Plan Review Details - Permit 15040498
Plan Review Stops For Permit 15040498
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-01 Cont ID  
Sent By shill Date 2015-06-01 Time 13:22 Rev Time 0.00
Received By shill Date 2015-06-01 Time 13:22 Sent To  
Notes
2015-06-01 13:25:08PROVISO
  
 ONLY COVER SHEET, C5 AND DOT SIGN DETAILS ARE
 APPLICABLE TO THIS PROJECT
  
 PER CONVERSATION WITH ENGINEER, THE SIGNS COMPLY WITH
 FBC 1609 (RESISTANCE TO WIND)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-05 Cont ID  
Sent By shill Date 2015-05-05 Time 13:04 Rev Time 0.00
Received By shill Date 2015-05-05 Time 13:04 Sent To E
Notes
2015-05-05 13:11:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A SITE PLAN WHICH SHOWS LOCATION OF PROPOSED
 SIGNS, FBC 107.
  
 2. REMOVE SHEETS NOT APPLICABLE TO THIS PROJECT. SCOPE
 IS NOT CLEAR. IF THIS IS FOR THE ACCESSIBLE PARKING
 SIGNAGE, THAT SCOPE IS INCLUDED IN THE PAVING PERMIT.
  
 3. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. VALUE TO INCLUDE LABOR, MATERIALS, OVERHEAD,
 PROFIT, ENGINEERING.
  
 4. PLEASE CONFIRM THAT THE PLANS FOR THE PROPOSED SIGNS
 INCLUDE WIND DESIGN CRITERIA FBC 1609 (**TOLD
 CONTRACTOR THAT THIS COULD BE A PROVISO ITEM**).
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-05-21 Cont ID  
Sent By shill Date 2015-05-21 Time 16:28 Rev Time 0.00
Received By dhayes Date 2015-05-21 Time 16:28 Sent To B
Notes
2015-05-21 16:36:405/21/2015
  
 AN ELECTRICAL PERMIT IS NOT APPLICABLE TO THIS
 APPLICATION. THE ELECTRICAL SHEETS INCLUDED WITH THE
 APPLICATION HAVE BEEN MARKED VOID. THESE ELECTRICAL
 PLANS WERE A PART OF ELECTRICAL SUB: PERMIT # 15010822
 TO ?INSTALL SITE LIGHTING? RESULT: "FINAL APPROVED"
 05/08/2015
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-09 Cont ID  
Sent By dhayes Date 2015-05-09 Time 16:17 Rev Time 0.00
Received By dhayes Date 2015-05-09 Time 16:04 Sent To  
Notes
2015-05-09 16:17:08REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 PLEASE KEEP THE FOLLOWING ELEMENTS IN MIND WHEN
 PREPARING YOUR SIGNAGE DESIGN DOCUMENTS:
  
 1) PROVIDE PLANS WITH A CLEARLY DEFINED SCOPE OF WORK.
 THE PERMIT APPLICATION STATES THE PURPOSE TO BE FOR THE
 INSTALLATION OF SIGNAGE. THE PLANS HOWEVER INDICATE
 POLES FOR CAMERAS AND FIBER OPTICS, AND DO NOT APPEAR
 TO INDICATE ANYTHING RELATED TO THE INSTALLATION OF
 SIGNAGE.
  
 2) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING,
 FIXED, MOBILE, OR PORTABLE, SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3
 LISTING.
  
 3) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 4) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 5) PROVIDE PROOF OF OVERALL VALUE OF THE PROJECT IS
 REQUIRED AND SHALL BE THE TOTAL REPLACEMENT VALUE TO
 INCLUDE ARCHITECTURAL DESIGN FEES, FABRICATION,
 STRUCTURAL, AND ELECTRICAL, PLUS OVERHEAD AND PROFIT.
 FINAL PERMIT VALUATION SHALL BE SET BY THE BUILDING
 OFFICIAL. FBC WPB AMENDMENTS. SECTION 109.3
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-01 Cont ID  
Sent By shill Date 2015-06-01 Time 13:25 Rev Time 0.00
Received By shill Date 2015-05-11 Time   Sent To  
Notes
2015-05-11 17:27:35SENT TO ZONING BOX TO E. SNIDER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-09 Cont ID  
Sent By dhayes Date 2015-05-09 Time 16:17 Rev Time 0.00
Received By dhayes Date 2015-04-14 Time 11:23 Sent To  
Notes
2015-05-05 13:11:295/5 TO ELEC BOX
  
2015-04-14 11:23:10ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-20 Cont ID  
Sent By eschneid Date 2015-05-20 Time 13:53 Rev Time 0.25
Received By eschneid Date 2015-05-20 Time 13:53 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-04-20 Cont ID  
Sent By eschneid Date 2015-04-20 Time 18:34 Rev Time 0.25
Received By eschneid Date 2015-04-20 Time 18:34 Sent To B
Notes
2015-04-20 18:43:20FAILED
  
 1) A SURVEY/SITE PLAN SHOWING THE SIGN LOCATIONS ALONG
 JOG ROAD WHICH INCLUDES THE SWA PROPERTY LINE.
  
 2) IF THE SIGNS ARE LOCATED ON THE SWA PARCEL, THEN A
 MINIMUM FIVE (5) FOOT SETBACK IS REQUIRED FROM THE JOG
 ROAD PROPERTY LINE.
  
 3) IF THE SIGNS ARE LOCATED WITHIN THE JOG ROAD
 RIGHT-OF-WAY, THEN THE SIGNS SHALL BE PERMITTED BY PALM
 BEACH COUNTY AND NOT SHOWN ON THE PLANS (SPECIFICALLY
 SHEET C-5).
  
 4) PROVIDE THE HEIGHT OF THE SIGNS LOCATED ON THE
 SCALEHOUSE AND ENTRANCE ROAD TO THE DROP OFF AREA.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.