Plan Review Details - Permit 15040881
Plan Review Stops For Permit 15040881
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-30 Cont ID  
Sent By aclange Date 2015-06-30 Time 16:06 Rev Time 0.00
Received By aclange Date 2015-06-30 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-16 Cont ID  
Sent By aclange Date 2015-06-16 Time 16:17 Rev Time 0.00
Received By aclange Date 2015-06-16 Time 16:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-13 Cont ID  
Sent By aclange Date 2015-05-13 Time 17:08 Rev Time 0.00
Received By aclange Date 2015-05-13 Time 17:08 Sent To  
Notes
2015-05-13 17:07:59****CORRECTIONS****
  
 ART LANGE ? BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310.
  
  
 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-06-27 Cont ID  
Sent By aclange Date 2015-06-27 Time 18:00 Rev Time 0.00
Received By dhayes Date 2015-06-27 Time 18:00 Sent To B
Notes
2015-06-27 18:04:00ROUTED TO A. C. LANGE FOR BUILDING REVIEW OF THE NEW
 PLAN PROVIDED.
  
2015-06-27 18:01:55PROVIDE A COMPLETE PANEL SCHEDULE FOR THE INSPECTOR IN
 THE FIELD NEC 408.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-06-11 Cont ID  
Sent By aclange Date 2015-06-11 Time 08:56 Rev Time 0.00
Received By dhayes Date 2015-06-11 Time 08:40 Sent To B
Notes
2015-06-11 08:55:576/11/2015
 PROJECT: RESIDENTIAL REMMODEL
 PERMIT#: 15040881
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INDICATE THE LOCATION OF THE ELECTRICAL PANEL ON THE
 FLOOR PLAN. 107.3.5.1.2.
 THE ELECTRICAL PANEL HAS NOW BEEN INDICATED ON THE PLAN
 BUT IT APPEARS TO BE LOCATED IN THE BATHROOM. THE
 ELECTRICAL PANEL IS NOT APPROVED FOR USE IN THE
 BATHROOM. NEC 240.24(E)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-29 Cont ID  
Sent By misc2 Date 2015-04-29 Time 13:51 Rev Time 0.00
Received By dhayes Date 2015-04-29 Time 13:46 Sent To B
Notes
2015-04-29 13:51:18REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) INDICATE THE LOCATION OF THE ELECTRICAL PANEL ON THE
 FLOOR PLAN. 107.3.5.1.2
  
 2) INDICATE THE LOCATION FOR THE SMOKE DETECTORS.
 FBC-RESIDENTIAL 314 AND 315.
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315.
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-02 Cont ID  
Sent By lmarchan Date 2015-06-30 Time 14:26 Rev Time 0.00
Received By lmarchan Date 2015-06-25 Time 17:39 Sent To  
Notes
2015-06-25 17:39:33SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-16 Cont ID  
Sent By aclange Date 2015-06-16 Time 16:17 Rev Time 0.00
Received By aclange Date 2015-06-09 Time 14:57 Sent To  
Notes
2015-06-09 14:57:51SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-13 Cont ID  
Sent By aclange Date 2015-05-13 Time 17:08 Rev Time 0.00
Received By aclange Date 2015-04-23 Time 16:41 Sent To  
Notes
2015-04-23 16:42:01***EXPEDITED****
 TO ELEC BOX
  