Plan Review Details - Permit 15050111
Plan Review Stops For Permit 15050111 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2015-05-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-07 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-05-07 |
Time |
12:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2015-05-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-07 |
Time |
06:22 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-05-07 |
Time |
05:50 |
Sent To |
|
|
Notes |
2015-05-07 06:15:00 | 1) PROVIDE SPEC SHEETS FOR THE EXTERIOR REGULATORS. | | REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING | | SHALL BE APPROVED FOR OUTDOOR INSTALLATION PER 2010 | | FBC-R SEC.G2421.1. | | 2) SHOW THE LENGTHS OF ALL SECTIONS OF PIPE FROM THE | | LINE EXITING THE METER TO THE POOL HEATER. THE PLANS | | SHOW THE DIMENSIONS OF ONLY 2 SECTIONS OF PIPE THAT | | TOTAL 25 FEET BUT THE PLAN STATES THE DEVELOPED LENGTH | | IS 20 FEET. IT DOES NOT ADD UP.WPB AMEND. TO 2010 FBC | | SEC. 107.2.1. | | 3) INDICATE ON THE PLAN HOW THE GALVANIZED PIPE TO THE | | POOL HEATER IS GOING TO BE INSTALLED. GALVANIZED PIPE | | CANNOT BE INSTALLED UNDERGROUND PER 2010 FBC-R | | SEC.G2415.9, G2415.9.2. IF THE PIPING IS TO BE ATTACHED | | TO THE EXTERIOR OF THE WALL, INDICATE SO ON PLANS. WPB | | AMEND. TO 2010 FBC SEC.107.2.1.. | | 4) SHOW THE HOT AND COLD WATER LINES ON THE PLAN.WPB | | AMEND. TO 2010 FBC SEC.107.2.1. | | 5) THE PLAN NOTES THE GAS METER AS 1/2 POUND SYSTEM AND | | ALSO A 2 LB. SYSTEM. WHICH IS IT? IF IT IS A HALF POUND | | SYSTEM, THE SYSTEM IS UNDERSIZED FOR THE BTU LOAD. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-05-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-07 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-05-07 |
Time |
12:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-05-07 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-07 |
Time |
06:22 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-05-05 |
Time |
09:36 |
Sent To |
|
|
Notes |
2015-05-06 09:37:01 | SENT TO PLUMBING UNDER $5000 SHELF FOR REVIEW. JG. |
|
|
|