Plan Review Stops For Permit 15041000 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2015-05-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-05-05 |
Time |
16:54 |
Rev Time |
|
Received By |
jwitmer |
Date |
2015-05-05 |
Time |
|
Sent To |
|
|
Notes |
2015-05-05 16:55:11 | BUILDING PROVISO; | | SUITE 2505-B GREY BOX | | 1) TENANT BUILDOUT WILL EXCEED COMMON PATH OF TRAVEL | | WITH FIXTURES IN PLACE REQUIRING (2) EXITS. THE 2ND | | MEANS OF EGRESS THROUGH THE STORAGE/ STOCK ROOM WILL | | NEED TO COMPLY WITH: | | 2010 FBC-B 1014.2.4 EXCEPTION # 2. MEANS OF EGRESS ARE | | NOT PROHIBITED THROUGH STOCKROOMS IN GROUP M | | OCCUPANCIES WHEN ALL OF THE FOLLOWING ARE MET: | | | | 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS | | THAT FOUND IN THE MAIN RETAIL AREA; | | | | 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS | | THROUGH THE STOCKROOM; | | | | 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE | | EGRESS SIDE; AND | | | | 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118 | | MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED | | WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE | | REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA | | TO THE EXIT WITHOUT OBSTRUCTIONS. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-05-18 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-18 |
Time |
16:32 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-05-18 |
Time |
16:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2015-05-04 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2015-05-04 |
Time |
15:52 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2015-05-04 |
Time |
15:52 |
Sent To |
|
|
Notes |
2015-05-04 15:54:42 | PERMIT # 15041000 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVISO: | | | | 1) AS PREVIOUSLY DISCUSSED WITH THE PROPERTY | | MANAGEMENT, THIS PROPERTY IS EQUIPPED WITH A COMMON | | FIRE ALARM SYSTEM. PROVIDE VISUAL AND AUDIBLE | | NOTIFICATION APPLIANCE IN ALL PUBLIC AND COMMON USE | | SPACES (NFPA 101: CHAPTER 9, SECTION 9.6: FIRE | | DETECTION, ALARM. AND COMMUNICATION SYSTEMS. 9.6.3.6.1: | | THE GENERAL EVACUATION ALARM SIGNAL SHALL OPERATE | | THROUGHOUT THE ENTIRE BUILDING.) | | | | SUE ELLEN CALDERON | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-07-07 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-07-07 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-06-11 |
Time |
16:53 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-06-01 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-06-01 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-04-29 |
Time |
13:24 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2015-05-05 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-05-05 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-05-05 |
Time |
16:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2015-07-07 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-07-07 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-07-07 |
Time |
12:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-06-01 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-06-01 |
Time |
15:06 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-06-01 |
Time |
13:42 |
Sent To |
|
|
Notes |
2015-06-01 15:06:32 | PLAN DENIED | | 1) PROVIDE OUTSIDE AIR CALCULATIONS ON PLANS | | PER TABLE 403.3 FBC (M) 2010 | | 2) ABANDONED EQUIPMENT MUST BE REMOVED FROM THE | | ROOF AND SEAL CURB WATER TIGHT | | 3) PROVIDE A DETAIL FROM THE ENGINEER ON THE | | EXHAUST FAN CURB TO ROOF AND FAN TO CURB, PROVIDE | | TYPE AND SIZE OF ANCHOR USED. PER SECTION | | 301.12 WIND RESISTANCE FBC (M) 2010 | | 4) REFER TO SECTION 503.2.5.4 SHUT OFF | | DAMPER CONTROLS FOR FRESH AIR. 2010 | | FLORIDA ENERGY CODE | | 5) PROVIDE ENERGY CALCULATIONS PER SECTION | | 503.2.1 FLORIDA ENERGY CODE 2010 | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2015-06-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-06-29 |
Time |
12:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-06-29 |
Time |
12:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-05-26 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-05-26 |
Time |
15:19 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-05-26 |
Time |
15:19 |
Sent To |
|
|
Notes |
2015-05-26 15:18:55 | 1) THE OCCUPANT LOAD FOR THE PLUMBING FIXTURES IS SHOWN | | AS 30 PERSONS. WHERE DID THIS NUMBER COME FROM? THE | | PLAN SHOWS 97 OCUPANTS JUST FOR THE SALES AREA. | | CLARIFY. NOTE: THE FIXTURE COUNT THAT IS NOTED IS | | CORRECT.PLEASE CORRECT THE NUMBER OF PERSONS.WPB AMEND. | | TO 2010 FBC SEC. 107.2.1. | | 2) SHT. A1.00 DELETE THE DIAGRAM FOR A PARALLEL | | APPROACH FOR THE DRINKING FOUNTAIN. A FORWARD APPROACH | | IS THE ONLY TYPE PER MITTED EXCEPT IN CHILDREN'S | | FACILITIES. FAC SEC.602.2. | | 3) SHT. A8.01, DETAIL #5 - SHOW THE WIDTH OF BOTH | | TOILET ROOMS. A MINIMUM OF 85 INCHES IF BUILT PERFECT, | | 86 INCHES ALLOWS FOR CONSTRUCTION TOLERANCES. | | 4) SHT. A8.01 - THE ELEVATION DETAIL SHOWS A DIMENSION | | OF 39" - 41". WHAT IS THIS DIMENSION FOR? NOTHING IS | | NOTED.CLARIFY. | | 5) SHOW THE HEIGHT DIMENSION OF THE GRAB BAR FROM THE | | FINISH FLOOR. COMPLY W/ FAC SEC. 609.4. THE GRAB BARS | | SHALL BE MEASURED TO THE HEIGHT OF THE GRIPPING | | SURFACE. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2015-07-07 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-07-07 |
Time |
13:34 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-07-07 |
Time |
13:34 |
Sent To |
|
|
Notes |
2015-06-16 15:24:44 | CD & PAPER PLANS SUBMITTED INSTEAD ON PEDDS. CP |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2015-05-14 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2015-05-14 |
Time |
|
Rev Time |
|
Received By |
llouie |
Date |
2015-05-14 |
Time |
|
Sent To |
|
|
Notes |
2015-05-14 11:04:36 | INTERIOR IMPROVEMENTS ONLY. |
|
|