Plan Review Details - Permit 15040521
Plan Review Stops For Permit 15040521
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-04-20 Cont ID  
Sent By Mgonzale Date 2015-04-20 Time   Rev Time 1.00
Received By mgonzale Date 2015-04-20 Time   Sent To P
Notes
2015-04-20 18:56:20PASSED WITH PROVISO:
  
 #1 THE INTERCEPTORS SHALL BE SIZED AND INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS AMD
 REQUIREMENTS OF THE FLORIDA PLUMBING CODE.
  
 #2 ANY STRUCTURAL ELEMENT, SLAB, COVERING PLATE, ACCESS
 DOOR, TRAFFIC-RATED LIDS OR ANY OTHER ELEMENT TO BE
 INSTALLED AND IS NOT WITHIN THE MANUFACTURER'S
 INTRUCTIONS FOR THE INTERCEPTORS WILL BE REQUIRED THAT
 A LICENSED FLORIDA PROFESSIONAL ENGINEER DESIGN AND
 SIZE IN ACCORDANCE WITH THE APPLICABLE BUILDING CODE,
 STATE REGULATION, AND CITY OF WPB CODES AND ORDINANCES.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-21 Cont ID  
Sent By tklarge Date 2015-04-21 Time 08:33 Rev Time 0.00
Received By tklarge Date 2015-04-16 Time 06:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-21 Cont ID  
Sent By tklarge Date 2015-04-21 Time 08:33 Rev Time 0.00
Received By tklarge Date 2015-04-21 Time 08:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-16 Cont ID  
Sent By tklarge Date 2015-04-16 Time 07:04 Rev Time 0.00
Received By tklarge Date 2015-04-16 Time 06:32 Sent To  
Notes
2015-04-16 07:04:441) THE INTERCEPTOR DETAIL DOES NOT SHOW THE INLET AND
 OUTLET PIPING DETAILS PER THE 2010 FPC SEC.1003.5.3.
 2) THE CONTRACTOR STATED TO ME THAT THE EXISTING TANKS
 ARE 2450 GALLONS BUT THESE TANKS ARE 3,000 GALLONS.
 CLARIFY. THE 2010 FL. PLUMBING CODE SEC.1003.5.1 STATES
 THE MAXIMUM VOLUME OF AN INDIVIDUAL GREASE INTERCEPTOR
 CHAMBER SHALL BE 1250 GALLONS.WHEN THE CAPACITY IS
 GREATER THAN 1250 GALLONS, THEY SHALL BE INSTALLED IN
 SERIES. SUBMIT DOCUMENTATION FROM THE HOSPITAL
 CONFIRMING THE CAPACITY OF THE EXISTING TANKS ( A
 RECENT PUMP-OUT BILL THAT SPECIFIES THE CAPACITY WILL
 SUFFICE).
 3) TWO DIFFERENT TANK SPECIFICATIONS HAVE BEEN
 SUBMITTED AND THEY REFERENCE TWO DIFFERENT STATE
 APPROVAL NUMBERS.CLARIFY. SUBMIT A COPY OF THE STATE
 APPROVAL OF THE TANK THAT WILL BE INSTALLED.WPB
 AMENDMENTS TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  