Plan Review Details - Permit 15041142
Plan Review Stops For Permit 15041142
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-24 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 06:12 Rev Time 0.00
Received By jwitmer Date 2015-06-24 Time 05:32 Sent To  
Notes
2015-06-24 06:09:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041142
 ADD: 705 N. OLIVE AVE.
 CONT: TBD
 TEL: ( 561)805-6715
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. JUNE 24/ 2015
 ACTION: BUILDING PROVISO
  
 1) THIS ONE ISSUE WILL BE RULED ON BY THE FIRE
 DEPARTMENT AND SINCE THEY WERE THE ONES THAT APPROVED
 THE LOCATION OF THE CONSTRUCTION TRAILER WITH THE
 STIPULATION THAT THE BUILDING WOULD BE LEFT
 UN-OCCUPIED. SHEET A.0 INDICATES TO THE EAST A CLEAR
 DRIVEWAY OF 20 FT. PLEASE BE AWARE THE CONSTRUCTION
 TRAILERS ARE JUST TO THE EAST OF THE DRIVEWAY. ONE OF
 THE CONDITIONS THAT THE FIRE DEPARTMENT PUT ON THE
 PLACEMENT OF THE CONSTRUCTION TRAILERS WAS COMPLIANCE
 WITH NFPA 251 WITH 60 FEET OF EXPOSED SIDE OF THE
 TRAILER THEY WOULD BE REQUIRED TO BE 50 FEET AWAY FROM
 BUILDINGS. AN AGREEMENT WAS MET THAT KAST COULD LEAVE
 THEIR CONSTRUCTION TRAILER WHERE IT WAS IF THE BUILDING
 TO THE WEST WAS LEFT UNOCCUPIED. NOW IT WOULD APPEAR
 THAT EITHER THE BUILDING REMAIN UNOCCUPIED OR KAST
 CONSTRUCTION TRAILER BE MOVED EAST TO COMPLY WITH NFPA
 251.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2015-06-09 Time   Rev Time 0.00
Received By jwitmer Date 2015-06-09 Time 07:24 Sent To  
Notes
2015-06-09 08:06:03BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041142
 ADD: 705 N. OLIVE AVE.
 CONT: TBD
 TEL: ( 561)805-6715
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 09/ 2015
 ACTION: DENIED
  
 1) DISCREPANCY IN ADDRESSING OF THE PROPERTY. THE
 PERMIT APPLICATION INDICATES THE ADDRESS TO BE 705 N.
 OLIVE AVE. THE PROPERTY APPRAISER HAS THIS PROPERTY'S
 ADDRESS AS 375 EUCALYPTUS ST, THE 3RD PHASE OF THE
 OVER-ALL PROJECT. PLEASE CORRECT THE PERMIT APPLICATION
 AND ENERGY CALCULATIONS TO REFLECT THE JOBSITE ADDRESS
 OF 375 EUCALYPTUS ST. PLEASE PROVIDE THE UNITITY OF
 TITLE. THE ADDRESS OF 705 N OLIVE DOES NOT SHOW UP WITH
 THE PROPERTY APPRAISERS WEB SITE WHICH IS USUAL WHEN
 THERE IS A REPLAT. BUT THE ADDRESS OF 375 EUCALYPTUS IS
 STILL SHOWING UP AS A SEPARATE PROPERTY CONTROL NUMBER
 AND ADDRESS. PERMIT: 14030096 : ADDRESS 705 N OLIVE IS
 A 8 LEVEL BUILDING, LOFTIN PLACE, A DIFFERENT LOCATION,
 PCN NUMBER AND ADDRESS.
  
 2) 2ND REQUEST. I'VE SPOKE WITH THE BUILDING OFFICIAL
 R. BROWN ABOUT THIS ISSUE, AND HE DOES NOT WANT TO HAVE
 A NEW ELEMENT BE A CODE VILATION.
 SHEET A.0 TEMPORARY LEASING OFFICE DOES NOT SHOW WHERE
 THE PROPERTY LINE IS LOCATED, IT CAN NOT BE DETERMINED
 IF THE FRONT ENTRY DOOR CROSSES OVER THE PROPERTY LINE.
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 3202.2
 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT.
 DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT INTO THE
 PUBLIC RIGHT-OF-WAY.
  
 3) BUILDING PROVISO:
 THIS ONE ISSUE WILL BE RULED ON BY THE FIRE DEPARTMENT
 AND SINCE THEY WERE THE ONES THAT APPROVED THE LOCATION
 OF THE CONSTRUCTION TRAILER WITH THE STIPULATION THAT
 THE BUILDING WOULD BE LEFT UN-OCCUPIED. SHEET A.0
 INDICATES TO THE EAST A CLEAR DRIVEWAY OF 20 FT. PLEASE
 BE AWARE THE CONSTRUCTION TRAILERS ARE JUST TO THE EAST
 OF THE DRIVEWAY. ONE OF THE CONDITIONS THAT THE FIRE
 DEPARTMENT PUT ON THE PLACEMENT OF THE CONSTRUCTION
 TRAILERS WAS COMPLIANCE WITH NFPA 251 WITH 60 FEET OF
 EXPOSED SIDE O FTHE TRAILER THEY WOULD BE REQUIRED TO
 BE 50 FEET AWAY FROM BUILDINGS. AN AGREEMENT WAAS MET
 THAT KAST COULD LEAVE THEIR CONSTRUCTION TRAILER WHERE
 IT WAS IF THE BUILDING TO THE WEST WAS LEFT UNOCCUPIED.
 NOW IT WOULD APPEAR THAT EITHER THE BUILDING REMAIN
 UNOCCUPIED OR KAST CONSTRUCTION TRAILER BE MOVED EAST
 TO COMPLY WITH NFPA 251.
  
 4) COMPLIED. SHEETS A1 & A2 BOTH SHOW THE EXISTING
 WINDOWS TO BE BLOCKED IN, THERE IS NO INFORMATION AS TO
 HOW THE NEW INFILL WILL BE TIED TO THE EXISTING
 BLOCKWORK.
 2010 FBC-B 2104.1.3 INSTALLATION OF WALL TIES. WALL
 TIES SHALL BE INSTALLED IN ACCORDANCE WITH TMS 602/ACI
 530.1/ASCE 6.
  
 5) 2ND REQUEST. SHEET A2 INDICATES VASD PRESSURES FOR
 THE NEW OPENING. THE PLANS FAIL TO IDENTFY THE
 WINDDESIGN CRITERIA, THE IMPORTANCE FACTOR OF THE
 BUILDING, EXPOSURE CATEGORY OF THE BUILDING AND OR IF
 HEIGHT ADJUSTMENT FACTORS ARE INVOLVED. THESE LISTED
 CRITERIA DETERMINES THE PRESSURES, WITHOUT THIS
 INFORMATION, WE CAN'T DETERMINE WHAT CRITERIA THE
 DESIGNER OF RECORD ARRIVED THE PRESSURES FOR THE
 OPENING.
  
 BOTH SHEETS A1 & A2 BOTH INDICATE A NEW WIDER FRONT
 ENTRY DOOR PLEASE PROVIDE THE WIND DESIGN CRETERIA;
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 6) COMPONENTS & CLADDING 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOW
 (C) MULLION
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7A) ONCE THEWIND DESIGN CRITERIA & PRESSURES ARE
 REVIEWED AND APPROVED. EITHER THE DESIGNER OF RECORD OR
 THE CONTRACTOR CAN ELECT TO SUBMIT THE PRODUCT
 APPROVALS AFTER THE PERMIT ISSUANCE, WRITTEN
 NOTIFICATION IS REQUIRED.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
  
 8-13) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By jwitmer Date 2015-05-15 Time 14:19 Rev Time 0.00
Received By jwitmer Date 2015-05-15 Time 09:34 Sent To  
Notes
2015-05-15 14:19:45 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041142
 ADD: 705 N. OLIVE AVE.
 CONT: TBD
 TEL: ( 561)805-6715
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. MAY 15/ 2015
 ACTION: DENIED
  
 1) DISCREPANCY IN ADDRESSING OF THE PROPERTY. THE
 PERMIT APPLICATION INDICATES THE ADDRESS TO BE 705 N.
 OLIVE AVE. PERMIT: 14030096 IS A 8 LEVEL BUILDING,
 LOFTIN PLACE. THE PLANS SUBMITTED SHOW THE PROPERTY IN
 QUESTION ON THE CORNER OF EUCALYPTUS ST. AND N. DIXIE
 HWY. THE PROPERTY APPRAISER HAS THIS PROPERTY'S ADDRESS
 AS
 375 EUCALYPTUS ST. THE 3RD PHASE OF THE OVER-ALL
 PROJECT.
  
 2) SHEET A.0 TEMPORARY LEASING OFFICE DOES NOT SHOW
 WHERE THE PROPERTY LINE IS LOCATED, IT CAN NOT BE
 DETERMINED IF THE FRONT ENTRY DOOR CROSSES OVER THE
 PROPERTY LINE. PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN
 HEIGHT. DOORS AND WINDOWS SHALL NOT OPEN OR PROJECT
 INTO THE PUBLIC RIGHT-OF-WAY.
  
 3) SHEET A.0 INDICATES TO THE EAST A CLEAR DRIVEWAY OF
 20 FT. PLEASE BE AWARE THE CONSTRUCTION TRAILERS ARE
 JUST TO THE EAST OF THE DRIVEWAY. ONE OF THE CONDITIONS
 THAT THE FIRE DEPARTMENT PUT ON THE PLACEMENT OF THE
 CONSTRUCTION TRAILERS WAS COMPLIANCE WITH NFPA 251 WITH
 60 FEET OF EXPOSED SIDE O FTHE TRAILER THEY WOULD BE
 REQUIRED TO BE 50 FEET AWAY FROM BUILDINGS. AN
 AGREEMENT WAAS MET THAT KAST COULD LEAVE THEIR
 CONSTRUCTION TRAILER WHERE IT WAS IF THE BUILDING TO
 THE WEST WAS LEFT UNOCCUPIED. NOW IT WOULD APPEAR THAT
 EITHER THE BUILDING REMAIN UNOCCUPIED OR KAST
 CONSTRUCTION TRAILER BE MOVED EAST TO COMPLY WITH NFPA
 251.
  
 4) SHEETS A1 & A2 BOTH SHOW THE EXISTING WINDOWS TO BE
 BLOCKED IN, THERE IS NO INFORMATION AS TO HOW THE NEW
 INFILL WILL BE TIED TO THE EXISTING BLOCKWORK.
 2010 FBC-B 2104.1.3 INSTALLATION OF WALL TIES. WALL
 TIES SHALL BE INSTALLED IN ACCORDANCE WITH TMS 602/ACI
 530.1/ASCE 6.
  
 5) BOTH SHEETS A1 & A2 BOTH INDICATE A NEW WIDER FRONT
 ENTRY DOOR PLEASE PROVIDE THE WIND DESIGN CRETERIA;
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 6) COMPONENTS & CLADDING 2010 FBC-B 1609.1.2 PROTECTION
 OF OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOW
 (C) MULLION
 7) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 8) NOTES FROM THE COVERSHEET INDICATE THE EXISITNG DOOR
 OPENING FOUND ON SHEET A1 WILL BE WIDENED FOR A NEW
 STOREFRONT DOOR AND SIDELITE. THE PLANS SHEET A3 DOOR
 SCHEDULE INDICATE THE DOOR TO BE A 3'-0"X 7'-0" WITH A
 2'-0" SIDELITE. THE PLANS DO NOT PROVIDE THE REQUIRED
 WIDTH FOR THE ROUGH OPENING, NOR DO WE KNOW IF THE DOOR
 AND SIDELIGHT ARE TO BE MANUFACTERED A SINGLE UNIT OR
 IF THEY ARE GOING TO BE (2) INDEPENT UNITS REQUIRING A
 MULLOIN. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) SHEET A1 THE FRONT ENTRY DOES HAVE A NOTE THAT THE
 NEW STOREFRONT ENTRY TO HAVE FILED CELL WITH #5 REBAR
 IN CELLS. THE PLANS ARE DEFICIENT IN HOW THE REBAR ARE
 TO CONNENT WITH THE FOOTING AND CONCRETE BEAM ABOVE TO
 FORM PART OF THE MWFRS MAIN WIND FORCE RESISTING
 SYSSTEM.
  
 10) SHEET A2 THE WEST ELEVATION SHOWS THE NEW PROPOSED
 ENTRY DOORWAY. SHEET A3 FOR THE FRONT ENTRY DOOR, DOOR
 # 1 AS A 3'-0"X 7'-0" DOOR WHERE AS IN THE ELEVATION IT
 IS DRARN AS A 8'-0" HIGH DOOR, PLEASE INDICATE IS THERE
 TO BE A NEW BEAM TO HOLD THE BLOCK IN PLACE OR WILL A
 LINTEL BE USED IN THIS APPLICATION? AGAIN ADDITIONAL
 INFORMATION IS REQUIRED. 107.2.1.3. 1609.1.4 MWFRS.
  
 11) SHEET A2 INDICATES A VERTICAL A/C CLOSET WITH A
 DOOR LABELED # 2 FOR ACCESS TO THE UNIT. SHEET A3 THE
 DOOR SCHEDULE DOOR # 2 IS A HOLLOW METAL DOOR WHERE AS
 WHEN YOU LOOK AT SHEET M1 THIS DOOR IS A LOUVERED DOOR.
 DISCREPANCY IN PLANS. 107.2.1.3 PLEASE NOTE THIS UNIT
 BEING A PLENUM RETURN, THERE CAN BE NO COMBUSTIBLES IN
 THE PLENUM, IF A LOUVERED DOOR IS TO BE USED IT MUST BE
 METAL. SEE 2010 FBC-M 602.2.1. MATERIALS WITHIN
 PLENUMS.
  
 12) SHEET A2.1 SHOWS THE USE OF DROPPED CEILINGS AND
 SOFFITS BUT THERE IS NO ATTACHMENT NOR FRAMING DESIGN
 PROVIDED, TYPE OF FRAMING, SPACING OF FRAMING,
 ALLOWABLE SPANS FOR THE FRAMING MEMBERS, IF SSTIFF
 BACKS ARE REQUIRED, NOR THE ALLOWABLE DEFLECTION AS
 WELL AS THE THICKNESS OF THE FINISHING MATERIALS. 2010
 FBC-B TABLE 2508.1. STEEL FRAMING FOR GYPSUM BOARD.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By dhayes Date 2015-06-08 Time 15:59 Rev Time 0.00
Received By dhayes Date 2015-06-08 Time 15:59 Sent To  
Notes
2015-06-08 16:09:27APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) 505.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN
 SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF
 TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT
 IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED
 DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A
 COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN
 ASTRONOMICAL TIME SWITCH.
  
 2) A BUILDING OR OTHER STRUCTURE SERVED SHALL BE
 SUPPLIED BY ONLY ONE SERVICE. NEC 230.2
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-16 Cont ID  
Sent By dhayes Date 2015-05-16 Time 13:33 Rev Time 0.00
Received By dhayes Date 2015-05-16 Time 13:17 Sent To  
Notes
2015-05-16 13:33:385/16/2015
 PROJECT: LOFTIN PLACE TEMP. LEASING OFFICE.
 PERMIT#: 15041142
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED.
  
 PLEASE CLARIFY THE FOLLOWING ELECTRICAL REVIEW
 COMMENTS.
  
 1) THE SERVICE DIAGRAM INDICATED ON THE EAST ELEVATION
 ON SHEET A-2 IS DIAGRAMATICALLY DIFFERENT THAN THE
 RISER DIAGRAM INDICATED ON SHEET E-1 AND YET AGAIN ON
 THE FIRST FLOOR PLAN THERE APPEARS TO BE TWO ELECTRICAL
 SERVICES. NEC 230.2 NUMBER OF SERVICES.
  
 2) THE NOTE ON SHEET E.2 THAT CALLS FOR THE DEMOLITION
 OF THE KITCHEN. PLEASE PROVIDE A DEMOLITION DETAIL THAT
 NOTES THE EXTENT OF THE DEMOLITION AND A NEW PLAN THAT
 INDICATES THE PROPOSED FINISHED KITCHEN.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SECURITY, CCTV, AUDIO/VIDEO, NETWORK,
 DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2015-06-26 Cont ID  
Sent By wjolin Date 2015-06-26 Time 14:32 Rev Time 0.00
Received By wjolin Date 2015-06-26 Time 14:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2015-06-24 Cont ID  
Sent By wjolin Date 2015-06-24 Time 15:52 Rev Time 0.00
Received By wjolin Date 2015-06-24 Time 15:48 Sent To  
Notes
2015-06-24 15:48:58I HAD A BRIEF PHONE CONVERSATION WITH KAST CONSTRUCTION
 THURSDAY - JUNE 11. KAST ASKED FOR PERMISSION TO
 PROVIDE A FIRE RATED WALL IN LIEU OF PROVIDING
 BUILDING/"TRAILER" SEPARATION PER NFPA 241. I RESPONDED
 THAT I WAS OPEN TO THE IDEA BUT WOULD NEED TO SEE AN
 ENGINEERED DRAWING, SKETCH OR DETAILED NARRATIVE THAT
 COULD BE DISCUSSED AND REVIEWED WITH THE BUILDING DEPT.
 NO APPROVALS WERE GIVEN, BUT WE DID DISCUSS BLOCKING IN
 THE WINDOWS AND CONSTRUCTING A FIRE RATED WALL THAT
 WOULD BE 3-FEET ABOVE THE ROOF LEVEL OF THE TRAILERS TO
 ACT AS RADIANT HEAT DEFLECTING PARAPET. THE SUBMITTAL
 REVIEWED TODAY (06/24/15) ONLY INDICATES THAT THE
 WINDOWS ARE TO BE BLOCKED IN.
  
  
 705 NORTH OLIVE AVENUE/375 EUCALYPTUS STREET
 PERMIT #15041142
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 AS AGREED IN 2014, TEMPORARY OFFICE TRAILERS WERE
 APPROVED IN THE CURRENT LOCATION BECAUSE THE ADJACENT
 BUILDING WAS TO REMAIN UNOCCUPIED OR RAZED.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-06-11 Cont ID  
Sent By wjolin Date 2015-06-11 Time 10:12 Rev Time 0.00
Received By wjolin Date 2015-06-11 Time 10:05 Sent To  
Notes
2015-06-11 10:07:02705 NORTH OLIVE AVENUE/375 EUCALYPTUS STREET
 PERMIT #15041142
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 AS AGREED IN 2014, TEMPORARY OFFICE TRAILERS WERE
 APPROVED IN THE CURRENT LOCATION BECAUSE THE ADJACENT
 BUILDING WAS TO REMAIN UNOCCUPIED OR RAZED.
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  
  
  
  
  
2015-06-04 15:03:42NEW DRAWINGS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-11 Cont ID  
Sent By scaldero Date 2015-05-11 Time 15:20 Rev Time 0.00
Received By scaldero Date 2015-05-11 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-06-26 Cont ID  
Sent By wjolin Date 2015-06-26 Time 14:32 Rev Time 0.00
Received By wjolin Date 2015-06-25 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-24 Cont ID  
Sent By wjolin Date 2015-06-24 Time 15:52 Rev Time 0.00
Received By wjolin Date 2015-06-22 Time 11:40 Sent To  
Notes
2015-06-23 11:41:18RE-SUBMITTAL SENT TO B1 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-18 Cont ID  
Sent By   Date 2015-06-18 Time   Rev Time 0.00
Received By jgomez Date 2015-06-04 Time 15:31 Sent To  
Notes
2015-06-04 15:31:41RE-SUBMITTAL SENT TO B5 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-23 Cont ID  
Sent By tklarge Date 2015-05-23 Time 11:26 Rev Time  
Received By tklarge Date 2015-05-01 Time   Sent To  
Notes
2015-05-07 15:10:24C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-05-15 Cont ID  
Sent By jwitmer Date 2015-05-15 Time 14:20 Rev Time 0.00
Received By jwitmer Date 2015-05-15 Time 14:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-18 Cont ID  
Sent By ccole Date 2015-06-18 Time 15:06 Rev Time 0.00
Received By ccole Date 2015-06-18 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-21 Cont ID  
Sent By ccole Date 2015-05-21 Time 07:58 Rev Time 0.00
Received By ccole Date 2015-04-30 Time 07:58 Sent To  
Notes
2015-05-21 08:03:211ST. MECHANICAL REVIEW
  
 1) THE OUTSIDE AIR DUCT FOR THE NEW AIR HANDLER IS NOT
 SHOWN ON THE PLAN. PLEASE PROVIDE DETAILS INCLUDING
 TYPE AND SIZE OF DUCT, DUCT RUN, AND AIR INLET
 LOCATION.
 2) PROVIDE TWO COPIES OF THE NOA FOR THE LOUVER (NOTED
 AS "L" IN THE AIR DISTRIBUTION SCHEDULE),
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-23 Cont ID  
Sent By tklarge Date 2015-05-23 Time 11:26 Rev Time 0.00
Received By tklarge Date 2015-05-23 Time 10:54 Sent To  
Notes
***NONE***