Plan Review Details - Permit 15041011
Plan Review Stops For Permit 15041011
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-07-01 Cont ID  
Sent By albarran Date 2015-07-01 Time 16:24 Rev Time 0.00
Received By albarran Date 2015-07-01 Time 16:24 Sent To I
Notes
2015-07-01 16:24:46PER A TELEPHONE CONVERSATION WITH TOM DRAKE OF
 LIGHTNING ELECTRIC, THIS PERMIT IS BEING ISSUED WITHOUT
 ELECTRIC SO THAT THE STRUCTURAL CAN PROCEED. EC WILL
 SUBMIT FOR THE ELECTRIC PRIOR TO COMMENCEMENT OF ANY
 ELECTRICAL WORK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-28 Cont ID  
Sent By albarran Date 2015-05-28 Time 20:09 Rev Time 0.00
Received By albarran Date 2015-05-28 Time 20:09 Sent To I
Notes
2015-05-28 20:11:505/28/2015
 PROJECT: GLUE PRODUCTS
 PERMIT#: 15041011
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE
 WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER
 DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 ELECTRICAL
  
 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL
 PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO
 ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC
 408.4
  
 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR
 AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE
 PROVIDED WITH CONTROLS AS REQUIRED IN FBC-ENERGY
 CONSERVATION SECTIONS 505 ELECTRICAL POWER & LIGHTING
 SYSTEMS (MANDATORY).
  
 4. INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL
 EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL
 WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT.
 NEC 110.26 (D)
  
 5. VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16
  
 6. INDICATE ALL REQUIRED EMERGENCY ILLUMINATION.
 EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS
 OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL
 OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED
 ILLUMINATION. NEC 700.16(F)
  
 7. PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT
 WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS.
 NEC 210.63, 210.8(A)(3), NEC 440.14
  
 8. INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT
 AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A)
  
 SEPARATE ELECTRICAL PERMIT ACCOMPANIED BY
 MANUFACTURER'S EQUIPMENT SUBMITTALS REQUIRED FOR
 ELECTRICAL WORK
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353,
 561-805-7943 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-29 Cont ID  
Sent By Lindow Date 2015-06-29 Time   Rev Time 0.00
Received By   Date 2015-06-29 Time   Sent To E
Notes
2015-06-29 15:25:46C9

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-06-09 Cont ID  
Sent By rlindow Date 2015-06-09 Time   Rev Time 0.00
Received By rlindow Date 2015-06-09 Time   Sent To M
Notes
2015-05-12 17:57:26PROVIDE QUANTITY AND CLASS OF FLAMMABLE LIQUIDS TO BE
 STORED IN MIXING ROOMS.
 PLAN SHOWS 3 DIFFERENT ROOMS, ADDRESS ALL 3.
 PROVIDE QUANTITY OF LARGEST CONTAINER(S) IN EACH ROOM.
  
 MIXING ROOMS ONLY NO SPRAYING PER CONTRACTOR. RLINDOW
 6/09/15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-08 Cont ID  
Sent By albarran Date 2015-07-08 Time 09:05 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-07-08 09:05:53ELECTRICAL PROVISO:
 IN AN EFFORT TO EXPEDITE THE CONSTRUCTION OF THIS
 PROJECT, THE PERMIT WAS ISSUED PENDING AN ELECTRICAL
 PERMIT. A REVISION TO THESE DRAWINGS, ADDRESSING ALL
 ELECTRICAL REQUIREMENTS PREVIOUSLY STATED TO BE
 SUBMITTED AT THE TIME OF ELECTRICAL PERMIT APPLICATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-30 Cont ID  
Sent By   Date 2015-06-30 Time   Rev Time 0.00
Received By skennedy Date 2015-06-24 Time 18:29 Sent To  
Notes
2015-06-30 13:20:12PULLED FROM B15 AND ROUTED TO ELECTRICAL.
2015-06-24 18:29:38TRAVELING W/ 15041010 SENT TO B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-28 Cont ID  
Sent By albarran Date 2015-05-28 Time 20:12 Rev Time  
Received By albarran Date 2015-04-27 Time   Sent To  
Notes
2015-05-28 20:15:06THIS APPLICATION IS RUNNING TOGETHER WITH THE MASTER
 {PERMIT 15041010 WHICH WILL HAVE A HOLD FOR ELECTRICAL
 SUB PERMIT ADDED
2015-04-27 15:36:44ROUTED TO MECHANICAL OVER 5K

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-07 Cont ID  
Sent By hmoser Date 2015-05-07 Time 15:30 Rev Time 0.00
Received By hmoser Date 2015-05-07 Time 15:30 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved