2015-05-14 11:43:47 | 901 45TH STREET - QUANTUM HOUSE |
| PERMIT #15050144 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| THE QUANTUM HOUSE IS FUNCTIONING AS A DORMITORY |
| OCCUPANCY (NON HOTEL/MOTEL OCCUPANCY); THEREFORE, |
| SPRINKLER PROTECTION IS REQUIRED IN THE SMALL CLOSEST |
| AND RECOMMENDED IN THE BATHROOMS. PER NFPA 13 SECTION |
| 8.15.8.2 "CLOSETS AND PANTRIES. SPRINKLERS ARE NOT |
| REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND |
| PANTRIES WITHIN DWELLING UNITS IN HOTELS AND MOTELS |
| WHERE THE AREA OF THE SPACE DOES NOT EXCEED 24 SQ.FT, |
| THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND THE |
| WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE OR |
| LIMITED-COMBUSTIBLE MATERIALS." THE ADDITIONAL |
| SPRINKLERS MAY AFFECT THE ORIGINAL HYDRAULIC |
| CALCULATIONS. |
| |
| NOTE: THE 2013 EDITION OF THE STANDARD REQUIRES |
| SPRINKLERS IN DORMITORY BATHROOMS. SECTION 8.15.8.1.1 |
| SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS THAT ARE |
| LOCATED WITHIN DWELLING UNITS OF HOTELS AND MOTELS, |
| THAT DO NOT EXCEED 55 SQ.FT. IN AREA, AND THAT HAVE |
| WALLS AND CEILINGS OF NONCOMBUSTIBLE OR |
| LIMITED-COMBUSTIBLE MATERIALS WITH A 15-MINUTE THERMAL |
| BARRIER RATING, INCLUDING THE WALLS AND CEILINGS BEHIND |
| ANY SHOWER ENCLOSURE OR TUB. |
| |
| SPRINKLER PROTECTION MISSING IN OFFICE #142 CLOSET. |
| |
| JANITOR #122A AND STORAGE #118A INDICATE SPRINKLERS |
| LOCATED MORE THAN 7'-6" FROM WALLS. THESE ROOMS ARE |
| CONSIDERED ORDINARY HAZARD THAT DO NOT QUALIFY FOR THE |
| "SMALL ROOM" RULES. |
| |
| REMOTE AREA #1 INDICATES USE OF THE AREA/DENSITY |
| METHOD; HOWEVER, THE ACTUAL CALCULATION USED APPEARS TO |
| BE THE ROOM DESIGN METHOD. HOW CAN NODE #303 BE AT A |
| HIGHER FLOW AND PRESSURE WHEN IT IS DOWNSTREAM OF NODE |
| #302? NODE #303 IS INDICATED AS BEING CONNECTED TO NODE |
| #15 AND BYPASSING NODE #9? |
| |
| REMOTE AREA #3 INDICATES USE OF THE AREA/DENSITY |
| METHOD; HOWEVER, THE ACTUAL CALCULATION USED APPEARS TO |
| BE THE ROOM DESIGN METHOD FOR CORRIDORS. ALSO THE |
| CALCULATION SHOWS SPRINKLERS WITH A K-FACTOR OF 8.0 |
| WHICH THE PLANS INDICATE AS ATTIC SPRINKLERS. HOW IS |
| THE ROOM DESIGN METHOD BEING USED FOR THE ATTIC SPACE? |
| |
| THE SPRINKLERS PROTECTING THE ATTIC SPACES APPEAR TO BE |
| LOCATED BELOW A CEILING/ROOF WITH A SLOPE EXCEEDING 2 |
| IN 12. SUBMIT A HYDRAULIC CALCULATION UTILIZING AN AREA |
| INCREASE OF 30% PER SECTION. |
| |
| REMOTE AREAS: CLEARLY INDICATE WHAT HYDRAULIC METHOD IS |
| BEING UTILIZED FOR EACH REMOTE AREA (AREA DENSITY, |
| QUICK RESPONSE REDUCTION, ROOM DESIGN METHOD, ETC.) AND |
| INDICATE THE LOCATION (ABOVE CEILING/BELOW CEILING). |
| |
| JIM WALKER/WESLEY JOLIN |