Plan Review Stops For Permit 15050012 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2015-05-07 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-07 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-05-07 |
Time |
10:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-05-04 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-04 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-05-04 |
Time |
15:10 |
Sent To |
|
|
Notes |
2015-05-04 15:33:46 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | COMMENTS: | | | | 1) INDICATE THE LOCATION IN COMPLIANCE WITH THE NEC | | 230.70 | | | | 2) INDICATE THE SIZE (AMPACITY RATING) OF THE MAIN | | OCPD, NEC 230.42 MINIMUM SIZE AND RATING. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-05-07 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-07 |
Time |
10:42 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-05-07 |
Time |
10:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-05-04 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-04 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-05-01 |
Time |
13:48 |
Sent To |
|
|
Notes |
2015-05-01 13:49:08 | SENT TO ELECTRIC UNDER $5K |
|
|
|