Plan Review Details - Permit 15050144
Plan Review Stops For Permit 15050144
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-24 Cont ID  
Sent By wjolin Date 2015-06-24 Time 15:00 Rev Time 0.00
Received By wjolin Date 2015-06-24 Time 12:55 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-14 Cont ID  
Sent By shill Date 2015-06-08 Time 09:51 Rev Time 0.00
Received By wjolin Date 2015-05-14 Time 09:00 Sent To M
Notes
2015-05-14 11:43:47901 45TH STREET - QUANTUM HOUSE
 PERMIT #15050144
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE QUANTUM HOUSE IS FUNCTIONING AS A DORMITORY
 OCCUPANCY (NON HOTEL/MOTEL OCCUPANCY); THEREFORE,
 SPRINKLER PROTECTION IS REQUIRED IN THE SMALL CLOSEST
 AND RECOMMENDED IN THE BATHROOMS. PER NFPA 13 SECTION
 8.15.8.2 "CLOSETS AND PANTRIES. SPRINKLERS ARE NOT
 REQUIRED IN CLOTHES CLOSETS, LINEN CLOSETS, AND
 PANTRIES WITHIN DWELLING UNITS IN HOTELS AND MOTELS
 WHERE THE AREA OF THE SPACE DOES NOT EXCEED 24 SQ.FT,
 THE LEAST DIMENSION DOES NOT EXCEED 3 FEET, AND THE
 WALLS AND CEILINGS ARE SURFACED WITH NONCOMBUSTIBLE OR
 LIMITED-COMBUSTIBLE MATERIALS." THE ADDITIONAL
 SPRINKLERS MAY AFFECT THE ORIGINAL HYDRAULIC
 CALCULATIONS.
  
 NOTE: THE 2013 EDITION OF THE STANDARD REQUIRES
 SPRINKLERS IN DORMITORY BATHROOMS. SECTION 8.15.8.1.1
 SPRINKLERS SHALL NOT BE REQUIRED IN BATHROOMS THAT ARE
 LOCATED WITHIN DWELLING UNITS OF HOTELS AND MOTELS,
 THAT DO NOT EXCEED 55 SQ.FT. IN AREA, AND THAT HAVE
 WALLS AND CEILINGS OF NONCOMBUSTIBLE OR
 LIMITED-COMBUSTIBLE MATERIALS WITH A 15-MINUTE THERMAL
 BARRIER RATING, INCLUDING THE WALLS AND CEILINGS BEHIND
 ANY SHOWER ENCLOSURE OR TUB.
  
 SPRINKLER PROTECTION MISSING IN OFFICE #142 CLOSET.
  
 JANITOR #122A AND STORAGE #118A INDICATE SPRINKLERS
 LOCATED MORE THAN 7'-6" FROM WALLS. THESE ROOMS ARE
 CONSIDERED ORDINARY HAZARD THAT DO NOT QUALIFY FOR THE
 "SMALL ROOM" RULES.
  
 REMOTE AREA #1 INDICATES USE OF THE AREA/DENSITY
 METHOD; HOWEVER, THE ACTUAL CALCULATION USED APPEARS TO
 BE THE ROOM DESIGN METHOD. HOW CAN NODE #303 BE AT A
 HIGHER FLOW AND PRESSURE WHEN IT IS DOWNSTREAM OF NODE
 #302? NODE #303 IS INDICATED AS BEING CONNECTED TO NODE
 #15 AND BYPASSING NODE #9?
  
 REMOTE AREA #3 INDICATES USE OF THE AREA/DENSITY
 METHOD; HOWEVER, THE ACTUAL CALCULATION USED APPEARS TO
 BE THE ROOM DESIGN METHOD FOR CORRIDORS. ALSO THE
 CALCULATION SHOWS SPRINKLERS WITH A K-FACTOR OF 8.0
 WHICH THE PLANS INDICATE AS ATTIC SPRINKLERS. HOW IS
 THE ROOM DESIGN METHOD BEING USED FOR THE ATTIC SPACE?
  
 THE SPRINKLERS PROTECTING THE ATTIC SPACES APPEAR TO BE
 LOCATED BELOW A CEILING/ROOF WITH A SLOPE EXCEEDING 2
 IN 12. SUBMIT A HYDRAULIC CALCULATION UTILIZING AN AREA
 INCREASE OF 30% PER SECTION.
  
 REMOTE AREAS: CLEARLY INDICATE WHAT HYDRAULIC METHOD IS
 BEING UTILIZED FOR EACH REMOTE AREA (AREA DENSITY,
 QUICK RESPONSE REDUCTION, ROOM DESIGN METHOD, ETC.) AND
 INDICATE THE LOCATION (ABOVE CEILING/BELOW CEILING).
  
 JIM WALKER/WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-25 Cont ID  
Sent By ccole Date 2015-06-25 Time 16:36 Rev Time 0.00
Received By ccole Date 2015-06-08 Time 09:56 Sent To  
Notes
2015-06-08 09:56:21TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-08 Cont ID  
Sent By shill Date 2015-05-21 Time 09:51 Rev Time 0.00
Received By shill Date 2015-05-06 Time 12:51 Sent To FIRE
Notes
2015-05-06 12:53:29ROUTE TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By ccole Date 2015-06-25 Time 16:35 Rev Time 0.00
Received By ccole Date 2015-06-25 Time 16:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-21 Cont ID  
Sent By ccole Date 2015-05-21 Time 16:49 Rev Time 0.00
Received By ccole Date 2015-05-06 Time 16:49 Sent To  
Notes
2015-05-21 17:07:521ST MECHANICAL REVIEW
  
 1) PROVIDE A PIPE HANGER DETAIL FOR THE THE 3" PIPING,
 AND HANGER SPACING TABLES ON THE PLANS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  