Plan Review Details - Permit 15040433
Plan Review Stops For Permit 15040433
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-04 Cont ID  
Sent By albarran Date 2015-06-04 Time 15:05 Rev Time 0.00
Received By albarran Date 2015-06-04 Time 14:27 Sent To I
Notes
2015-06-04 15:05:30APPROVED AS NOTED:
 ELECTRICAL PROVISO:
 PER NEC 422.52 ELECTRIC WATER FOUNTAINS SHALL BE ON GFI
 PROTECTED CIRCUIT.
 PER 406.8 RECEPTACLES INSTALLED OUTDOORS SHALL BE RATED
 WEATHER RESISTANT (WR).
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-15 Cont ID  
Sent By dhayes Date 2015-04-15 Time 10:18 Rev Time 0.00
Received By dhayes Date 2015-04-15 Time 10:18 Sent To  
Notes
2015-04-15 10:26:28THERE ARE NO ELECTRICAL PLANS OR PERMIT INCLUDED IN
 THIS SUBMITTAL. THERFORE THERE HAS BEEN NO ELECTRICAL
 REVIEW PERFORMED AT THIS TIME. THIS IS AN ELECTRICAL
 DRINKING FOUNTAIN AND AS SUCH REQUIRES AN ELECTRICAL
 PERMIT APPLICATION FROM A REGISTERRED ELECTRICAL
 CONTRACTOR ALONG WITH TWO COPIES OF AN ELECTRICAL PLAN
 INDICATING THE REQUIRED CIRCUIT CONNECTED TO A GFI
 OUTLET FOR THE SUPPLY TO THE UNIT. PLEASE PROVIDE THE
 REQUIRED DOCUMENTATION.
  
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6717 OR [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-04 Cont ID  
Sent By albarran Date 2015-06-04 Time 15:13 Rev Time 0.00
Received By albarran Date 2015-05-19 Time 08:42 Sent To  
Notes
2015-06-04 15:14:37APPROVED ELECTRIC; SENT TO SMALL READY BIN "P".
2015-05-20 08:42:48RE-SUBMITTAL SENT TO TIM LARGE FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-15 Cont ID  
Sent By tklarge Date 2015-04-15 Time 10:05 Rev Time 0.00
Received By tklarge Date 2015-04-15 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-21 Cont ID  
Sent By tklarge Date 2015-05-21 Time 06:23 Rev Time 0.00
Received By tklarge Date 2015-05-21 Time 03:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-15 Cont ID  
Sent By tklarge Date 2015-04-15 Time 10:05 Rev Time 0.00
Received By tklarge Date 2015-04-15 Time 09:25 Sent To  
Notes
2015-04-15 10:05:201) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE
 PLUMBING WORK TO BE DONE. SHOW ORIGINATION AND
 TERMINATION POINTS OF ALL PIPING AND PIPE SIZES. WPB
 AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 2) THE DOCUMENT SUBMITTED FROM LIBERTY PUMPS IS LACKING
 INFORMATION REQUIRED BY THE PLUMBING CODE. REFER TO THE
 2010 FL. PLUMBING CODE SECS.712.3.2 FOR THE MINIMUM
 SIZE OF THE SUMP PIT.
 3) THE SUMP PIT SHALL BE VENTED PER FPC SEC.712.3.2 AND
 CHAPTER 9.
 4) THE EJECTOR PIPING SHALL CONNECT TO THE DRAINAGE
 SYSYTEM IN ACCORDANCE WITH THE 2010 FPC SEC. 712.3.5.
 5) THE MINIMUM CAPACITY OF THE PUMP SHALL COMPLY WITH
 TABLE 712.4.2.
 6) SUBMIT MANUF. SPECIFICXATIONS FOR THE PUMP.
 7) DRINKING FOUNTAINS SHALL COMPLY WITH FL.
 ACCESSIBILITY CODE SECS. 305 & 602.2 FOR CLEAR FLOOR
 SPACE REQS.
 8) THE PLACEMENT OF THE DRINKING FOUNTAIN SHALL NOT
 INTERFERE WITH THE APPROACH TO THE DOOR FROM THE
 EXTERIOR FOR HANDICAP ACCESSIBILTY MANEUVERING
 CLEARANCES.. A MINIMUM OF 18 INCHES CLEARANCE SHALL BE
 PROVIDED ADJACENT TO THE LATCH SIDE OF THE DOOR.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  