Plan Review Details - Permit 15040646
Plan Review Stops For Permit 15040646
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-05-06 Cont ID  
Sent By jwitmer Date 2015-05-06 Time 05:59 Rev Time 0.00
Received By jwitmer Date 2015-05-05 Time 15:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-15 Cont ID  
Sent By skennedy Date 2015-05-15 Time 10:13 Rev Time 0.00
Received By skennedy Date 2015-05-15 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-21 Cont ID  
Sent By pleduc Date 2015-04-21 Time   Rev Time 0.00
Received By pleduc Date 2015-04-21 Time 12:46 Sent To  
Notes
2015-04-21 13:04:23THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) ON SHEET T THERE ARE INCORRECT REFERENCES TO THE
 FIRE CODE: THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-15 Cont ID  
Sent By skennedy Date 2015-05-15 Time 10:15 Rev Time  
Received By skennedy Date 2015-04-17 Time   Sent To  
Notes
2015-04-18 07:31:52C16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-05-06 Cont ID  
Sent By jwitmer Date 2015-05-06 Time 05:59 Rev Time 0.00
Received By jwitmer Date 2015-05-06 Time 05:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-06 Cont ID  
Sent By jwitmer Date 2015-05-06 Time 05:59 Rev Time  
Received By jwitmer Date 2015-05-06 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-05-15 Cont ID  
Sent By skennedy Date 2015-05-15 Time 10:14 Rev Time 0.00
Received By skennedy Date 2015-05-15 Time 10:14 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved