2015-04-29 11:13:10 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | COMMENTS: | | | | 1) THE RISER DIGRAM INDICATES A 200AMP MAIN FEEDING A | | 100AMP PANEL. PROVIDE A CIRCUIT DIRECTORY FOR THE | | METER/MAIN COMBO PANEL. INDICATE THE OCPD FEEDING THE | | EXISTING 100AMP PANEL. NEC 408.4, | | 2) INDICATE TWO GROUNDING ELECTRODES. NEC 250.56 | | 3) PROVIDE THE FEEDER SIZE AND TYPE FEEDING THE | | EXISTING 100AMP PANEL. WPB AMENDMENTS TO FBC | | 107.3.5.1.2 | | 4) PROVIDE THE REQUIRED INTERSYSTEM BONDING DEVICE. | | NEC250.94 | | 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | INTERRUPTED. NEC 110.9 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-05-02 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-05-02 |
Time |
14:42 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-04-30 |
Time |
15:52 |
Sent To |
|
|
Notes |
2015-04-30 15:52:40 | TO DAH DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-04-29 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-04-29 |
Time |
10:51 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-04-23 |
Time |
12:29 |
Sent To |
|
|
Notes |
2015-04-23 12:29:28 | ROUTED TO ELECTRIC $5000 & UNDER |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |