Plan Review Stops For Permit 15050093 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-05-18 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-05-18 |
Time |
17:24 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-05-18 |
Time |
16:42 |
Sent To |
I |
|
Notes |
2015-05-18 17:25:00 | APPROVED W/PROVISOS AS MENTIONED BELOW: | | | | 1. IF ITEM #7 ON RISER DIAGRAM RUNS UNDERGROUND | | CONDUCTOR INSULATION SHALL BE THWN TYPE | | 2. OUTLETS MARKED ON PLANS SHALL BE INSTALLED | | 3. CARBON MONOXIDE DETECTORS REQUIRED | | 4. ARC-FAULT CIRCUIT PROTECTION REQUIRED | | 5. TAMPER-RESISTANT DEVICES REQUIRED | | 6. CEILING BOXES TO BE LISTED FOR 50#?S | | | | ALL WORK IS SUBJECT TO FIELD INSPECTOR?S APPROVAL | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-05-18 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-05-18 |
Time |
17:25 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-05-05 |
Time |
12:50 |
Sent To |
|
|
Notes |
2015-05-18 17:26:37 | CONTRACTOR NOTIFIED VIA EMAIL. | 2015-05-05 12:50:56 | SENT TO ELECTRICAL SHELF FOR REVIEW. JG. |
|
|
|