Plan Review Details - Permit 15040715
Plan Review Stops For Permit 15040715
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-08 Cont ID  
Sent By shill Date 2015-07-08 Time 12:12 Rev Time 0.00
Received By shill Date 2015-07-08 Time 12:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-06-13 Cont ID  
Sent By shill Date 2015-06-13 Time 18:59 Rev Time 0.00
Received By shill Date 2015-06-13 Time 18:59 Sent To  
Notes
2015-06-13 19:00:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE ENGINEERING FOR PROPOSED CONSTRUCTION, FBC
 1609. NO PLANS WERE PROVIDED.
  
 2. PROVIDE A COPY OF A VERIFIABLE CONTRACT FOR THIS
 JOB, FBC 109. VALUE TO INCLUDE MATERIALS, LABOR,
 OVERHEAD, PROFIT, ENGINEERING.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 20:40 Rev Time 0.00
Received By albarran Date 2015-07-07 Time 20:24 Sent To B
Notes
2015-07-07 20:43:17THE FOLLOWING PROVISOS ARE ATTACHED TO THIS APPROVAL:
 1. REGARDLESS OF WHO OR WHEN THIS IS DONE, BUT FOR
 FINAL INSPECTION THIS SIGN SHALL COMPLY WITH THE FBC-E
 W/REGARDS TO LIGHTING CONTROLS.
 2. THE SUBMITTED/APPROVED DRAWING DOES NOT REFLECT THE
 DISCONNECT REQUIRED BY NEC 600.6. IT SHALL BE IN FOR
 FINAL INSPECTION.
  
  
  
  
 SENT TO BLDG. SH. MA

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-08 Cont ID  
Sent By albarran Date 2015-06-08 Time 15:53 Rev Time 0.00
Received By albarran Date 2015-06-08 Time 15:46 Sent To B
Notes
2015-06-08 15:55:03YOU SHALL PROVIDE TWO SETS OF DRAWINGS; EACH OF WHICH
 SHALL INCLUDE ALL THE NECESSARY ELECTRICAL DATA TO
 COMPLY WITH BOTH, THE 2008 EDITION OF THE NEC AND THE
 2010 EDITION OF THE FBC-ENERGY CONSERVATION. CORRECT
 THE DECLARED VALUATION FOR THE ELECTRICAL WORK ON THIS
 APPLICATION

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-07-08 Cont ID  
Sent By shill Date 2015-07-08 Time 12:12 Rev Time 0.00
Received By shill Date 2015-06-29 Time 14:08 Sent To  
Notes
2015-07-08 08:22:137/8 TO SH DESK
  
2015-06-29 14:09:36ROUTED TO ELECTRIC/CC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-06-13 Cont ID  
Sent By shill Date 2015-06-13 Time 19:00 Rev Time 0.00
Received By shill Date 2015-04-21 Time 11:32 Sent To  
Notes
2015-04-22 11:32:17SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-06-02 Cont ID  
Sent By ajones Date 2015-06-02 Time 11:07 Rev Time 0.00
Received By ajones Date 2015-06-02 Time 11:07 Sent To  
Notes
***NONE***