Plan Review Details - Permit 15040647
Plan Review Stops For Permit 15040647
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-19 Cont ID  
Sent By rmcdouga Date 2015-05-19 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2015-05-19 Time 07:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-30 Cont ID  
Sent By rmcdouga Date 2015-04-30 Time 13:45 Rev Time 0.00
Received By rmcdouga Date 2015-04-30 Time 07:26 Sent To  
Notes
2015-04-30 07:36:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE CODE EDITIONS SPECIFIED ON BOTH THE PLANS AND
 CALCULATIONS ARE INCORRECT. THE CODES THAT APPLY TO
 THIS PROJECT ARE THE 2010 FLORIDA BUILDING CODE AND THE
 CODES AND STANDARDS REFERENCED BY THE 2010 FBC. THE
 2008 NATIONAL ELECTRICAL CODE AND THE 2010 FLORIDA FIRE
 PREVENTION CODE ARE REFERENCED. FBC-R CHAPTER 43.
  
 2) THE FLORIDA LICENSED ENGINEER IS REQUIRED TO USE A
 TITLE BLOCK CONTAINING THE PRINTED NAME, ADDRESS, AND
 LICENSE NUMBER OF THE ENGINEER AND IF PRACTICING
 THROUGH A DULY AUTHORIZED ENGINEERING BUSINESS, THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS ON THE COVER OR INDEX SHEET
 FOR THE CALCULATIONS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-28 Cont ID  
Sent By misc2 Date 2015-04-28 Time 08:27 Rev Time 0.00
Received By dhayes Date 2015-04-28 Time 07:15 Sent To B
Notes
2015-04-28 08:27:19FIELD INSPECTION CHECKLIST FOR ARRAY:
  
 _____ PROVE MODEL# OF PROPOSED PV MODULES AND MODEL# OF
 INSTALLED PV MODULES MATCH PRODUCT SPEC SHEETS [690.51]
 _____ PV MODULES ARE LISTED TO UL 1703 STANDARD [110.3]
 _____ ARRAY CONDUCTORS ARE NEATLY AND PROFESSIONALLY
 HELD IN PLACE, GROUPED AND SEPARATED [690.4 B]
 _____ CHECK CONNECTORS ARE POLARIZED,
 NON-INTERCHANGEABLE AND UNIQUE [690.33 A]
 _____ PROVE CONNECTORS STATE ?DO NOT DISCONNECT UNDER
 LOAD? [690.33 E 2]
 _____ CHECK THAT ELECTRICAL JUNCTION BOXES ARE READILY
 ACCESSIBLE, LISTED AND SUITABLE
 FOR ENVIRONMENT (NEMA)
 _____ ARRAY ATTACHMENTS ARE FASTENED AND SEALED
 ACCORDING TO ATTACHMENT DETAIL IN PLANS
  
 CONDUCTORS
  
 _____ CONDUCTOR TYPES USE-2 OR PV WIRE FOR EXPOSED ARE
 90? C WET RATED AND SUNLIGHT
 RESISTANT [690.31(B)] [NOTE 2008 AND 2011 NEC RESTRICT
 EXPOSED SINGLE CONDUCTOR
 WIRING TO USE-2 AND LISTED PV WIRE]. IF IN CONDUIT:
 RHW-2, THWN-2 OR XHHW-2 90? C WET RATED CONDUCTORS ARE
 REQUIRED [310.15]
 _____ CHECK CONDUCTORS INSULATION RATINGS AT 90? C [UL
 1703] TO ALLOW OPERATION AT ARE 70? C+ NEAR MODULES AND
 IN CONDUIT EXPOSED TO SUNLIGHT (ADD 17-20? C TO AMBIENT
 TEMPERATURE-2005NEC), (SEE TABLE 310.15(B)(2) IN
 2008NEC OR TABLE 310.15(B)(3)(C)
 IN 2011NEC)
  
 NOTE: TEMPERATURE-DERATED AMPACITY CALCULATIONS ARE
 BASED ON 156% OF THE SHORT CIRCUIT
 CURRENT (ISC) AND THE DERATED AMPACITY OF THE
 OVERCURRENT DEVICE IS MATCHED [690.8,9]
  
 _____ STRAIN RELIEFS/CABLE CLAMPS ARE USED ON ALL CABLE
 AND CORDS [300.4, 400.10]
 _____ CONDUCTORS SHALL BE LISTED FOR THE APPLICATION
 AND ENVIRONMENT. USE OF FINE STRANDED, FLEXIBLE
 CONDUCTOR CABLES SHALL BE PROPERLY TERMINATED WITH
 TERMINALS RATED FOR THESE CONDUCTORS [690.31 (E)(4)]
  
 _____ EXPOSED CONDUCTORS SHALL BE READILY ACCESSIBLE
 AND IN A RACEWAY IF OVER 30 VOLTS ?
 RACEWAYS CANNOT BE INSTALLED ON MODULES. CONDUCTORS
 SHOULD BE INSTALLED NOT READILY
 ACCESSIBLE.
 _____ DC CONDUCTOR COLORS ARE THE SAME AS AC. GROUNDED
 CONDUCTORS SHALL BE WHITE AND
 EQUIPMENT GROUNDING CONDUCTORS ARE GREEN, GREEN/YELLOW
 OR BARE.
  
 NOTE: 1)
 UNGROUNDED PV ARRAY CONDUCTORS ON UNGROUNDED ARRAYS
 WILL NOT BE WHITE IN COLOR.
 NOTE 2) TRADITIONALLY ALL PV SOURCE ARRAY WIRING WILL
 BE BLACK. NON-BLACK COLORS HAVE
 PROVEN TO NOT BE AS DURABLE IN THE UV RICH ENVIRONMENT
 AS BLACK.
  
 GROUNDING:
  
 _____ CHECK MODULE CONNECTIONS AND ALLOW FOR REMOVAL
 WITHOUT INTERRUPT GROUNDED CONDUCTOR [690.4 C]
 _____ 2 WIRE OVER 50 VOLTS SHALL BE GROUNDED [690.41]
 _____ CHECK POINT OF SYSTEM GROUNDING CONNECTION
 [690.42] IS AT ANY POINT ALONG PV OUTPUT CIRCUIT
 _____ CHECK EQUIPMENT GROUNDING OF METAL PARTS ON SOLAR
 PANEL FRAMES ARE GROUNDED PER
 250.134 AND 250.136
 _____ INSURE EITHER UNIVERSAL GROUNDING CLIPS (UGC) OR
 WEEBS? ARE LISTED AND IDENTIFIED FOR BONDING PANELS TO
 GROUNDED MOUNTING STRUCTURES [690.43]
 _____ EQUIPMENT GROUNDING CONDUCTOR (EGC) SHALL BE
 CONTAINED IN SAME RACEWAY WHEN
 LEAVING VICINITY OF ARRAY [690.43]
 _____ EGC SIZED NO SMALLER THAN #14 AND NOT SMALLER
 THAN LARGEST CURRENT CARRYING CONDUCTOR [250.122].
 _____ CHECK AC/DC IS BONDED AT INVERTER [690.C 1]
 _____ CHECK EQUIPMENT GROUNDING CONDUCTORS ARE SIZED IN
 ACCORDANCE WITH 690.45(A)
 250.122 OR (B) WHEN NO GROUND FAULT EGC SIZED TO TWO
 (2) TIMES THE TEMP AND CONDUIT
 FILL CONDUCTOR AMPACITY.
 _____ ARRAY GROUNDING ELECTRODE CONDUCTORS (GEC) NOT
 SMALLER THAN #6 AND COMPLIES WITH 250.120(C)
  
 _____ SYSTEMS WITH AC ONLY (MICRO INVERTERS) THE
 GROUNDING ELECTRODE SYSTEM SHALL BE
 INSTALLED PER [690.47(A) IN ACCORDANCE WITH [250.50
 THRU 250.60] AND [250.64]
 _____ SYSTEMS WITH BOTH AC AND DC SHALL BE INSTALLED
 PER [690.47 (C)(1) THRU (C)(8) AND SIZED PER 250.66
 (AC) 250.166 (DC)
 _____ INSPECT PREMISES GROUNDING AS IT SERVES AS THE AC
 GROUNDING FOR PV SYSTEMS
 [690.47 C 8]
 _____ IF GROUND OR POLE MOUNT GROUNDING ELECTRODE
 INSTALLED PER 250.52 AND WITHIN 6 FEET
 [690.47D EXCEPTION 2].
 _____ CHECK ELECTRODE IS CONNECTING DIRECTLY TO FRAMES
 AND STRUCTURES [690.47 D]
 _____ IF BREAKS IN RAILS OF MOUNTING STRUCTURE, CHECK
 FROM JUMPER [690.48]
 _____ BONDING, GROUNDED FITTINGS AND/OR BUSHINGS SHALL
 BE USED WITH METAL CONDUITS IF VOLTAGE IS OVER 250V DC
 [250.97]
  
 DISCONNECTING MEANS
  
 _____ DC DISCONNECTS SHALL BE LISTED FOR DC OPERATION,
 ARE NOT REQUIRED TO BE SUITABLE AS
 SERVICE EQUIPMENT AND SHALL MEET [690.17]. GENERALLY,
 MARINE, AUTOMOTIVE NOR TELECOM
 DEVICES ARE ACCEPTABLE AS THEY ARE NOT SUITED FOR USE.
 _____ DISCONNECTS SHALL BE READILY ACCESSIBLE EITHER ON
 THE OUTSIDE OF THE BUILDING OR INSIDE NEAREST THE FIRST
 POINT OF ENTRANCE [690.14(C)(1)]
 _____ NOTE MANY UL 1741 LISTED INVERTERS HAVE INTERNAL
 DC DISCONNECTS. INSPECT DC INPUT?S MAXIMUM CURRENT
 [690.53] DOES NOT EXCEED DISCONNECT LISTING AS THE
 DISCONNECT MAY BE A SEPARATELY MANUFACTURED PRODUCT
 (EITHER BY THE INVERTER MANUFACTURE OR OTHERS).
  
 AC GRID CONNECTION
  
 _____ POINT OF CONNECTION, SUPPLY SIDE. AN ELECTRICAL
 POWER PRODUCTION SOURCE CONNECTED
 SUPPLY SIDE OF THE SERVICE DISCONNECTING MEANS AS
 PERMITTED IN 230.82 (6) IS PERMITTED
 PER 705.12 (A) PERMITTING THE SUM OF THE RATINGS OF ALL
 OVERCURRENT DEVICES CONNECTED TO
 ALL POWER PRODUCTION SOURCES DO NOT EXCEED THE RATING
 OF THE SERVICE.
 _____ CIRCUIT BREAKER SHALL BE SUITABLE AS A BACKFEED
 BREAKER IF INSTALLED ON THE LOAD SIDE OF THE SERVICE
 DISCONNECTING MEANS ON THE PREMISES.
 NOTE: CIRCUIT BREAKER MARKED ?LINE? AND ?LOAD? HAVE
 BEEN EVALUATED FOR THE DIRECTION MARKED. CIRCUIT
 BREAKERS WITHOUT ?LINE? AND ?LOAD? HAVE BEEN EVALUATED
 IN BOTH DIRECTIONS.
 _____ CHECK THE SUM OF THE AMPERE RATING OF THE
 OVERCURRENT DEVICES IN CIRCUIT SUPPLYING
 POWER TO A BUSBAR OR CONDUCTOR DO NOT EXCEED 120% OF
 THE RATING OF THE BUSBAR AS
 CALCULATED IN [220.82 ~88] NEC 2008/11 [705.12(D)(2)]
  
 APPROPRIATE SIGNS INSTALLED 690 VI - MARKINGS:
  
 _____ CHECK PROPER SIGN CONSTRUCTION 690.53 WITH
 MARKINGS AS FOLLOWS:
 690.53 (1) RATED MAXIMUM POWER POINT CURRENT
 690.52 (2) RATED MAXIMUM POWER POINT VOLTAGE
 690.53 (3) MAXIMUM SYSTEM VOLTAGE (I.E. ARRAY MAX
 VOLTAGE ? A CALCULATED VALUE 690.7)
 690.53 (4) SHORT CIRCUIT CURRENT (I.E. SEE 690.8(A) ? A
 CALCULATED VALUE
 690.53 (5) MAXIMUM RATED OUTPUT CURRENT OF THE CHARGE
 CONTROLLER (IF INSTALLED)
 NOTE: NEC2011 690.53 CALLS FOR A PERMANENT LABEL. LABEL
 SHALL BE ENGRAVED AND/OR SUNLIGHT RESISTANT (I.E.
 STICKERS MAY NOT MEET THE CODE)
 _____ THE INTERACTIVE SYSTEM (GRID TIED) POINT OF
 INTERCONNECTION SHALL BE MARKED IN AN ACCESSIBLE
 LOCATION AT THE POWER SOURCE DISCONNECTING MEANS WITH
 THE RATED AC OUTPUT CURRENT AND NOMINAL AC VOLTAGE
 [690.54].
 _____ IF ENERGY STORAGE IS EMPLOYED (I.E. BATTERIES)
 THE ENERGY STORAGE SHALL ALSO BE MARKED WITH MAXIMUM
 OPERATING VOLTAGE, INCLUDING ANY EQUALIZATION VOLTAGE
 AND THE POLARITY OF THE GROUNDED CIRCUIT CONDUCTOR
 [690.55].
 _____ CHECK FOR DIRECTORY I.E. A PERMANENT SIGN, PLAQUE
 OF DIRECTORY DENOTING ALL ELECTRICAL POWER SOURCES ARE
 POSTED AT A READILY ACCESSIBLE LOCATION PER [705.10] ON
 OR IN THE PREMISES IDENTIFYING PV POWER SOURCE SYSTEM
 ATTRIBUTES AT DC DISCONNECT [690.53(1~5)]
 _____ FACILITIES WITH STAND ALONE SYSTEMS. ANY
 STRUCTURE OR BUILDING WITH A PV POWER SYSTEM THAT IS
 NOT CONNECTED TO THE GRID IS CONSIDERED STAND ALONE.
 CHECK FOR A PERMANENT SIGN IDENTIFYING SERVICE
 DISCONNECT AND PV DISCONNECTING MEANS PER [690.56,
 705.10]
  
 CHECK THAT EQUIPMENT RATINGS ARE CONSISTENT WITH
 APPLICATION AND SIGNS:
 _____ CHECK THAT INVERTER HAS A RATING AS HIGH AS MAX
 VOLTAGE ON PV POWER SOURCE SIGN [690.53]
 _____ CHECK THAT DC-SIDE OCPDS ARE DC RATED AT LEAST AS
 HIGH AS MAX VOLTAGE ON SIGN
 _____ CHECK THAT SWITCHES AND OCPDS ARE INSTALLED
 ACCORDING TO MANUFACTURERS SPECIFICATIONS
  
 (I.E. MANY 600VDC SWITCHES NOW REQUIRE PASSING THROUGH
 THE SWITCH POLES TWICE IN A
 SPECIFIC WAY TO PROTECT FOR ARC FLASH AND BLAST).
  
 NOTE: ALL EQUIPMENT SHALL BE INSTALLED PER 110.3(B)
  
 _____ CHECK THAT INVERTER IS RATED FOR THE SITE AC
 VOLTAGE SUPPLIED AND SHOWN ON THE AC POINT OF
 CONNECTION SIGN [690.54]
 _____ CHECK THAT OCPD CONNECTED TO THE AC OUTPUT OF THE
 INVERTER IS RATED AT LEAST 125% OF MAXIMUM CURRENT ON
 SIGN, AND IS NO LARGER THAN THE MAXIMUM OCPD ON THE
 INVERTER
 LISTING LABEL [690.8 A3, B1]
  
  
  
 DAVID A. HAYES
 CITY OF WEST PALM BEACH
 ELECTRICAL PLANS EXAMINER
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-19 Cont ID  
Sent By rmcdouga Date 2015-05-19 Time 07:31 Rev Time 0.00
Received By rmcdouga Date 2015-05-15 Time   Sent To B
Notes
2015-05-16 12:31:59"EXPEDITED"
 TO R. MCDOUGAL'S DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-30 Cont ID  
Sent By rmcdouga Date 2015-04-30 Time 13:45 Rev Time  
Received By rmcdouga Date 2015-04-17 Time   Sent To  
Notes
2015-04-17 18:05:11SENT TO ZONING


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved