Plan Review Details - Permit 15040559
Plan Review Stops For Permit 15040559
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-17 Cont ID  
Sent By dhayes Date 2015-04-17 Time 11:09 Rev Time 0.00
Received By dhayes Date 2015-04-17 Time 11:09 Sent To  
Notes
2015-04-17 11:15:281) ROMEX APPROVED FOR INSTALLATION SLEVED IN PVC
 CONDUIT BUT AN APPROVED BUSHING IS REQUIRED WHER THE
 CABLE EXITS THE RACEWAY. NEC 334.15(C)
  
 2) NMC ROMEX IS APPROVED FOR DAMP LOCATION. TYPE NM
 ROMEX IS ONLY APPROVED FOR DRY LOCATION. NEC
 334.10(B)(1)
  
 3) #2CU GROUNDING ELECTRODE CONDUCTOR REQUIRED DUE TO
 SIZE OF THE SERVICE ENTRANCE CONDUCTORS. NEC 250.66
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-16 Cont ID  
Sent By dhayes Date 2015-04-16 Time 13:35 Rev Time 0.00
Received By dhayes Date 2015-04-16 Time 13:35 Sent To  
Notes
2015-04-16 14:09:091) THE TYPE AND SIZE OF ROMEX PROPOSED IS NOT CLEAR.
 PLEASE CLARIFY THE TYPE AND SIZE OF CABLE THAT IS
 PROPOSED FOR THE INSTALLATION OF THE FEEDER FROM THE
 SERVICE DISCONNECT TO THE PANEL. THE SIZE APPEARS TO BE
 INDICATED AS #6-3-2 + GRD. PLEASE BE MORE SPECIFIC AS
 TO HOW MANY CONDUCTOR CABLE THIS IS .
  
 2) THE TYPE OF CONDUCTORS FOR THE 100AMP UNIT #1 ARE
 NOT SHOW. PLEASE IDENTIFY THE TYPE OF CONDUCTORS
 PROPOSED TO BE INSTALLED FROM THE SERVICE DISCONNECT TO
 THE PANEL IN UNIT #1
  
 3) THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR IS
 INDICATED TO BE A #6 SOLID. THE GEC IS BASED ON THE
 SIZE AND TYPE OF THE SERVICE ENTRANCE CONDUCTORS
 HOWEVER THE SERVICE ENTRANCE CONDUCTORS SIZE AND TYPE
 IS NOT SHOWN ON THIS PLAN. PROVIDE THE SIZE AND TYPE OF
 THE SERVICE ENTRANCE CONDUCTORS AND GEC
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-17 Cont ID  
Sent By dhayes Date 2015-04-17 Time 11:09 Rev Time 0.00
Received By dhayes Date 2015-04-17 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-16 Cont ID  
Sent By dhayes Date 2015-04-16 Time 13:56 Rev Time 0.00
Received By dhayes Date 2015-04-15 Time 13:35 Sent To  
Notes
***NONE***