC-10
 MECHANICAL.
 12) SITE SPECIFIC, WINDLOAD TIE-DOWN ENGINEERING IS
 REQUIRED FOR THE NEW CONDENSER STANDS ON THE ROOF-
 SECTION 301.12 FBC-10 MECHANICAL. PROVIDE DESIGN
 CRITERIA AND DESIGN PRESSURES ON THE PLANS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-08-20 Cont ID  
Sent By gjohnson Date 2015-08-20 Time 15:44 Rev Time 0.00
Received By gjohnson Date 2015-08-20 Time 15:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-07-21 Cont ID  
Sent By tklarge Date 2015-07-21 Time 06:05 Rev Time 0.00
Received By tklarge Date 2015-07-21 Time 04:52 Sent To  
Notes
2015-07-21 06:00:131) SUBMIT A NARRATIVE THAT CLEARLY REFLECTS THE SCOPE
 OF UNPERMITTED WORK THAT WAS DONE AND THE SCOPE OF WORK
 TO CORRECT THE VIOLATION.WPB AMEND. TO FBC SEC. 107.1,
 107.2.1. 2ND REQUEST.
 2) CLEARLY SHOW ON THE PLANS THE ENTIRE SCOPE OF
 PLUMBING WORK TO BE DONE.WPB AMEND. TO FBC SEC.107.2.1.
 3) PAGE 1 - CLEARLY SHOW THE WIDTH OF THE TOILET ROOMS.
 THE LAVATORY SHALL NOT ENCROACH INTO THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET.FAC 604.3.1.
 4) SHOW THE FIXTURE CLEARANCE OF THE HANDICAP WATER
 CLOSET FROM THE NEAREST ADJACENT FINISHED WALL TO THE
 CENTERLINE OF THE WATER CLOSET.COMPLY WITH FGURE 604.2
 IN THE FAC.
 5) SHOW THE LOCATION OF THE CONTROL WALL FOR THE
 HANDICAP SHOWERS ON SHT.#1.
 6) THE SHOWER IN THE LOCKER ROOM DOES NOT APPEAR TO
 SUPPLY THE 36"
 X 48" CLEAR FLOOR SPACE ADJACENT TO THE SHOWER. FAC
 SEC.608.2.1.
 7) THE RESTROOMS ARE NOT SHOWN ON THE SANITARY OR WATER
 RISERS. WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 8) LABEL THE FIXTURES ON THE WATER RISER. WPB AMEND. TO
 FBC SEC. 107.2.1.
 9) THE SANITARY RISER AND THE WATER RISER DOES NOT
 CORRELATE WITH THE FLOOR PLAN. WPB AMEND. TO FBC SEC.
 107.5.1.3.
 10) THE ENTIRE HOT AND COLD WATER LINES ARE PIPED IN
 1/2 " PIPE. SUBMIT CALCULATIONS THAT THIS SIZING WILL
 SUPPLY THE MINIMUM FLOW RATES AND PRESSURES REQUIRED AT
 EACH FIXTURE PER TABLE 604.3 OF 2010 FPC.
 11) THE PLANS NOTE AN OCCUPANCY OF A-2 AND A OCCUPANT
 LOAD OF 267 PERSONS. TABLE 403.1 OF THE 2010 FL. PLBG.
 CODE WOULD REQUIRE 4 WATER CLOSETS FOR THE MALES AND 4
 WATER CLOSETS FOR THE FEMALES.
 12) INDICATE THE PREVIOUS OCCUPANCY OF THIS SPACE PER
 CHAPTER 302 OF THE 2010 FBC.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-06-03 Cont ID  
Sent By tklarge Date 2015-06-03 Time 14:28 Rev Time 0.00
Received By tklarge Date 2015-06-03 Time 14:12 Sent To  
Notes
2015-06-03 14:28:301) THE PLANS ARE UNCLEAR AS TO THE LEVEL AND SCOPE OF
 INTERIOR ALTERATIONS BEING DONE. SUBMIT A NARRATIVE
 THAT CLEARLY REFLECTS THE SCOPE OF UNPERMITTED WORK
 THAT WAS DONE AND THE SCOPE OF WORK TO CORRECT THE
 ISSUE. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) CLEARLY SHOW ON THE PLANS THE SCOPE OF WORK TO BE
 DONE. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 3) THE DESIGN PROFESSIONAL SHALL INDICATE ON THE PLANS
 THE LEVEL OF ALTERATION OF THE WORK PER THE FL.
 EXISTING BUILDING CODE SEC.401.4.
 4) CLEARLY INDICATE THE WORK AREA ON THE PLANS PER THE
 FL. EXISTING BUILDING CODE SEC. 401.2.
 5) PAGE 1 - CLEARLY INDICATE THE WIDTH OF THE TOILET
 ROOMS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) SHT. OC-1 - HOW CAN THE BAR AREA BE DESIGNATED AS A
 BUSINESS OCCUPANCY? THIS AREA IS AN A-2 AND SHALL BE
 INCLUDED IN THE A-2 OCCUPANT LOAD COUNT. 201 FBC 303.
 7) A BUILDING, FACILITY OR ELEMENT THAT IS ALTERED
 SHALL COMPLY WITH THE PROVISIONS OF THE FBC-
 ACCESSIBILITY. REFER TO FL. ACCESSIBILITY CODE SEC. 202
 FOR ALTERATIONS TO AN EXISTING BUILDING.
 8) SUBMIT PLUMBING PLANS FOR ANY CHANGES TO THE
 SANITARY OR WATER SYSTEM.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 9) SHT. LS-1 - PLEASE PROVIDE DIMENSIONS FOR ALL
 RESTROOMS AND SHOWER STALLS TO REVIEW FOR REQUIRED
 COMPLIANCE WITH THE FAC. PROVIDE ENLARGED FLOOR PLANS &
 ELEVATIONS OF BATHROOMS & SHOWERS. SHOW FLOOR
 CLEARANCES FOR PLUMBING FIXTURES, PLUMBING FIXTURE
 CLEARANCES, GRAB BARS HEIGHTS, ETC.
  
 NOTE: DUE TO LACK OF INFORMATION ON THE PLANS AS TO THE
 EXTENT OF THE ALTERATIONS, THIS IS NOT A COMPREHENSIVE
 REVIEW. MORE COMMENTS MAY BE GENERATED ONCE A COMPLETE
 SET OF PLANS IS SUBMITTED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  