| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1. PROVIDE THE CIRCUITRY ON THE FLOOR PLAN TO COINCIDE |
| WITH THE REQUIRED PANEL SCHEDULE AS WELL AS A RISER |
| DIAGRAM AND LOAD CALCULATION. FBC 107.3.5 ELECTRICAL |
| |
| 2. PROVIDE COMPLETE CIRCUIT DIRECTORIES FOR ELECTRICAL |
| PANELS. EVERY CIRCUIT SHALL BE LEGIBLY IDENTIFIED AS TO |
| ITS CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC |
| 408.4 |
| |
| 3. INDICATE THE REQUIRED LIGHTING CONTROLS FOR INTERIOR |
| AND EXTERIOR ILLUMINATION. LIGHTING SYSTEMS SHALL BE |
| PROVIDED WITH CONTROLS AS REQUIRED IN FBC-ENERGY |
| CONSERVATION SECTIONS 505 ELECTRICAL POWER & LIGHTING |
| SYSTEMS (MANDATORY). |
| |
| 4. INDICATE THE REQUIRED LIGHTING ABOUT ELECTRICAL |
| EQUIPMENT. ILLUMINATION SHALL BE PROVIDED FOR ALL |
| WORKING SPACES ABOUT ELECTRICAL PANELS AND EQUIPMENT. |
| NEC 110.26 (D) |
| |
| 5. VERIFY SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16 |
| |
| 6. INDICATE ALL REQUIRED EMERGENCY ILLUMINATION. |
| EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED MEANS |
| OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND ALL |
| OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE REQUIRED |
| ILLUMINATION. NEC 700.16(F) |
| |
| 7. PROVIDE THE LOCATION OF ALL MECHANICAL EQUIPMENT |
| WITH ASSOCIATED REQUIRED DISCONNECTS AND GFI OUTLETS. |
| NEC 210.63, 210.8(A)(3), NEC 440.14 |
| |
| 8. INDICATE PROVISIONS FOR THE REQUIRED SIGN CIRCUIT |
| AND SHOW WINDOW LIGHTING. NEC 210.62, 600.5(A) |
| |
| SEPARATE ELECTRICAL PERMIT ACCOMPANIED BY |
| MANUFACTURER'S EQUIPMENT SUBMITTALS REQUIRED FOR |
| ELECTRICAL WORK |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |