Plan Review Details - Permit 15041018
Plan Review Stops For Permit 15041018
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-28 Cont ID  
Sent By jgomez Date 2015-05-28 Time 15:12 Rev Time 0.00
Received By jgomez Date 2015-05-28 Time 15:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-26 Cont ID  
Sent By jgomez Date 2015-05-26 Time 11:59 Rev Time 0.00
Received By jgomez Date 2015-05-26 Time 11:12 Sent To  
Notes
2015-05-26 12:22:01RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENERGY CALCULATIONS FORM 402-2010 SUBMITTED:
 A) COMPLETE ALL THE INFORMATION ON THE COVER PAGE. NEED
 TO COMPLETE ITEMS #6C, ##9A, #9B, ##15. SEC. AND,
 COMPLETE INFORMATION ON TOP OF FORM: PERMITTING OFFICE
 AND JURISDICTION NUMBER. SEC. 103.2.2 OF 2020
 FBC-ENERGY CONSERVATION.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. SEC.
 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) COMPLETE ALL THE INFORMATION ON TABLE 402A ON SECOND
 PAGE OF FORM SUBMITTED. NOTE: THE INSTALLED VALUES MUST
 MEET OR EXCEED THE VALUES SHOWN ON THE PERFORMANCE
 CRITERIA. SEE NOTES BELOW TABLE 402A. SEC. 103.2.2 OF
 2020 FBC-ENERGY CONSERVATION.
  
 D) COMPLETE ALL THE INFORMATION ON TABLE 402B ON SECOND
 PAGE OF FORM SUBMITTED. SEC. 103.2.2 OF 2020 FBC-ENERGY
 CONSERVATION.
  
 2- CLEARLY SPECIFY TYPE AND SIZE OF EXISTING WINDOWS
 (SPECIALLY THE BEDROOM WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 604 OF
 FBC-EXISTING BUILDING.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-19 Cont ID  
Sent By rlecky Date 2015-05-19 Time 14:28 Rev Time 0.00
Received By rlecky Date 2015-05-19 Time 14:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-28 Cont ID  
Sent By jgomez Date 2015-05-28 Time 15:12 Rev Time 0.00
Received By jgomez Date 2015-05-28 Time 08:31 Sent To  
Notes
2015-05-28 08:33:57TO JG DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-26 Cont ID  
Sent By   Date 2015-05-26 Time   Rev Time 0.00
Received By jgomez Date 2015-04-28 Time 14:57 Sent To  
Notes
2015-04-28 14:57:45SENT TO R7 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-26 Cont ID  
Sent By ccole Date 2015-05-26 Time 15:03 Rev Time 0.00
Received By ccole Date 2015-05-26 Time 15:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-16 Cont ID  
Sent By tklarge Date 2015-05-16 Time 07:07 Rev Time 0.00
Received By tklarge Date 2015-05-16 Time 06:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-05-07 Cont ID  
Sent By ajones Date 2015-05-07 Time 16:36 Rev Time 0.00
Received By ajones Date 2015-05-07 Time 16:36 Sent To  
Notes
***NONE***