Plan Review Stops For Permit 15041163
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-06-29 Cont ID  
Sent By aclange Date 2015-06-29 Time 14:17 Rev Time 0.00
Received By aclange Date 2015-06-29 Time 14:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-06-12 Cont ID  
Sent By shill Date 2015-06-12 Time 06:50 Rev Time 0.00
Received By shill Date 2015-06-12 Time 06:49 Sent To  
Notes
2015-06-12 06:52:29****CORRECTIONS****
 ****COURTESTY REVIEW VIA EMAIL****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IIC TEST FOR QUIETWALK UNDERLAYMENT WITH LAMINATE
 FLOORING WAS SENT VIA EMAIL
  
 1. FBC 2010 1207.2, 1207.3:
  
 A. THE IIC TEST PROVIDED IS ACCEPTABLE.
  
 B. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FROM PREVIOUS LIST:
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 NOT PROVIDED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-06 Cont ID  
Sent By shill Date 2015-06-06 Time 19:06 Rev Time 0.00
Received By shill Date 2015-06-06 Time 19:06 Sent To  
Notes
2015-06-06 19:10:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
  
 1. FBC 2010 1207.2, 1207.3:
  
 FLOORING UNDERLAYMENT TESTS PROVIDED WERE FOR
 WHISPERMAT HW, 8" SLAB, 7/16" HARDWOOD T&G FLOORING
  
 FOR THE FLOORING UNDERLAYMENT, COMPLIANCE IS NOT CLEAR.
 PROVIDE INFORMATION REGARDING THE SLAB THICKNESS FOR
 THIS BUILDING.
  
 EITHER PROVIDE TEST REPORTS WHICH ARE CONSISTENT WITH
 THE PROPOSED INSTALLATION (LAMINATE FLOORING, THICKNESS
 NOT PROVIDED) OR PROVIDE OTHER DATA FROM THE
 MANUFACTURER FOR CONSIDERATION.
  
 THIS INFORMATION MAY BE SENT VIA EMAIL FOR PRELIMINARY
 REVIEW.
  
 2. FROM PREVIOUS LIST:
  
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-03 Cont ID  
Sent By shill Date 2015-06-03 Time 09:44 Rev Time 0.00
Received By shill Date 2015-06-03 Time 09:44 Sent To  
Notes
2015-06-03 09:49:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, SCOPE NOT CLEAR. FLOORING UNDERLAYMENT SPEC
 SHEET PROVIDED, BUT PLANS DO NOT INDICATE FLOORING
 INSTALLATION. THE PLAN IS TO BE ARCHITECTURAL QUALITY,
 TO SCALE, AND TO CLEARLY SHOW SCOPE AND NATURE OF
 PROPOSED IMPROVEMENT.
  
 2. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED UTILIZED A SUSPENDED GYPSUM
 CEILING. EITHER PROVIDE EVIDENCE THAT THE UNIT BELOW
 INCLUDES A SUSPENDED GYPSUM CEILING WHICH WILL NEVER BE
 REMOVED, OR PROVIDE A TEST REPORT WHICH DOES NOT
 INCLUDE THE SUSPENDED GYPSUM CEILING.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 THE TEST REPORT PROVIDED UTILIZED A SUSPENDED GYPSUM
 CEILING. EITHER PROVIDE EVIDENCE THAT THE UNIT BELOW
 INCLUDES A SUSPENDED GYPSUM CEILING WHICH WILL NEVER BE
 REMOVED, OR PROVIDE A TEST REPORT WHICH DOES NOT
 INCLUDE THE SUSPENDED GYPSUM CEILING.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-05 Cont ID  
Sent By pleduc Date 2015-06-05 Time   Rev Time 0.00
Received By pleduc Date 2015-06-05 Time 13:28 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By pleduc Date 2015-05-04 Time   Rev Time 0.00
Received By pleduc Date 2015-05-04 Time 14:33 Sent To B
Notes
2015-05-04 14:39:16THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THERE IS INSUFFIECIENT DETAIL TO DETERMINE WHAT IS
 EXISTING AND WHAT IS BEING INSTALLED.
  
 PLEASE INDICATE EXISTING SPRINKLER HEADS AND OR FIRE
 ALARM DEVICES AND/OR IF THEY WILL BE AFFECTED BY THIS
 INSTALLATION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-29 Cont ID  
Sent By aclange Date 2015-06-29 Time 14:17 Rev Time 0.00
Received By aclange Date 2015-06-16 Time 16:54 Sent To  
Notes
2015-06-16 16:54:09TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-06 Cont ID  
Sent By shill Date 2015-06-06 Time 19:10 Rev Time 0.00
Received By shill Date 2015-06-04 Time 09:27 Sent To  
Notes
2015-06-05 09:28:01SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-03 Cont ID  
Sent By shill Date 2015-06-03 Time 09:50 Rev Time 0.00
Received By shill Date 2015-04-30 Time 17:56 Sent To  
Notes
2015-04-30 17:56:40TO FIRE
  