Plan Review Details - Permit 15041103
Plan Review Stops For Permit 15041103
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-07 Cont ID  
Sent By tlarge Date 2015-05-07 Time 09:07 Rev Time 0.00
Received By tklarge Date 2015-05-06 Time 12:07 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-02 Cont ID  
Sent By tklarge Date 2015-05-02 Time 11:21 Rev Time 0.00
Received By tklarge Date 2015-05-02 Time 11:03 Sent To  
Notes
2015-04-29 14:15:30ROUTED TO GARY DESK PER DOUG

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-07 Cont ID  
Sent By tklarge Date 2015-05-07 Time 09:07 Rev Time 0.00
Received By tklarge Date 2015-05-07 Time 09:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-02 Cont ID  
Sent By tklarge Date 2015-05-02 Time 11:21 Rev Time 0.00
Received By tklarge Date 2015-05-02 Time 11:03 Sent To  
Notes
2015-05-02 11:21:08!) SUBMIT A CLEAR AND DESCRIPTIVE NARRATIVE AS TO THE
 ENTIRE SCOPE OF WORK TO BE DONE. FROM THE SUBMITTED
 DRAWING I CANNOT DETERMINE WHAT TYPE OF WORK IS BEING
 DONE ON THE EXTERIOR UNDERGROUND PLUMBING LINES. THERE
 IS NO DESCRIPTION OF THIS WORK ON THE APPLICATION.WPB
 AMENDMENTS TO 2010 FPC SEC.107.2.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 TANKLESS WATER HEATER. THE DOCUMENT THAT WAS SUBMITTED
 IS INADEQUATE.
 3) WHAT IS BEING DONE WITH THE PLUMBING ON THE EXTERIOR
 KITCHEN WALL? THE PLAN IS UNCLEAR AND CONFUSING.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 REPLACING AN EXISTING TANKLESS WATER HEATER OR
 REPLACING A TANK TYPE WATER HEATER.
 5) AN ELECTRIC PLAN, APPLICATION, AND PERMIT MAY BE
 REQUIRED FOR THE SCOPE OF WORK BEING DONE.WPB AMEND. TO
 2010 FBC SEC. 105.1.
 6) SUBMIT A CLEAR AND LEGIBLE PLUMBING PLAN FOR REVIEW.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 7) WILL ANY OF THE WALL BE REMOVED AND REPLACED TO
 REPLACE THE TUB/SHOWER VALVE? IF SO, A SEPARATE PERMIT
 MAY BE REQUIRED,
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  