Plan Review Stops For Permit 15040682 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2015-06-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-10 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-10 |
Time |
08:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2015-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-09 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-09 |
Time |
12:44 |
Sent To |
|
|
Notes |
2015-06-09 12:46:49 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 4TH REVIEW; NEW STRUCTURAL SHEET SUBMITTED, LACKING THE | | NUMBER OF FASTENERS REQUIRED (SEE FIRST PLAN REVIEW): | | | | 1. OK | | | | 2. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS | | JOB, FBC 109. VALUE TO INCLUDE LABOR, MATERIALS, | | OVERHEAD, PROFIT, ENGINEERING. | | | | 2ND REVIEW, NOT ADDRESSED. VALUE IS UNREASONABLY LOW. | | 3RD REVIEW, THE VERIFIABLE CONTRACT REQUESTED WAS NOT | | PROVIDED. | | 4TH REVIEW, NOT ADDRESSED. | | | | 3. REPEAT COMMENT FOR THIS ENGINEER: | | | | SIGN FASTENING SPECIFICATION TO INCLUDE NUMBER OF | | FASTENERS REQUIRED OR FASTENING PATTERN, FBC 1609. | | | | A SET HAS BEEN RETAINED. | | | | 2ND REVIEW - THE PLANS PROVIDED ARE NOT IDENTICAL. ONE | | STRUCTURAL SHEET IN ONE SET HAS BEEN MODIFIED, THE | | OTHER HAS NOT. HAVE ENGINEER INCORPORATE THE STRUCTURAL | | INFORMATION INTO THE PLAN. | | 3RD REVIW - CORRECTION WAS HAND WRITTEN ON THE PLAN. | | THE STRUCTURAL INFORMATION IS TO BE INCORPORATED INTO | | THE DRAWING PREPARED BY THE ENGINEER. | | 4TH REVIEW - A NEW SHEET WAS PROVIDED, BUT WITHOUT THE | | NUMBER OF FASTENERS WHICH WAS PREVIOUSLY HANDWRITTEN ON | | THE PLAN BY SOMEONE OTHER THAN THE ENGINEER. | | INCORPORATE THIS INFORMATION INTO THE ENGINEER'S PLAN. | | | | 4. WHEN COMPLETING THE RESUBMITTAL FORM, PLEASE PROVIDE | | CORRECT INFORMATION - "CONTRACTOR" SHOULD BE THE | | CONTRACTOR COMPANY NAME. FAILURE TO PROVIDE THE CORRECT | | NAME WILL RESULT IN PLANS BEING FILED INCORRECTLY AND | | MAY RESULT IN PLANS GOING TEMPORARILY MISSING. | | | | 5. IF THE NEXT SUBMITTAL IS NOT CORRECT, A 4X FEE WILL | | BE ASSESSED TO THIS PERMIT AS PER FS553. | | | | WHEN RESUBMITTING, COLLATE THE PLANS SO THERE ARE TWO | | IDENTICAL SETS FOR PERMIT ISSUANCE. OLD SHEETS ARE TO | | REMAIN IN THE PACKAGE AND SHOULD BE MARKED "VOID". | | 3RD REVIEW - PLANS ARE NOT IDENTICAL. ONE SET HAS A | | PAGE WHICH IS LACKING FROM THE OTHER SET. | | 4TH REVIEW - PLANS ARE NOT IDENTICAL; NEW SHEET NOT | | INCORPORATED INTO THE PLAN. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2015-06-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-04 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-04 |
Time |
14:53 |
Sent To |
|
|
Notes |
2015-06-04 14:55:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 3RD REVIEW: | | | | 1. OK | | | | 2. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS | | JOB, FBC 109. VALUE TO INCLUDE LABOR, MATERIALS, | | OVERHEAD, PROFIT, ENGINEERING. | | | | 2ND REVIEW, NOT ADDRESSED. VALUE IS UNREASONABLY LOW. | | 3RD REVIEW, THE VERIFIABLE CONTRACT REQUESTED WAS NOT | | PROVIDED. | | | | 3. REPEAT COMMENT FOR THIS ENGINEER: | | | | SIGN FASTENING SPECIFICATION TO INCLUDE NUMBER OF | | FASTENERS REQUIRED OR FASTENING PATTERN, FBC 1609. | | | | A SET HAS BEEN RETAINED. | | | | 2ND REVIEW - THE PLANS PROVIDED ARE NOT IDENTICAL. ONE | | STRUCTURAL SHEET IN ONE SET HAS BEEN MODIFIED, THE | | OTHER HAS NOT. HAVE ENGINEER INCORPORATE THE STRUCTURAL | | INFORMATION INTO THE PLAN. | | 3RD REVIW - CORRECTION WAS HAND WRITTEN ON THE PLAN. | | THE STRUCTURAL INFORMATION IS TO BE INCORPORATED INTO | | THE DRAWING PREPARED BY THE ENGINEER. | | | | | | WHEN RESUBMITTING, COLLATE THE PLANS SO THERE ARE TWO | | IDENTICAL SETS FOR PERMIT ISSUANCE. OLD SHEETS ARE TO | | REMAIN IN THE PACKAGE AND SHOULD BE MARKED "VOID". | | 3RD REVIEW - PLANS ARE NOT IDENTICAL. ONE SET HAS A | | PAGE WHICH IS LACKING FROM THE OTHER SET. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-05-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-05-27 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-05-27 |
Time |
10:21 |
Sent To |
|
|
Notes |
2015-05-27 10:24:30 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. OK | | | | 2. PROVIDE A VERIFIABLE COPY OF THE CONTRACT FOR THIS | | JOB, FBC 109. VALUE TO INCLUDE LABOR, MATERIALS, | | OVERHEAD, PROFIT, ENGINEERING. | | | | 2ND REVIEW, NOT ADDRESSED. VALUE IS UNREASONABLY LOW. | | | | 3. REPEAT COMMENT FOR THIS ENGINEER: | | | | SIGN FASTENING SPECIFICATION TO INCLUDE NUMBER OF | | FASTENERS REQUIRED OR FASTENING PATTERN, FBC 1609. | | | | A SET HAS BEEN RETAINED. | | | | 2ND REVIEW - THE PLANS PROVIDED ARE NOT IDENTICAL. ONE | | STRUCTURAL SHEET IN ONE SET HAS BEEN MODIFIED, THE | | OTHER HAS NOT. HAVE ENGINEER INCORPORATE THE STRUCTURAL | | INFORMATION INTO THE PLAN. | | | | WHEN RESUBMITTING, COLLATE THE PLANS SO THERE ARE TWO | | IDENTICAL SETS FOR PERMIT ISSUANCE. OLD SHEETS ARE TO | | REMAIN IN THE PACKAGE AND SHOULD BE MARKED "VOID". | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-05-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-05-11 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-05-11 |
Time |
12:13 |
Sent To |
E |
|
Notes |
2015-05-11 12:17:21 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PERMIT APPLICATION IS INCOMPLETE. VALUE IS REQUIRED, | | FS 553, FBC 107. | | | | 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC | | 109. VALUE TO INCLUDE LABOR, MATERIALS, OVERHEAD, | | PROFIT, ENGINEERING. | | | | 3. REPEAT COMMENT FOR THIS ENGINEER: | | | | SIGN FASTENING SPECIFICATION TO INCLUDE NUMBER OF | | FASTENERS REQUIRED OR FASTENING PATTERN, FBC 1609. | | | | A SET HAS BEEN RETAINED. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-05-13 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-05-13 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-05-13 |
Time |
10:29 |
Sent To |
I |
|
Notes |
2015-05-13 11:14:40 | IMPORTANT NOTICE: | | FOR FINAL ELECTRICAL INSPECTION, REGARDLESS IF THIS | | SIGN WAS CONNECTED TO NEW OR EXISTING POWER, FULL | | COMPLIANCE WITH 2008 NEC & 2010 FBC ENERGY CONSERVATION | | SECTION 505.2.4 WILL BE REQUIRED. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2015-06-10 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-10 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-09 |
Time |
|
Sent To |
|
|
Notes |
2015-06-09 18:15:58 | SENT TO S HILL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2015-06-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-09 |
Time |
12:46 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-06-05 |
Time |
|
Sent To |
B |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-06-04 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-06-04 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-05-27 |
Time |
18:13 |
Sent To |
|
|
Notes |
2015-05-27 18:23:59 | RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-05-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-05-27 |
Time |
10:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-05-15 |
Time |
12:34 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-05-13 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-05-13 |
Time |
11:14 |
Rev Time |
|
Received By |
albarran |
Date |
2015-04-20 |
Time |
|
Sent To |
|
|
Notes |
2015-05-13 11:22:33 | CONTACTED DESIGNS2GO VIA EMAIL AND ROUTED TO SMALL | | DENIED BIN "D". MA | 2015-05-11 12:17:40 | 5/11 TO ELEC BOX | | | 2015-04-20 15:46:36 | INCOMING SENT TO ZONING BOX. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2015-04-22 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2015-04-22 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2015-04-22 |
Time |
09:48 |
Sent To |
B |
|
Notes |
|
|