Plan Review Details - Permit 15040864
Plan Review Stops For Permit 15040864
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-09 Cont ID  
Sent By JWITMER Date 2015-06-09 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2015-06-09 Time 06:02 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-27 Cont ID  
Sent By jwitmer Date 2015-04-27 Time 08:03 Rev Time 0.00
Received By jwitmer Date 2015-04-27 Time 07:30 Sent To  
Notes
2015-04-27 08:03:29PROVISO:
 SHEET A1.1 DETAIL # 3 SHOWS A NEW EXTERIOR WALL LOUVER
 DETAIL. PRODUCT APPROVAL WILL NEED TO BE SUPPLIED TO
 COMPLY WITH:
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(C) WALL LOUVERS,
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-04 Cont ID  
Sent By RLECKY Date 2015-06-04 Time 11:56 Rev Time 0.00
Received By rlecky Date 2015-06-04 Time 11:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-12 Cont ID  
Sent By rlecky Date 2015-05-12 Time 12:42 Rev Time 0.00
Received By rlecky Date 2015-05-12 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-03 Cont ID  
Sent By PLEDUC Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-29 Cont ID  
Sent By pleduc Date 2015-04-29 Time   Rev Time 0.00
Received By pleduc Date 2015-04-27 Time 16:48 Sent To  
Notes
2015-04-29 10:30:20THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) SHEET A1.1 INDICATES AN INCORRECT REFERENCE TO THE
 FIRE CODE. THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 2) SHEET A1.1, A2.1 AND E2.1 ADD ONE (1) EXIT SIGN TO
 LEAD TO THE REAR EXIT ACCESS AND EXIT.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-09 Cont ID  
Sent By ccole Date 2015-06-09 Time 08:16 Rev Time 0.00
Received By ccole Date 2015-06-01 Time   Sent To  
Notes
2015-06-02 13:11:19B32
 NEW PLANS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-05-15 Time   Rev Time 0.00
Received By shill Date 2015-04-23 Time 17:04 Sent To  
Notes
2015-04-23 17:06:49****EXPEDITED****
 B07
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-09 Cont ID  
Sent By CCOLE Date 2015-06-09 Time 08:16 Rev Time 0.00
Received By ccole Date 2015-06-09 Time 08:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-15 Cont ID  
Sent By skennedy Date 2015-05-15 Time 10:35 Rev Time  
Received By skennedy Date 2015-04-23 Time   Sent To  
Notes
2015-05-15 10:54:25 
 1ST REVIEW: FBC 2010 MECHANICAL
 CHRISTOPHER COLE
  
 1) PROVIDE SHEET M0.1. IT WAS NOT ENCLOSED WITH THE
 SUBMITTED PLAN SETS.
 2) PROVIDE SIZING CALCULATIONS FOR THE FCU'S AND 1.5
 TON SPLIT SYSTEM- SECTION 505.2.2 FBC-10 ENERGY
 CONSERVATION.
 3) INDICATE THE MAKE AND MANUFACTURER OF THE DS
 DETECTORS ON THE PLAN, AND CLARIFY HOW THEY WILL BE
 SUPERVISED PER SECTION 606.4.1 FMC-10.
 4) PROVIDE TYPICAL DETAILS FOR SUPPORT AND HANGING OF
 THE FCU'S, AHU-1, THE DUCTWORK, AND THE CHILLED WATER
 PIPING.
 5) INDICATE THE THICKNESS OF THE CHILLED WATER PIPING
 INSULATIONS- TABLE 503.2.8 FBC-10 ENERGY CONSERVATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-14 Cont ID  
Sent By tklarge Date 2015-05-14 Time 12:15 Rev Time 0.00
Received By tklarge Date 2015-05-14 Time 05:54 Sent To  
Notes
***NONE***