Plan Review Details - Permit 15041121
Plan Review Stops For Permit 15041121
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 14:03 Rev Time 0.00
Received By jwitmer Date 2015-06-19 Time 13:36 Sent To G
Notes
2015-06-19 14:03:06 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15041121
 ADD: 1616 N FLORIDA MANGO
 CONT: MARYJULI
 TEL: ( 561)386-6032
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 1) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 416.7 SPRAY ROOMS SHALL BE SEPARATED BY 1 HOUR
 SEPARATION FIRE BARRIERS.
  
 2) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B
 416.7 SPRAY ROOMS. FLOORS SHALL BE WATER-PROOFED AND
 DRAINED IN AN APPROVED MANNER.
  
 3) SHOW COMPLIANCE WITH FBC-B 416.3 SPRAYING SURFACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FBC-MECHANICAL CODE.
  
 4) SHOW COMPLIANCE WITH 416.4 SPRAY BOOTHS SHALL BE
 DESIGNED, CONSTRUCTED AND OPERATED IN ACCORDANCE THE
 FLORIDA FIRE PREVENTION CODE. NFPA 33.
  
 5) THE PLANS NEED TO SHOW COMPLIANCE WITH: FBC-B 416.5.
 A AUTOMATIC FIRE EXTINGUISHING SYSTEM.
  
 6) THE PLANS WILL NEED TO SHOW COMPLIANCE WITH HOW THE
 ROOFTOP VENTS WILL BE ATTACHED/ ANCHORED TO RESIST THE
 MOMENT OF OVERTURNING IN A 170 VULT MPH/ 3 SECOND GUST
 WIND. THE ROOFTOP EXHAUST IS CONSIDERED COMPONENTS AND
 CLADDING.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-01 Cont ID  
Sent By dhayes Date 2015-05-01 Time 10:03 Rev Time 0.00
Received By dhayes Date 2015-05-01 Time 07:56 Sent To  
Notes
2015-05-01 10:03:325/1/2015
 PROJECT: RELIEF AUTO BODY
 PERMIT#: 15041121
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) NEC 220.
 PROVIDE A TOTAL CONNECTED LOAD SUMMARY CALCULATION
 INDICATING THE ADDITIONAL LOAD OF THE NEW SPRAY BOOTH
 EQUIPMENT.
  
 2) NEC 230.42(B)
 THE SERVICE ENTRANCE INDICATED ON THE RISER DIAGRAM HAS
 BEEN UNDERSIZED. THE MINIMUM AMPACITY FOR UNGROUNDED
 CONDUCTORS FOR SPECIFIC INSTALLATIONS SHALL NOT BE LESS
 THAN THE RATING OF THE SERVICE DISCONNECTING MEANS.
  
 3) NEC 310.16
 USE THE NEC 310.16 TO SIZE THE SERVICE ENTRANCE
 CONDUCTORS.
  
 4) NEC 210.19(A)
 THERE ARE CIRCUITS IN THE PANEL SCHEDULE WITH
 UNDERSIZED CONDUCTORS CONNECTED TO OCPD. BRANCH-CIRCUIT
 CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN THE
 MAXIMUM LOAD TO BE SERVED. NEC 210.19(A)
  
 5) NEC 408.4
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. NEC 408.4
  
 6) WPB AMENDMENTS TO THE FBC 107.2.5
 INDICATE THE LOCATION OF THE ELECTRICAL SERVICE ON THE
 BUILDING RELATIVE TO THE LOCATION OF THE NEW SPRAY
 BOOTH.
  
 7) WPB AMENDMENTS TO THE FBC 107.2.5
 INDICATE THE LOACTION OF THE ELECTRICAL PANEL ON OR IN
 THE BUILING RELATIVE TO THE LOCATION OF THE NEW SPRAY
 BOOTH.
  
 8) WPB AMENDMENTS TO THE FBC 107.3.5.1.2
 INDICATE THE LOCATION ON A FLOOR PLAN OF THE SWITCHES,
 OUTLETS, LIGHTS, FANS, MOTORS, CONTROLERS, DISCONNECTS,
 ETC ON, IN, ON, AND/OR AROUND THE SPRAY BOOTH. INDICATE
 WHICH ARE NEW AND WHICH ARE EXISTING TO REMAIN.
  
 9) NEC 516.3
 INDICATE THE HAZARDOUS LOCATIONS ON THE FLOOR PLAN AND
 INDICATE WHICH OF THE DEVICES WITHIN THOSE LOCATIONS
 ARE TO BE HOUSED AND OR PROTECTED BY EQUIPMENT SUITABLE
 FOR THAT ENVIRONMENT.
  
 10) NEC 516
 PROVIDE MANUFACTURER PRODUCT APPROVAL DOCUMENTS
 INDICATING COMPLIANCE WITH THE NEC 110(3)(B) AND NEC
 516.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-05-04 Cont ID  
Sent By pleduc Date 2015-05-04 Time   Rev Time 0.00
Received By pleduc Date 2015-05-04 Time 13:20 Sent To B
Notes
2015-05-04 13:22:22THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 ALL INSTALLATIONS SHALL COMPLY WITH THE 2012 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE AND ALL APPLICABLE
 ASSOCOATED CODES.
  
 THE REQUIRED SUPPRESSION SYSTEM SHALL BE DONE UNDER
 SPARATE SHOP DRAWINGS.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-06-20 Cont ID  
Sent By tklarge Date 2015-06-20 Time 03:53 Rev Time 0.00
Received By tklarge Date 2015-06-20 Time 03:30 Sent To  
Notes
2015-06-20 03:38:411) SUBMIT 2 COPIES OF MANUFACTURING SPECS./
 INSTALLATION MANUAL FOR THE SPRAY BOOTH.WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE SPRAY
 BOOTH. COMPLY W/2010 FUEL GAS CODE SEC.304.
 3) THE PLANS SHOW A 2" GAS LINE REDUCING DOWN TO 1".
 CLARIFY.
 4) INDICATE ON THE PLANS THE TYPE OF PIPE BEING USED
 FOR THE GAS.WPB AMEND. TO 2010 FBC SEC. 107.2.1, 2010
 FUEL GAS CODE SEC. 402.1,402.3.
 5) SUBMIT TWO COPIES OF THE APPLICABLE GAS SIZING TABLE
 USED TO SIZE TO THE GAS LINE TO THE BOOTH. 2010 FUEL
 GAS CODE SEC. 402.1,402.3.
 6) SHOW THE LOCATION OF THE NEW GAS METER AND GAS TRAIN
 ON THE TOP VIEW OF THE BOOTH.
 7) CLARIFY THE ACRONYM "FLA:56" THAT SHOWN AT THE NEW
 GAS METER.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-20 Cont ID  
Sent By tklarge Date 2015-06-20 Time 03:52 Rev Time 0.00
Received By tklarge Date 2015-05-01 Time 10:24 Sent To  
Notes
2015-05-01 07:54:15B40

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-15 Cont ID  
Sent By ccole Date 2015-06-15 Time 10:14 Rev Time 0.00
Received By ccole Date 2015-06-15 Time 10:14 Sent To  
Notes
2015-06-15 10:51:231ST REVIEW: FBC 2010 MECHANICAL
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS (CUT SHEETS)
 FOR THE SPRAY BOOTH, FANS, AND SPRAY EQUIPMENT-
 SECTIONS 5.1, 7.10, AND 11.1 NFPA 33. THE EXHAUST FANS
 SHALL BE IN COMPLIANCE WITH SECTION 502.7.3.6 FBC-
 MECHANICAL: FANS NOT PERMITTED IN DUCTS, AND SHALL HAVE
 NON-FERROUS OR NON-SPARKING ROTATING ELEMENTS.
 2) THE PLAN INDICATES NON-COMPLIANCE FOR THE REQUIRED
 3' CLEARANCE TO BE MAINTAINED ON ALL SIDES OF THE BOOTH
 SECTION 5.3.2 NFPA 33. RELOCATE THE BOOTH OR PROVIDE
 DATA CONSISTENT WITH EXCEPTIONS 1 OR 2.
 3) PROVIDE CALCULATIONS FOR THE VENTILATION SYSTEM
 INDICATING COMPLIANCE WITH THE 100 CFM AIR VELOCITY
 REQUIREMENT PER SECTION 502.7.3.3 FBC-10 MECHANICAL.
 4) INDICATE A SEQUENCE OF OPERATIONS INDICATING HOW
 CONTINUOUS VENTILATION WILLL BE PROVIDED DURING SPRAY
 OPERATIONS- SECTION 502.7.3.1 MECHANICAL.
 5) PROVIDE A DETAIL SHOWING THE EXHAUST DISHARGE
 HEIGHTS ABOVE THE ROOF IN COMPLIANCE WITH SECTION 7.4
 NFPA- 33: MINIMUM 6 FT. ABOVE THE ROOF SURFACE.
 6) PROVIDE A ROOF PLAN INDICATING THE CLEARANCE
 DISTANCE MEASUREMENTS OF THE EXHAUST DISCHARGE TO THE
 PROPERTY LINE, THE AIR INTAKE AND OTHER OPERABLE
 OPENINGS, AND EXTERIOR WALLS AND ROOFS- 501.2.1(1).
 7) SHOW A MEANS OF SUPPORT FOR THE DUCTS ABOVE AND
 BELLOW THE ROOF- SECTION 7.8 NFPA 33. PLEASE NOTE THAT
 EQUIPMENT INSTALLED ABOVE THE ROOF SHALL BE ANCHORED TO
 WITHSTAND 170 MPH WIND LOADS.
 8) IDENTIFY AND LABEL THE STORAGE MIXING AREAS ON THE
 PLAN, AND INDICATE THE QUANTITIES OF FLAMMABLE AND
 COMBUSTIBLE LIQUIDS TO BE STORED AND HANDLED IN THESE
 ROOMS OR SPACES, AND HOW THEY WILL BE VENTILATED- SEE
 CHAPTER 8 NFPA 33, AND SECTION 502.8 FBC-10 MECHANICAL.
 9) PROVIDE COMPLETE PLANS, DETAILS, AND SPECIFICATIONS
 FOR THE REQUIRED AUTOMATIC FIRE PROTECTION SYSTEM-
 SECTION 9.1 NFPA 33; OR INDICATE ON THE PLAN IT WILL BE
 DONE UNDER SEPARATE PERMIT.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-08 Cont ID  
Sent By dkittred Date 2015-05-08 Time 13:38 Rev Time 0.00
Received By dkittred Date 2015-05-08 Time 12:53 Sent To  
Notes
***NONE***