Plan Review Details - Permit 15040958
Plan Review Stops For Permit 15040958
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-27 Cont ID  
Sent By shill Date 2015-05-27 Time 10:49 Rev Time 0.00
Received By shill Date 2015-05-27 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-05 Cont ID  
Sent By shill Date 2015-05-05 Time 13:24 Rev Time 0.00
Received By shill Date 2015-05-05 Time 13:24 Sent To  
Notes
2015-05-05 13:25:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A DETAIL FOR THE INFILL, FBC 107.
  
 2. VALUE TO INCLUDE THE MARKET VALUE OF LABOR,
 MATERIALS, OVERHEAD, PROFIT, ENGINEERING, FBC 109.
 PROVIDE A VALUE WITH COST BREAKDOWN WHICH INCLUDES ALL
 ITEMS LISTED.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-03 Cont ID  
Sent By dhayes Date 2015-06-03 Time 08:10 Rev Time 0.00
Received By dhayes Date 2015-06-03 Time 07:28 Sent To  
Notes
2015-06-03 08:10:216/3/2015
 PROJECT: REMODEL
 PERMIT#: 15040958
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND
 (B).
  
 2) RECESSED LUMINAIRES INSTALLED IN THE BUILDING
 THERMAL ENVELOPE SHALL BE IC AND AIR TIGHT RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN CONDITIONED AND
 UNCONDITIONED SPACES. FBC-E 502.3.8 RECESSED LIGHTING.
  
 3) IN ADDITION TO THE NUMBER OF BRANCH CIRCUITS
 REQUIRED BY OTHER PARTS OF THIS SECTION, AT LEAST ONE
 20-AMPERE BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY
 BATHROOM RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE
 NO OTHER OUTLETS. NEC 210.11(C)(3)
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION WORK.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-16 Cont ID  
Sent By dhayes Date 2015-05-16 Time 15:12 Rev Time 0.00
Received By dhayes Date 2015-05-16 Time 15:05 Sent To  
Notes
2015-05-16 15:33:435/16/2015
 PROJECT: 330 FRANKLIN RD
 PERMIT#: 15040958
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 NO ELECTRICAL PLANS HAVE BEEN SUBMITTED WITH THIS
 APPLICATION. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT
 THIS TIME.
  
 1) THE ARCHITECTUAL PLANS SUBMITTED WITH THIS
 APPLICATION INDICATE THE INSTALLATION OF SEVERAL
 ELECTRICAL ELEMENTS ASSOCIATED WITH THE RENOVATION OF A
 KITCHEN AND BATHROOM OF AN EXISTING SINGLE FAMILY
 DWELLING. PROVIDE COMPLETE ELECTRICAL PLANS DETALAILING
 THE INSTALLATION OR RENNOVATION OF THESE ELEMENTS
 INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
  
 2) A PANEL SCHEDULE INDICATING THE ALL CIRCUIT NUMBERS
 AND CORRESPONDING OCPD AND WRE SIZES. NEC 408.4
  
 3) ALL ELEMENTS INVOLVED IN THE RENOVATION INDICATED ON
 A FLOOR PLAN WITH CIRCUIT NUMBERS CORRESPONDING TO THE
 PANEL SCHEDULE. WPB AMENDMENTS TO FBC 107.3.5.1.2
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 5) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN
 BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH
 BASIN. NEC 210.52 (D)
  
 6) RECEPTACLE OUTLETS SHALL BE LOCATED ON BRANCH
 CIRCUITS IN ACCORDANCE WITH PART III OF ARTICLE 210.
 GENERAL INSTALLATION REQUIREMENTS SHALL BE IN
 ACCORDANCE WITH 406.3(A) THROUGH (F). (D) REPLACEMENT
 OF RECEPTACLES SHALL COMPLY WITH 406.3(D)(1),(2), AND
 (3) AS APPLICABLE. NEC 406.3
  
 7) IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM, LIVING
 ROOM, PARLOR, LIBRARY, DEN, SUNROOM, BEDROOM,
 RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING
 UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN NEC
 210.52(A)(1) THROUGH (A)(3).
  
 8) A RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH WALL
 COUNTERTOP SPACE THAT IS 300 MM (12 IN.) OR WIDER.
 RECEPTACLE OUTLETS SHALL BE INSTALLED SO THAT NO POINT
 ALONG THE WALL LINE IS MORE THAN 600 MM (24 IN.)
 MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN THAT
 SPACE.NEC 210.52(C)(1)
  
 9) INDICATE AND PROVIDE OR VERIFY ALL REQUIRED SMOKE
 AND/OR CARBON MONOXIDE DETECTORS. FBC-R 314-315
  
 ONCE ELECTRICAL PLANS HAVE BEEN SUBMITTED AND A REVIEW
 CAN BE COMPLETED ADDITIONAL ELERICAL REVIEW
 DEFICIENCIES MAY BE FOUND.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-03 Cont ID  
Sent By dhayes Date 2015-06-03 Time 08:11 Rev Time 0.00
Received By dhayes Date 2015-06-01 Time   Sent To  
Notes
2015-06-02 08:50:31SENT TO PLUMBING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-27 Cont ID  
Sent By shill Date 2015-05-27 Time 10:49 Rev Time 0.00
Received By shill Date 2015-05-07 Time 17:09 Sent To  
Notes
2015-05-18 07:53:485/18 TO PLUMBING BOX
  
  
2015-05-07 17:10:00TO ELEC BOX
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-05 Cont ID  
Sent By shill Date 2015-05-05 Time 13:25 Rev Time 0.00
Received By shill Date 2015-05-05 Time 13:25 Sent To  
Notes
2015-04-24 15:56:07ROUTED TO BUILDING LESS THAN $5000

Review Stop P PLUMBING
Rev No 2 Status N Date 2015-06-03 Cont ID  
Sent By tklarge Date 2015-06-03 Time 05:28 Rev Time 0.00
Received By tklarge Date 2015-06-03 Time 05:17 Sent To  
Notes
2015-06-03 05:28:18PLUMBING COVERED UNDER PERMIT # 15031305.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-20 Cont ID  
Sent By tklarge Date 2015-05-20 Time 14:52 Rev Time 0.00
Received By tklarge Date 2015-05-20 Time 14:04 Sent To  
Notes
2015-05-20 14:15:16SUBMIT A SANITARY AND WATER RISER FOR REVIEW FOR THE
 THE PLUMBING CHANGES TO BE MADE. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1..
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved