Plan Review Details - Permit 15040413
Plan Review Stops For Permit 15040413
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-04-26 Cont ID  
Sent By jwitmer Date 2015-04-26 Time 07:00 Rev Time  
Received By jwitmer Date 2015-04-26 Time 06:20 Sent To  
Notes
2015-04-26 07:01:05REVISION: DELTA # 1 DATED 2/18/2015

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-05-12 Cont ID  
Sent By rlecky Date 2015-05-12 Time 13:40 Rev Time 0.00
Received By rlecky Date 2015-05-12 Time 13:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-27 Cont ID  
Sent By scaldero Date 2015-04-27 Time 13:36 Rev Time 0.00
Received By scaldero Date 2015-04-27 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-23 Cont ID  
Sent By tklarge Date 2015-05-23 Time 13:42 Rev Time 0.00
Received By tklarge Date 2015-05-21 Time   Sent To  
Notes
2015-05-22 16:59:27SENT TO T LARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-15 Cont ID  
Sent By ccole Date 2015-05-15 Time 12:49 Rev Time 0.00
Received By ccole Date 2015-04-13 Time 16:36 Sent To  
Notes
2015-04-13 16:36:42C06
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-05-15 Cont ID  
Sent By ccole Date 2015-05-15 Time 12:47 Rev Time 0.00
Received By ccole Date 2015-04-13 Time 12:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-23 Cont ID  
Sent By tklarge Date 2015-05-23 Time 13:42 Rev Time 0.00
Received By tklarge Date 2015-05-23 Time 13:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-05-10 Cont ID  
Sent By tklarge Date 2015-05-10 Time 08:10 Rev Time 0.00
Received By tklarge Date 2015-05-10 Time 07:15 Sent To  
Notes
2015-05-10 08:09:021) SHT. P2.0 - THE MAXIMUM SQUARE FOOTAGE PERMITTED ON
 AN 8 INCH HORIZONTAL STORM DRAIN IS 9,200 SQ. FT. BASED
 ON 5 INCH RAINFALL PER TABLE 1106.3 OF 2010
 FBC-PLUMBING. THE PLAN IS SHOWING 12,200 SQ. FT. INTO
 EACH DRAIN. IS THIS NUMBER A TYPOGRAPHICAL ERROR? THE
 EXISTING PLANS SHOW A LOT LESS SQUARE FOOTAGE DRAINING
 INTO THESE DRAINS.
 2) SHT.A1.7 SHOW THESE DRAINA AS EXISTING BUT THE
 EXISTING PLANS AND THIS PLAN APPEARS TO SHOW THEM AS
 NEW. CLARIFY.
 3) AIR CONDITIONING DRAINS THAT DISCHARGE INTO ROOF
 DRAINS SHALL BE ADDED AS EACH GPM = 96 SQUARE FEET PER
 AIR CONDITIONING DRAIN PER 2010 FBC-PLUMBING
 SEC.1109.1. THIS SHALL BE SHOWN ON THE CALCULATIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  