Plan Review Details - Permit 15050067
Plan Review Stops For Permit 15050067
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-28 Cont ID  
Sent By jwitmer Date 2015-06-28 Time 06:22 Rev Time 0.00
Received By jwitmer Date 2015-06-28 Time 05:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-10 Cont ID  
Sent By jwitmer Date 2015-06-10 Time 16:25 Rev Time 0.00
Received By jwitmer Date 2015-06-10 Time 06:30 Sent To  
Notes
2015-06-10 16:25:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050067
 ADD: 120 S. OLIVE AVE.
 CONT: URBAN BUILDING CONCEPTS
 TEL: (561)727-8343
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. JUNE 06/ 2015
 ACTION: DENIED
  
 NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A
 CODE VIOLATION.
  
  
  
 1) 2ND REQUEST. SHEET A-1 DOOR # 5 AT CHECK OUT DOES
 NOT HAVE 18 INCHES CLEAR ON THE LATCH SIDE OF THE DOOR
 THE COUNTERTOP IS LOCATED WITHIN THE REQUIRED CLEAR 18
 INCHES!!!! SEE ACCESSIBILITY CODE;
  
 2010 FL. ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 2010 FL. ACCESS. CODE 307.2 PROTRUSION LIMITS. OBJECTS
 WITH LEADING EDGES MORE THAN 27 INCHES (685 MM) AND NOT
 MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES (100 MM) MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2) COMPLIED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-06 Cont ID  
Sent By jwitmer Date 2015-05-06 Time 12:28 Rev Time 0.00
Received By skennedy Date 2015-05-04 Time 13:59 Sent To  
Notes
2015-05-06 12:28:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15050067
 ADD: 120 S. OLIVE AVE.
 CONT: URBAN BUILDING CONCEPTS
 TEL: (561)727-8343
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE JUNE 01, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE.
  
 1ST REVIEW
 DATE: WED. MAY 06/ 2015
 ACTION: DENIED
  
 1) SHEET A-1 DOOR # 5 AT CHECK OUT DOES NOT HAVE 18
 INCHES CLEAR ON THE LATCH SIDE OF THE DOOR. SEE
 ACCESSIBILITY CODE;
  
 2010 FL. ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 MINIMUM MANEUVERING CLEARANCES AT DOORS AND GATES SHALL
 COMPLY WITH 404.2.4. MANEUVERING CLEARANCES SHALL
 EXTEND THE FULL WIDTH OF THE DOORWAY AND THE REQUIRED
 LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 2010 FL. ACCESS. CODE 307.2 PROTRUSION LIMITS. OBJECTS
 WITH LEADING EDGES MORE THAN 27 INCHES (685 MM) AND NOT
 MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH FLOOR OR
 GROUND SHALL PROTRUDE 4 INCHES (100 MM) MAXIMUM
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 2) DOOR # 19 DOES NOT HAVE THE REQUIRED MANUEVERING
 CLEARANCES OF 60 INCHES FROM THE FACE OF THE DOOR,
 ACCESS. FIGURE 404.2.4.1(A).
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-12 Cont ID  
Sent By rlecky Date 2015-05-12 Time 13:19 Rev Time 0.00
Received By rlecky Date 2015-05-12 Time 12:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By pleduc Date 2015-06-25 Time   Rev Time 0.00
Received By pleduc Date 2015-06-25 Time 14:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-05 Cont ID  
Sent By pleduc Date 2015-05-05 Time   Rev Time 0.00
Received By pleduc Date 2015-05-05 Time 15:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-07 Cont ID  
Sent By ccole Date 2015-07-07 Time 07:06 Rev Time 0.00
Received By ccole Date 2015-06-24 Time 19:22 Sent To  
Notes
2015-06-24 19:31:10TO B24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-16 Cont ID  
Sent By   Date 2015-06-16 Time   Rev Time 0.00
Received By shill Date 2015-06-16 Time 15:29 Sent To  
Notes
2015-06-02 15:34:44***EXPEDITED****
 B38
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-16 Cont ID  
Sent By tklarge Date 2015-05-16 Time 09:22 Rev Time  
Received By tklarge Date 2015-05-04 Time   Sent To  
Notes
2015-05-04 17:12:32SENT TO B03/ EXPEDITED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-07 Cont ID  
Sent By ccole Date 2015-07-07 Time 07:06 Rev Time 0.00
Received By ccole Date 2015-07-07 Time 06:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-15 Cont ID  
Sent By ccole Date 2015-06-15 Time 12:36 Rev Time 0.00
Received By ccole Date 2015-06-15 Time 12:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-14 Cont ID  
Sent By skennedy Date 2015-05-14 Time 14:01 Rev Time 0.00
Received By skennedy Date 2015-05-04 Time 14:01 Sent To  
Notes
2015-05-14 14:17:18REVIEWED BY CHRIS COLE
  
 1) SHEET M-2: A DUCT SMOKE DETECTOR IS REQUIRED PER
 SECTION 606.2.1 FMC-10. SHOW THE LOCATION OF THE DEVICE
 AND TEST STATION PER SECTION 606.4.1 FMC-2010.
 2) PROVIDE WIND LOAD ENGINEERED TIE-DOWN DETAILS FOR
 INSTALLATION OF THE CU ON THE EXISTING STAND- SECTION
 301.12 FMC-10. SUBMIT TWO COPIES OF VALID FL. PRODUCT
 APPROVALS OR MIAMI-DADE NOA'S FOR THE INTAKE AND
 EXHAUST LOUVERS.
 3) VERIFY THE AIR INTAKE WILL HAVE A MINIMUM 10'
 HORIZONTAL CLEARANCE TO THE STREET OR PARKING LOT-
 SECTION 401.4.1 FMC-10.
 4) AN AIR INTAKE DAMPER THAT WILL AUTIOMATICALLY SHUT
 IS REQUIRED PER SECTION 503.2.5.4 FBC-10 ENERGY
 CONSERVATION. SHOW THE LOCATION ON SHEET M-2, AND
 CORRECT THE NOTES ON THE AHU DETAIL ON SHEET M-1.
 5) PLEASE NOTE THAT THE CONDENSATE FROM THE AIR HANDLER
 IS NOT PERMITTED TO DRAIN INTO THE CITY SANITARY SYSTEM
 PER SECTION 90-203 WPB CODE OR ORDINANCES.
 INDICATE ON THE PLAN THE ACTUAL DRAINAGE LOCATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-13 Cont ID  
Sent By tklarge Date 2015-06-13 Time 08:38 Rev Time 0.00
Received By tklarge Date 2015-06-13 Time 08:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-16 Cont ID  
Sent By tklarge Date 2015-05-16 Time 09:21 Rev Time 0.00
Received By tklarge Date 2015-05-16 Time 08:29 Sent To  
Notes
2015-05-16 09:21:401) THE SINK IN MOH'S LAB RM.# 115 IS NOT SHOWN ON THE
 SANITARY RISER.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. A-1 - THE GRAB BAR'S HEIGHT SHALL BE MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. 2010
 FBC-ACCESSIBILITY, SEC.609.4.
 3) IDENTIFY THE DRINKING FOUNTAIN ON THE WATER AND
 SANITARY RISERS.
 4) SHOW THE TERMINATION POINT OF THE CONDENSATE DRAIN
 FROM THE A/C UNIT.CONDENSATE SHALL NOT DISCHARGE TO THE
 CITY'S SANITARY SYSTEM PER CITY ORDINANCE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  