Plan Review Details - Permit 15041017
Plan Review Stops For Permit 15041017
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-11 Cont ID  
Sent By hmoser Date 2015-05-11 Time 14:41 Rev Time 0.00
Received By hmoser Date 2015-04-29 Time 09:38 Sent To  
Notes
2015-04-29 09:38:52ROUTED TO MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-11 Cont ID  
Sent By hmoser Date 2015-05-11 Time 14:41 Rev Time 0.00
Received By hmoser Date 2015-05-11 Time 14:24 Sent To  
Notes
2015-05-11 14:37:44PASS PROVISO
 1) PROVIDE DETAIL FROM THE ENGINEER ON CURB TO ROOF
 TIE DOWN AND FAN TO CURB TIE DOWN. PROVIDE TYPE OF
 ANCHOR AND SIZE FOR WIND LOAD
 PER SECTION 301.12 WIND RESISTANCE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676