Plan Review Details - Permit 15041109
Plan Review Stops For Permit 15041109
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-09 Cont ID  
Sent By dhayes Date 2015-06-09 Time 09:54 Rev Time 0.00
Received By dhayes Date 2015-06-09 Time 09:54 Sent To  
Notes
2015-06-09 09:55:57APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL TO A MINIMUM 1/8 INCH
 SCALE. WPB AMENDMENTS TO FBC 107.2.1, AND 107.2.1.4
  
 2) INDICATE THE LOCATION OF THE SOURCE FOR THE CABLE
 RUN. THE PLAN INDICATES ONLY THE ROOM WHERE THE CABLE
 TERMINATES.
  
 3) PROVIDE THE MANUFACTURER INFORMATION FOR THE
 EQUIPMENT AND CABLES TO BE INSTALLED OR AT MINIMUM
 INDICATE THE CABLE TYPE TO BE INSTALLED.
  
 4) SIGN ALL PLANS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC, WPB AMENDMENTS 107.2.1
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-04 Cont ID  
Sent By dhayes Date 2015-05-04 Time 14:36 Rev Time 0.00
Received By dhayes Date 2015-05-04 Time 14:22 Sent To  
Notes
2015-05-04 14:36:23REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND
 DRAWN UPON SUITABLE MATERIAL TO A MINIMUM 1/8 INCH
 SCALE. WPB AMENDMENTS TO FBC 107.2.1, AND 107.2.1.4
  
 2) INDICATE THE LOCATION OF THE SOURCE FOR THE CABLE
 RUN. THE PLAN INDICATES ONLY THE ROOM WHERE THE CABLE
 TERMINATES.
  
 3) ALWAYS PROVIDE THE MANUFACTURER INFORMATION FOR THE
 EQUIPMENT AND CABLES TO BE INSTALLED OR AT MINIMUM
 INDICATE THE CABLE TYPE TO BE INSTALLED.
  
 4) SIGN ALL PLANS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. FBC, WPB AMENDMENTS 107.2.1
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-09 Cont ID  
Sent By dhayes Date 2015-06-09 Time 10:14 Rev Time 0.00
Received By dhayes Date 2015-05-22 Time 10:41 Sent To  
Notes
2015-05-13 10:41:44RESUBMITTAL SENT TO DAVID HAYES FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-04 Cont ID  
Sent By dhayes Date 2015-05-04 Time 14:36 Rev Time 0.00
Received By dhayes Date 2015-04-29 Time   Sent To  
Notes
2015-04-29 14:53:15<5000 ELEC