Plan Review Details - Permit 15041085
Plan Review Stops For Permit 15041085
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-06-10 Cont ID  
Sent By shill Date 2015-06-10 Time 11:58 Rev Time 0.00
Received By shill Date 2015-06-10 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-06-09 Cont ID  
Sent By shill Date 2015-06-09 Time 08:54 Rev Time 0.00
Received By dhayes Date 2015-06-09 Time 08:54 Sent To B
Notes
2015-06-09 09:04:39APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) NEC 600.3 LISTING. ELECTRIC SIGNS, SECTION SIGNS,
 AND OUTLINE LIGHTING SHALL BE LISTED AND INSTALLED IN
 CONFORMANCE WITH THAT LISTING..
  
 2) NEC 600.6(A)(1) EACH SIGN OR BRANCH CIRCUIT
 SUPPLYING A SIGN, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN.
  
 3) FBC-E 505.2.4. LIGHTING FOR ALL EXTERIOR
 APPLICATIONS NOT EXEMPTED IN SECTION 505.1 SHALL HAVE
 AUTOMATIC CONTROLS CAPABLE OF TURNING OFF EXTERIOR
 LIGHTING WHEN SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN
 THE LIGHTING IS NOT REQUIRED. LIGHTING DESIGNATED FOR
 DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY AN
 ASTRONOMICAL TIME SWITCH OR PHOTOCELL. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMMING
 DURING LOSS OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-10 Cont ID  
Sent By shill Date 2015-06-10 Time 11:58 Rev Time 0.00
Received By shill Date 2015-05-21 Time 07:54 Sent To  
Notes
2015-06-02 07:53:446/2 TO ELEC
  
2015-04-29 11:36:39ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-02 Cont ID  
Sent By shill Date 2015-05-22 Time 07:53 Rev Time 0.00
Received By shill Date 2015-06-02 Time 07:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-22 Cont ID  
Sent By sgraham Date 2015-05-22 Time 11:17 Rev Time 0.00
Received By sgraham Date 2015-05-22 Time 11:17 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-05-06 Cont ID  
Sent By sgraham Date 2015-05-06 Time 12:14 Rev Time 0.00
Received By sgraham Date 2015-05-06 Time 12:14 Sent To B
Notes
2015-05-06 12:17:265/6/15 ZONING FAILED
  
 1. SUBMIT TWO UP TO DATE SURVEYS SHOWING THE LOCATION
 OFEXISTING SIGN
 2. SUBMIT A PICTURE OF THE EXISTING SIGN WITH THE
 DIMENSION OF THE SIGN, THE HEIGHT AND WIDTH,
  